OPEN FRAME & ENCLOSED
NAC
A C F I LT E R
Features
• • • • • High-attenuation type of common mode noise from 150kHz to 1MHz. Single Phase 250Vac. Selectable leakage current. Quick and easy push down terminal. Din rail installation type (Option).
Specifications
INPUT
Voltage Test voltage (Terminal-mounting plate) Isolation resistance (Terminal-mounting plate) 250Vac/250Vdc, 1 phase 2.5kVac (cutoff current = 20mA), 1 minute at room temperature and humidity. 500Vdc, 100MW minute at room temperature and humidity.
Ordering Information
NAC (1) -10 (2) -472 (3) _ (4)
OUTPUT
Current Leakage current Voltage drop See table. 0.5mA/1.0mA (125/250Vac, 60Hz) 1.0V max
1. Model name 2 Rated current 3. Line to ground capacitor code 4. Options D: Din rail installation type.
CODE
06 10 16 20 30
CURRENT
6A 10A 16A 20A 30A
ENVIRONMENTAL
Safety agency approval Temperature Operating temperature Storage temperature Humidity Vibration Impact -25°C to 85°C (Refer to derating curve). -40°C to 85°C (Refer to derating curve). -40°C to 85°C 20% to 95% RH (Non-condensing) 10 to 55Hz, 19.6m/s2 (2G), 3min. Period, 1 hour each X, Y and Z axis. 196.1m/s2 (20G), 11ms once each X, Y and Z axis.
CODE
681 102 222
LEAKAGE CURRENT(INPUT 125/250V 60HZ)
75.5mA / 150mA max 0.13mA / 0.25mA max 0.25mA / 0.5mA max 0.38mA / 0.75mA max
LINE TO GROUND CAPACITOR(NOMINAL VALUE)
680pF 1000pF 2200pF 3300pF
STANDARDS
Safety C-tick UL1283, CSA C 22.2 No. 8 (C-UL), DIN EN133200 VDE0565 Teil3-1, ENEC (At only AC input). AS/NZS CISPR11 Group 1, Class A
332
472 0.5mA / 1.0mA max 4700pF When the line to ground capacitor code is different, the attenuation characteristic is different.