OPEN FRAME & ENCLOSED
NAP
A C F I LT E R
Features
• • • • • High-voltage pulse high attenuation type. Single Phase 250Vac. Selectable leakage current. Quick and easy push down terminal. Din rail installation type (Option).
Specifications
INPUT
Voltage Test voltage (Terminal-mounting plate) Isolation resistance (Terminal-mounting plate) 250Vac/250Vdc, 1 phase 2.5kVac (cutoff current = 20mA), 1 minute at room temperature and humidity. 500Vdc, 100MW minute at room temperature and humidity.
Ordering Information
NAM (1) -10 (2) -000 (3) _ (4)
OUTPUT
Current Leakage current Voltage drop See table. 5mA/10mA max (125/250Vac, 60Hz) 1.0V max
1. Model name 2. Rated current 3. Line to ground capacitor code 4. Options D: Din rail installation type.
CODE
04 06 10 16 20 30
CURRENT
4A 6A 10A 16A 20A 30A
ENVIRONMENTAL
Safety agency approval Temperature Operating temperature Storage temperature Humidity Vibration Impact -25°C to 85°C (Refer to derating curve). -40°C to 85°C (Refer to derating curve). -40°C to 85°C 20% to 95% RH (Non-condensing) 10 to 55Hz, 19.6m/s2 (2G), 3min. Period, 1 hour each X, Y and Z axis. 196.1m/s2 (20G), 11ms once each X, Y and Z axis.
CODE
000 101 221
LEAKAGE CURRENT(INPUT 125/250V 60HZ)
5mA / 10mA max 12.5mA / 25mA max 25mA / 50mA max 37.5mA / 75mA max 50mA / 100mA max 75.5mA / 150mA max 0.13mA / 0.25mA max 0.25mA / 0.5mA max 0.38A / 0.75mA max 0.5mA / 1.0mA max
LINE TO GROUND CAPACITOR(NOMINAL VALUE)
Not Provided 100pF 220pF 330pF 470pF 680pF 1000pF 2200pF 3300pF 4700pF
STANDARDS
Safety UL1283, CSA C 22.2 No. 8 (C-UL), DIN EN133200 VDE0565 Teil3-1, ENEC (At only AC input).
331 471 681 102 222 332 472
When the line to ground capacitor code is different, the attenuation characteristic is different.