M
C O N V ER
T
Input
Output Voltage
Voltage Range
Factory Set
[VAC]
[VDC]
Output Voltage
Range
[VDC]
80-264
24
24-28
50
95
RACM1200-36SAV/ENC
80-264
36
30-36
40
95
RACM1200-48SAV/ENC
80-264
48
48-56
25
95
Notes:
Note1: Efficiency is tested at nominal input and 40-60% load at +25°C ambient temperature
Accessible Part
RAC-MB1
Description
Datasheet Link
mounting bracket
RAC-MB1.pdf
Model Numbering
RACM1200-__ S AV/ENC/PMB
Peak Output Power
Nom. Output Voltage
Single
TS
C
D
IA N
T PRO
U
CO NVE R
T
REACH
compliant
M
P
ERP
compliant
LOT6
U
LIA
D
N T PRO
Max. Output Efficiency
Current
typ. (1)
[A]
[%]
RACM1200-24SAV/ENC
Part Number
PL
M
S
M
O
CO
Part
Number
CO
Selection Guide
10 from 10
C
R
S
RoHS 2 +
compliant
E
O
R
C
E
RE
1200 Watt
9” x 3.8”
Enclosed
Single Output
TS
Description
The RACM1200-V series is setting a new benchmark for compactness in the class of AC power
supplies for reliable fan-less operation supporting long term system availability. A special baseplate
cooled design supports heat transfer to allow up to 1000W continuous output power. Up to 1200 Watt
output power is available for up to 10 seconds and in boost mode operation or for extended time with
sufficient system airflow through the unit. A wide output voltage adjustment range and a combination
of constant current limitation and hiccup mode settings makes the product multipurpose. The various
analogue control and monitoring functions are accessible via connector. Optional firmware settings
available on project base. The RACM1200-V Series can be limited to inherently fail-safe settings on
request, using smart, controlled, fault-limiting functions. Only the /PMB Variant supports default settings
ex factory to be adjusted, and warning signals to be adopted. An adjustable 12V system FAN output
and a 1.5kVAC isolated auxiliary stand by output of 5VSB/1A are available to power the application’s
housekeeping functions. Peak efficiency reaches up to 95% and in standby mode, the unit is
compliant to ecodesign requirements. The product holds worldwide safety files to medical, industrial and
ITE standards along with electromagnetic compatibility compliance with class A immunity and class B
emissions. Spring stainless steel mounting brackets are available separately for a perfect fixation when
mounting over the top of the base plate is preferred. All these features make the product one of the
easiest to integrate modular power solutions in the industry.
RACM1200-V
C
Regulated
Converter
AC/DC Converter
RE
• Up to 1000 Watt fan-less power / 1200W boost
• Designed and manufactured in europe
• Efficiency exceeding 90% from 15% load
• Wide Operating temperature range -40…+80°C
• Certified to Industrial, and medical standards
• Analogue control & monitor function
• Custom Variants
Features
PMBus function (2)
E224736
2MOPP
250VAC
IEC/EN62368-1 certified
UL62368-1 certified
CAN/CSA-C22.2 No. 62368-1 certified
IEC/EN60601-1 certified
ANSI/AAMI ES60601-1 certified
UL8750 (48V only) certified
IEC/EN61347-1 (pending)
IEC/EN61347-2-13 (pending)
IEC/EN61558-1/2 compliant (9)
IEC61010-1/-2-201 compliant (10)
IEC/EN60601-1-2 compliant
EN55032/35 compliant
EN55024 compliant
CB Report
Enclosed Case Style
VSB Auxiliary Output Voltage (5VDC)
Notes:
Note2: with suffix “/PMB” PMBus option is built-in (available with 24V and 48V Versions)
For master commands please refer to link: PMBus_mastercommands.pdf
www.recom-power.com
REV.: 4/2023
PA-1
RACM1200-SAV
Series
AC/DC Converter
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
BASIC CHARACTERISTICS
Parameter
Condition
Min.
Nominal Input Voltage
60/50Hz
100VAC
240VAC
Operating Range
47-63Hz
80VAC
264VAC
Input Current
according to CB report
Inrush Current
cold start at +25°C, 230VAC
Typ.
Max.
11.5A
No load Power Consumption
MAIN output REMOTE ON
Standby Power
MAIN output REMOTE OFF
14A
25A
2W
1W
Minimum Load
0%
refer to ”Power Factor”
Power Factor
5VSB Aux.
refer to “SIGNALS”
Start-up Time
Hold-up Time
500ms
FAN
750ms
1.5s
MAIN, 800W, 85-264VAC (-25°C to +70°C)
750ms
1.5s
800W
20ms
20MHz BW, valid for MAIN, 5VSB, FAN
Output Ripple and Noise (3)
1% of nom. Vout
Notes:
Note3: Measurements are made with a 0.1μF MLCC & 10μF E-cap in parallel across output. (low ESR)
Efficiency vs. Load
Power Factor
1.1
90
1
80
0.9
Power Factor [ ]
Efficiency [%]
100
70
60
50
40
0.7
0.6
0.5
0.2
20
0.1
10
0
0
0
115VAC
240VAC
0.4
0.3
115VAC
240VAC
30
0.8
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
Output Load [W]
100 200 300 400 500 600 700 800 900 1000 1100 1200
Output Load [W]
Power Dissipation
100
Power Dissipation [W]
90
80
70
60
50
40
30
20
115VAC
240VAC
10
0
0
100 200 300 400 500 600 700 800 900 1000 1100 1200
Output Load [W]
www.recom-power.com
REV.: 4/2023
PA-2
RACM1200-SAV
Series
AC/DC Converter
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
REGULATIONS
Parameter
Condition
Set Point Accuracy
Total Regulation
Value
MAIN
±1.0% max.
5VSB / FAN
±5.0% max.
line, load and temperature drift
MAIN & FAN
±2.0% max.
5VSB Aux.
±5.0% max.
ADDITIONAL FEATURES
Parameter
Condition
5VSB Stand By Output Voltage
Min.
1A
24Vout type (100mV steps)
Remote ON/OFF
Max.
5VDC
always on
5VSB Stand By Output Current
Output Voltage Adjustability
Typ.
24VDC
28VDC
tactile button push up/down 36Vout type (150mV steps)
30VDC
36VDC
48Vout type (200mV steps)
48VDC
56VDC
maximum allowed voltage referenced to SIGNAL RTN
FAN Output Voltage adjustment
via FAN ADJ Pin #6 @ TTL levels
5VDC
OFF
CTRL= 2.5VDC
CTRL= 2.2VDC...0VDC or open
5VDC
FAN Output Current
ON/OFF with MAIN channel
12VDC
1A
“Remote Sense”
differential mode, cable loss compensation
500mV
Parallel Operation
please get in touch with your RECOM contact
on request
Green continuously
PSU-Good: PSU in standard operation mode
Blue intermittent (30% on)
STBY: Standby mode; MAIN Output OFF via REMOTE signal
Green intermittent (50% on)
DC-LOW: Signal: {75%