!NOT RECOMMENDED FOR NEW DESIGNS!
Features
• Long 5 year warranty
• 2MOPP/250VAC
AC/DC Converter
• Suitable for built in Class II applications
• Wide input voltage range (85-264VAC)
Regulated
Converter
• Low leakage current (8.0mm
>8.0mm
Notes:
Note5: For repeat Hi-Pot testing, reduce the time and/or the test voltage
ENVIRONMENTAL
Parameter
Condition
Value
refer to ”Derating Graph”
Operating Temperature Range
full load, 230VAC
enclosed
open frame
Temperature Coefficient
5000m max.
non-condensing
Pollution Degree
5% to 95% RH
PD2
High Temperature Operating Life (HTLO)
JEDEC JESD22-A108
Shock
IEC60068-2-27
Vibration
MTBF
-25°C to +60°C
-25°C to +55°C
±0.02%/K
Operating Altitude
Operating Humidity
-25°C to +85°C
IEC60068-2-6
according to MIL-HDBK-217F, full load, +25°C
790.3 x 103 hours
continued on next page
www.recom-power.com
REV.: 12/2022
MED-3
! NOT RECOMMENDED FOR NEW DESIGNS !
RACM100
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, 250VAC, full load and after warm-up)
Derating Graph
(@ Chamber and natural convection 0.1m/s)
/OF version
100
90
90
80
80
70
70
Output Load [%]
Output Load [%]
Enclosed
100
60
50
40
30
50
40
30
20
10
60
20
115VAC
230VAC
0
-25 -20 -10 0
115VAC
230VAC
10
0
-25 -20 -10 0
10 20 30 40 50 60 70 80 90 100 110
55
85
Ambient Temperature [°C]
10 20 30 40 50 60 70 80 90 100 110
85
55
Ambient Temperature [°C]
SAFETY AND CERTIFICATIONS
Certificate Type (Safety)
Report / File Number
Medical Electric Equipment, General Requirements for Safety and Essential Performance
E314885
Medical Electric Equipment, General Requirements for Safety and Essential Performance (CB)
181200102
Medical Electric Equipment, General Requirements for Safety and Essential Performance
Information Technology Equipment - General Requirements for Safety (LVD)
TW1708008-001
Information Technology Equipment - General Requirements for Safety
EAC
RU-AT.49.09571
RoHS2
Standard
CAN/CSA-C22.2 No. 60601-1:14
ANSI/AAMI ES60601-1:2005 + A2:2010
IEC60601-1:2005 + A1:2012, 3rd Edition
EN60601-1:2006 +12:2014
EN60950-1:2006 + A2:2013
IEC60950-1:2005, 2nd Edition + A2:2013
TP TC 004/2011 TP TC 004/2011
RoHS-2011/65/EU + AM-2015/863
EMC Compliance (Medical)
Conditions
Standard / Criterion
Medical electrical equipment - Part 1-2: General requirements for basic safety and essential
performance - Collateral standard: Electromagnetic compatibility - Requirements and tests
EN60601-1-2:2015
Industrial, scientific and medical equipment – Radio frequency disturbance characteristics –
Limits and methods of measurement
EN55011:2009 + A1:2010
Class B Conducted, Class A Radiated
Industrial, scientific and medical equipment - Radio frequency disturbance characteritics Limits and methods of measurement
CISPR11:2009 + A1:2010
Class B Conducted, Class A Radiated
ESD Electrostatic discharge immunity test
Radiated, radio-frequency, electromagnetic field immunity test
Air ±15kV; Contact ±8kV
IEC61000-4-2:2008
10V/m (80-2700MHz)
27V/m (385MHz)
28V/m (450MHz)
IEC61000-4-3:2006 + A2:2010
Fast Transient and Burst Immunity
AC Power Port: ±2kV
IEC61000-4-4:2012
Surge Immunity
AC
Port:
IEC61000-4-5:2005
Immunity to conducted disturbances, induced by radio-frequency fields
Power Frequency Magnetic Field
Voltage Dips and Interruptions
Limits of Harmonic Current Emissions
L-N= ±1kV
L-GND= ±2kV
6Vr.m.s
IEC61000-4-6:2013
50Hz, 30A/m
IEC61000-4-8:2009
Dips: >95%; 30%;
Interruptions >95%
IEC61000-4-11:2004
EN61000-3-2:2005 + A2:2009, Class D
Limits of Voltage Fluctuations and Flicker
EN61000-3-3:2013
continued on next page
www.recom-power.com
REV.: 12/2022
MED-4
! NOT RECOMMENDED FOR NEW DESIGNS !
RACM100
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, 250VAC, full load and after warm-up)
EMC Compliance (Industrial)
Conditions
Standard / Criterion
47CFR FCC Part 15 Subpart B, Class B
Limitations on the amount of electromagnetic intererence allowed from digital & electronic devices
Methods of Measurement of Radio-Noise Emissions from Low-Voltage Electrical and
Electronic Equipment in the Range of 9 kHz to 40 GHz
ANSI C63.4:2014
Electromagnetic compatibility of multimedia equipment – Emission Requirements
EN55032:2015+AC:2013, Class B
Information technology equipment - Immunity characteristics - Limits and methods of
measurement
EN55024:2010+A1:2015
ESD Electrostatic discharge immunity test
Air ±8kV; Contact ±6kV
IEC61000-4-2:2008, Criteria A
Radiated, radio-frequency, electromagnetic field immunity test
3V/m (80-1000MHz)
20V/m (80-1000MHz)
3V/m (1-2.5GHz)
10V/m (1-2.5GHz
IEC61000-4-3:2006 + A2:2010, Criteria A
Fast Transient and Burst Immunity
DC Port: ±2kV
IEC61000-4-4:2012, Criteria A
Surge Immunity
DC Port: ±1kV
IEC61000-4-5:2014, Criteria A
DC Power Port 3V + 20V
IEC61000-4-6:2013, Criteria A
50Hz/60Hz 1A/m
50Hz/60Hz 10A/m
IEC61000-4-8:2009, Criteria A
Dips: >95%; 60%; 30%
Interruptions >95%
IEC61000-4-11:2004, Criteria A
IEC61000-4-11:2004, Criteria B
Immunity to conducted disturbances, induced by radio-frequency fields
Power Frequency Magnetic Field
Voltage Dips and Interruptions
Limits of Harmonic Current Emissions
EN61000-3-2:2014, Class D
Limits of Voltage Fluctuations and Flicker
EN61000-3-3:2013
DIMENSION and PHYSICAL CHARACTERISTICS
Parameter
Material
Type
enclosed
Value
aluminum
Dimension (LxWxH)
enclsoded
open frame
91.4 x 62.0 x 39.2mm
76.2 x 50.8 x 32.0mm
Weight
enclosed
open frame
210g
150g
continued on next page
www.recom-power.com
REV.: 12/2022
MED-5
! NOT RECOMMENDED FOR NEW DESIGNS !
RACM100
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, 250VAC, full load and after warm-up)
Dimension Drawing Enclosed (mm)
24.5
Trim Adj.
62.0
FC 41.3
CON2
CON1
Top View
22.1
76.2
Connection via Connector
AC Input (CON1)
FC 84.2
91.4
Side View
Pin #
Pin Header
1 AC/L
3 AC/N
SVH-21T-P1.1
1.20
39.2
DC Output Connector (CON2)
Pin #
Pin Header
1,2 -Vout
3,4 +Vout
SVH-21T-P1.1
FC = fixing centers
Crimp Terminal AWG Range: 18-22AWG
Tolerance: ±0.5mm
3.5
10.4
10.0
14.0
Bottom View
Ø4.0
34.0
36.5
continued on next page
www.recom-power.com
REV.: 12/2022
MED-6
! NOT RECOMMENDED FOR NEW DESIGNS !
RACM100
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, 250VAC, full load and after warm-up)
Dimension Drawing Open Frame (mm)
Top View
Connection via Connector
AC Input (CON1)
CON1
Trim Adj.
18.5
CON2
FC 44.4
50.8
76.2
Ø3.2
FC 69.8
29.5
Pin #
Pin Header
1 AC/L
3 AC/N
SVH-21T-P1.1
DC Output Connector (CON2)
Pin #
Pin Header
1,2 -Vout
3,4 +Vout
SVH-21T-P1.1
FC = fixing centers
Crimp Terminal AWG Range: 18-22AWG
Tolerance: ±0.5mm
2.5
1.6
29.5
Side View
PACKAGING INFORMATION
Parameter
Packaging Dimension (LxWxH)
Packaging Quantity
Type
cardboard box
Value
enclosed case
418.0 x 258.0 x 105.0mm
open frame
494.0 x 250.0 x 95.0mm
enclosed case
open frame
Storage Temperature Range
Storage Humidity
10pcs
25pcs
-40°C to +85°C
non-condensing
5% to 95% RH
The product information and specifications may be subject to changes even without prior written notice.The product has been designed for various applications; its suitability lies in the responsibility of each customer. The
products are not authorized for use in safety-critical applications without RECOM’s explicit written consent. A safety-critical application is an application where a failure may reasonably be expected to endanger or cause
loss of life, inflict bodily harm or damage property. The applicant shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized
use of RECOM products in such safety-critical applications.
www.recom-power.com
REV.: 12/2022