FST 6,3 32
FUSES
Non resettable fuses
Miniature Fuses
Type FST 6,3 32
20 mA - 2 A
2,5 A - 20 A
time-lag T
low breaking capacity
Glass tube
1000
100
10
50
75
100
Standards
1
Approvals
none
Pre-arcing time/current
characteristic (at Ta 23 °C)
Rated
current In
n · In
2 · In
2,75 · In
4 · In
min.
10 · In
min.
max.
min.
max.
max.
min.
20 mA – 2 A
800 ms*
20 s*
150 ms*
3 s*
60 ms
1s
10 ms
200 ms
2,5 – 20 A
800 ms
20 s
200 ms
6s
80 ms
2s
15 ms
300 ms
Pre-arcing time in seconds ts
none
0,1
0,01
,001
1
max.
2
3
4 5 6
8 10
Multiple of rated current In
Non fusing current Inf = 1,15 In
* These values are not guaranteed at 20 mA
Order No.
0034.3401
0034.3402
0034.3403
0034.3404
0034.3405
0034.3406
0034.3407
0034.3408
0034.3409
0034.3410
0034.3411
0034.3412
0034.3413
0034.3414
0034.3415
0034.3416
0034.3417
0034.3418
0034.3419
0034.3420
0034.3421
0034.3422
0034.3423
0034.3424
0034.3425
0034.3426
0034.3427
0034.3428
0034.3429
0034.3430
Rated current In
Rated voltage Un
20
32
40
50
63
80
100
125
160
200
250
315
400
500
630
800
1
1,25
1,6
2
2,5
3,15
4
5
6,3
8
10
12,5
16
20
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
Breaking capacity
35 A / 250 V AC,
p.f. / cos 1
10 · In / 250 V AC
p.f. / cos 1
Voltage drop
Sustained
power dissipation
Pre-arcing
l2t
at In
at 1,15 · In
at
10 · In
max.
mV
5500
5500
5000
5000
4000
3400
2500
2000
1700
1400
1200
900
650
550
450
320
270
250
200
200
200
200
200
200
200
200
200
180
150
150
typ.
mV
2800
2700
2100
1600
1500
1100
940
890
770
840
590
200
180
140
140
140
140
100
100
90
80
80
80
80
80
120
110
100
90
100
typ.
W
0,1
0,1
0,1
0,1
0,1
0,1
0,1
0,1
0,1
0,2
0,2
0,1
0,1
0,1
0,1
0,1
0,2
0,2
0,2
0,2
0,3
0,3
0,4
0,5
0,7
1,5
1,6
1,7
2,2
3,3
A2s
on request
www.schurterinc.com
103
FST 6,3 32
FUSES
Non resettable fuses
Miniature Fuses
Type FST 6,3 32
50
75
Pre-arcing time in seconds ts
time-delay
Glass tube
100
Approvals
Standards
UL 248-14 (formerly 198.G)
CSA C22.2 No. 248.14 (formerly 59.2 M)
UL
CSA
Pre-arcing time/current
characteristic (at Ta 23 °C)
Rated
current In
n · In
1,1 · In* 1,35 · In
0,062 – 15 A
2 · In
Multiple of rated current In
min.
max.
min.
max.
4h
1h
5s
30 s
* Non fusing current Inf
0034.5204
0034.5207
0034.5208
0034.5209
0034.5211
0034.5212
0034.5213
0034.5214
0034.5215
0034.5217
0034.5219
0034.5220
0034.5223
0034.5224
0034.5225
0034.5226
0034.5227
0034.5228
0034.5229
0034.5230
0034.5231
0034.5232
0034.5233
0034.5234
0034.5235
0034.5237
0034.5238
0034.5239
0034.5241
0034.5243
0034.5244
0034.5245
0034.5246
0034.5247
63
100
125
150
175
187
200
250
300
375
500
600
750
800
1
1,2
1,25
1,5
1,6
1,8
2
2,25
2,5
2,8
3
3,2
4
5
6,25
7
8
10
12
15
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
mA / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 125 V
A / 125 V
A / 125 V
104 www.schurterinc.com
Breaking capacity
35 A /
250 V AC
p.f. / cos
0,7–0,8
100 A /
250 V AC
p.f. / cos
0,7–0,8
200 A /
250 V AC
p.f. / cos
0,7–0,8
Voltage drop
Sustained
power dissipation
Pre-arcing
l2t
at In
max.
at 1,1 In
max.
at 10 · In
mV
7500
4500
4136
3502
3150
2850
2808
2334
1950
1800
1125
1081
931
876
750
729
537
531
450
435
427
393
359
330
325
319
286
270
180
156
140
91
90
90
W
1,05
1,17
1,22
1,28
1,31
1,34
1,35
1,41
1,46
1,58
1,8
1,88
2,03
2,1
2,21
2,25
2,3
2,33
2,37
2,4
2,48
2,52
2,57
2,61
2,66
2,7
2,75
2,84
1,4
1,47
1,53
2,7
3,3
4,5
A2s
1,21 · 10–1
2,1 · 10–1
2,88 · 10–1
4,4 · 10–1
5 · 10–1
5,2 · 10–1
9,85 · 10–1
6,4 · 10–1
1,27
1,38
3,34
4,91
9,04
10,5
16,7
18,5
20,8
25
32,5
33,4
47,1
50,5
108
126
180
136
232
620
538
765
1930
Approvals
UL
CSA
Rated current In
Rated voltage Un
10 000 A / 125 V AC / p.f. / cos 0,7–0,8
Order No.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•