FMAC NEO
3-Phase AC Filters / DC Filters
https://www.schurter.com /PG80
1-stage filter for 3-phase systems
Case 4C-50
See below:
Approvals and Compliances
Description
Applications
- Terminals for three phases and ground
- 1 stage
- Very high attenuation
- Industrial or low leakage current versions
- Voltage rating 520 VAC for world wide acceptance
- Protection against interference voltage from the mains
- Especially designed for industrial applications such as: Frequency Converters, Stepper Motor Drives, UPS-Systems, Inverters
- Variants Machine Safety suitable for machine applications according to
IEC 60204-1
- Suitable for use in equipment according to IEC/UL 62368-1
Unique Selling Proposition
- Compact design with small footprint
- Single-stage filter for high efficiency
- Light weight design
- Wide temperature range
References
Weblinks
pdf data sheet, html datasheet, General Product Information, Approvals,
Distributor-Stock-Check, Detailed request for product, Microsite
Technical Data
Rated Current
Rated voltage
Approval for
Overload Current
Dielectric Strength
␣
Number of Filter Stages
Weight
Material: Housing
Sealing Compound
16 - 230 A
300/520 VAC, 50/60 Hz
16 - 230 A @ 50 °C / 300/520 VAC;
50/60 Hz
1.5 x Ir for 1 minute, per hour
> 2.25 kVDC between L-L
> 2.75 kVDC between L-PE
Test voltage 2 sec
1-stage
0.9 - 4 kg
Metal
UL 94V-0
Mounting
Terminal
Operating Temperature
Climatic Category
Degree of Protection
Protection Class
MTBF
Screw-on mounting on chassis
Screw clamps
-40 °C to 100 °C
40/100/21 acc. to IEC 60068-1
IP20 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
> 200'000 h acc. to MIL-HB-217 F
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agreements by SCHURTER.
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: FMAC NEO
Approval Logo
Certificates
Certification Body
Description
VDE Approvals
VDE
Certificate Number: 40049000
UL Approvals
UL
UR File Number: E72928
EMC Products
1
FMAC NEO
3-Phase AC Filters / DC Filters
https://www.schurter.com /PG80
Product standards
Product standards that are referenced
Organization
Design
Standard
Description
Designed according to
IEC 60939
Passive filters for suppressing electromagnetic interference
Designed according to
UL 1283
Passive filters for suppressing electromagnetic interference
Design
Standard
Description
Suitable for applications acc.
IEC/UL 62368-1
Audio/video, information and communication technology equipment - Part
1: Safety requirements
Details
Initiator
Description
CE declaration of conformity
SCHURTER AG
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
UKCA declaration of conformity
SCHURTER AG
The UKCA marking declares that the product complies with the applicable
requirements laid down in the British Amendment of Regulation (EC)
765/2008.
RoHS
SCHURTER AG
Directive RoHS 2011/65/EU, Amendment (EU) 2015/863
China RoHS
SCHURTER AG
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH
SCHURTER AG
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
Application standards
Application standards where the product can be used
Organization
Compliances
The product complies with following Guide Lines
Identification
Dimension [mm]
Case 5A-4
91 max.
60
157 max.
EMC Products
12
LOAD
M6
5-7 [Nm]
(2x)
121 max.
2
6.5 ±0.3
4 mm²
max. 0.5 [Nm]
(6x)
23
81 max.
90 ±0.3
LINE
0
92.5 -1
110 max.
30 ±0.2
64
FMAC NEO
3-Phase AC Filters / DC Filters
https://www.schurter.com /PG80
Case 5A-10
90 ±0.3
M6
5-7 [Nm]
(2x)
121 max.
12
LINE
LOAD
0
23
81 max.
10 mm²
max. 1.2 [Nm]
(6x)
92.5 -1
110 max.
91 max.
58
6.5 ±0.3
30 ±0.2
64
157 max.
Case 5B-10
100 ±0.3
LOAD
LINE
0
23
95 max.
10mm²
max. 1.2 [Nm]
(6x)
106.5-1
124 max.
91 max.
57
6.5 ±0.3
30 ±0.2
130 max.
165 max.
12
M6
5-7 [Nm]
(2x)
63
Case 5B-16
M6
5-7 [Nm]
(2x)
130 max.
30
max. 95
59
12
LOAD
LINE
106.5
6.5 ±0.3
91 max.
51
16mm²
2-2.2 [Nm]
(6x)
0
-1
124 max.
30 ±0.2
100 ±0.3
170 max.
EMC Products
3
FMAC NEO
3-Phase AC Filters / DC Filters
https://www.schurter.com /PG80
Case 4C-25
max. 200
max. 161
90 ±0.3
6.5±0.3
max. 101
60
36
max. 106
LOAD
LINE
max. 134
0
120-1
25 mm2
2 Nm
12
M6
3-4 Nm
70
Case 4C-50
max. 248
max. 161
90 ±0.3
6.5±0.3
max. 101
46
60
max. 106
M6
5-7 Nm
12
LINE
LOAD
0
120 -1
max. 134
50 mm2
max. 6 Nm
26
Case 4D
95 mm2
3.5-14.7 Nm
68
M10
max. 20 Nm
42.5
29
4
EMC Products
max. 151
70
max. 121
LOAD
LINE
max. 150
0
135 -1
max. 301
max. 201
130 ±0.3
6.5±0.3
FMAC NEO
3-Phase AC Filters / DC Filters
https://www.schurter.com /PG80
Diagrams
Industrial version
1)
Low leakage current version
L1
L1’
L1
L1’
L2
L2’
L2
L2’
L3
L3’
L3
L3’
PE
PE
PE
PE
1) Line
1)
1) Line
Attenuation Loss
- - - - 50Ω differential mode _____ 50Ω common mode
Industrial version
16 A
25 A
36 A
50 A
64 A
80 A
110 A
180 A
230 A
EMC Products
5
FMAC NEO
3-Phase AC Filters / DC Filters
https://www.schurter.com /PG80
Low leakage current version
16 A
25 A
36 A
50 A
64 A
All Variants
Rated Current @
Ta 50°C [A]
Filter Type
Machine
Safety
Tripped Power
Dissipation [W]
Contact Resistance [mΩ]
Leakage Current [mA] @ 440V,
60Hz 1)
Weight [kg]
Screw clamps
[mm2] 2)
Housing
Order Number
16
Industrial version
l
1.6
6.2
10.5
0.9 kg
4
5A-4
25
Industrial version
l
1.9
3
10.7
1.1 kg
10
5A-10
3-138-284
36
Industrial version
l
3.2
2.4
10.7
1.2 kg
10
5B-10
3-138-285
50
Industrial version
l
6
2.4
11.4
1.2 kg
10
5B-10
3-138-286
64
Industrial version
l
3.7
0.9
11.4
1.3 kg
16
5B-16
3-138-287
3-138-283
80
Industrial version
l
4
0.6
12.2
1.4 kg
25
4C-25
3-138-288
110
Industrial version
l
4.9
0.4
12.2
2.5 kg
50
4C-50
3-138-289
180
Industrial version
l
4.4
0.1
12.2
3 kg
95
4D
3-138-290
230
Industrial version
l
5.8
0.1
13.1
4 kg
95
4D
3-138-291
16
Low leakage current
version
l
1.6
6.2
1.4
0.9 kg
4
5A-4
3-138-292
25
Low leakage current
version
l
1.9
3
3
1.1 kg
10
5A-10
3-138-293
36
Low leakage current
version
l
3.2
2.4
3
1.2 kg
10
5B-10
3-138-294
50
Low leakage current
version
l
6
2.4
3
1.2 kg
10
5B-10
3-138-296
64
Low leakage current
version
l
3.7
0.9
3
1.3 kg
16
5B-16
3-138-297
16
Industrial version
1.6
6.2
10.5
0.9 kg
4
5A-4
3-104-580
25
Industrial version
1.9
3
10.7
1.1 kg
10
5A-10
3-104-581
36
Industrial version
3.2
2.4
10.7
1.2 kg
10
5B-10
3-104-582
50
Industrial version
6
2.4
11.4
1.2 kg
10
5B-10
3-104-583
64
Industrial version
3.7
0.9
11.4
1.3 kg
16
5B-16
3-104-584
80
Industrial version
4
0.6
12.2
1.4 kg
25
4C-25
3-104-585
█
█
█
110
Industrial version
4.9
0.4
12.2
2.5 kg
50
4C-50
3-104-586
█
180
Industrial version
4.4
0.1
12.2
3 kg
95
4D
3-104-587
█
230
Industrial version
5.8
0.1
13.1
4 kg
95
4D
3-104-588
█
16
Low leakage current
version
1.6
6.2
1.4
0.9 kg
4
5A-4
3-104-862
█
25
Low leakage current
version
1.9
3
3
1.1 kg
10
5A-10
3-104-841
36
Low leakage current
version
3.2
2.4
3
1.2 kg
10
5B-10
3-104-872
█
50
Low leakage current
version
6
2.4
3
1.2 kg
10
5B-10
3-104-873
█
6
EMC Products
FMAC NEO
3-Phase AC Filters / DC Filters
https://www.schurter.com /PG80
Rated Current @
Ta 50°C [A]
Filter Type
64
Low leakage current
version
Machine
Safety
Tripped Power
Dissipation [W]
Contact Resistance [mΩ]
Leakage Current [mA] @ 440V,
60Hz 1)
Weight [kg]
Screw clamps
[mm2] 2)
Housing
3.7
0.9
3
1.3 kg
16
5B-16
Order Number
3-104-874
█
█ Most Popular.
Availability for all products can be searched real-time: https://www.schurter.com/en/info-center/support-tools/stock-check-distributors
1) Leakage current according IEC 60939-1
2) Maximum conductor cross section (wire gauge) to be used; a comparative table for AWG and mm² values can be found in the general product information
https://www.schurter.com/en/FAQ#10
1 Pcs
28.03.2024
Packaging unit
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
EMC Products