FMBB EP
1-Phase Line Filters
https://www.schurter.com /PG84
AC Filter 2-Stage, excellent Attenuation
Case ME
Case MB
Case MF
See below:
Approvals and Compliances
Description
- Line filter in standard and medical version
- 2 stage
- Compact design
- Very light due to partial potting
Unique Selling Proposition
- Excellent differential and common-mode attenuation
- Broad band attenuation
- Completely closed steel housing
- Wide temperature range
Characteristics
- Designed for current applications of 1 - 36 A
- Protection against interference voltage from the mains
Possible interferences generated in the equipment are strongly attenuated
- Especially designed for industrial applications such as: Frequency Converters, Stepper Motor Drives, UPS-Systems, Inverters
- Suitable for use in equipment according to IEC/UL 62368-1
Suitable for use in medical equipment according to IEC/UL 60601-1 (1
MOOP, 1 MOPP)
References
Alternative: High attenuation version FMBB NEO
Weblinks
pdf data sheet, html datasheet, General Product Information, Approvals,
Distributor-Stock-Check, Detailed request for product, Microsite
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temperature
Climatic Category
IP-Protection
Protection Class
Terminal
Material
1 - 36 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 36 A @ Ta 40 °C / 125/250 VAC;
60 Hz
standard < 0.5 mA (250 V / 50 Hz)
medical (M5) < 5 µA resp. (M80) < 80
µA (250 V / 50 Hz)
1.7 kVDC between L-N
2.7 kVDC between L/N-PE
Test voltage (2 sec)
-40 °C to 100 °C
Line Filter
MTBF
Standard and Medical Version, IEC
60939, UL 60939-3, CSA C22.2 no. 8
Technical Details
> 200'000 h acc. to MIL-HB-217 F
40/100/21 acc. to IEC 60068-1
rear-side IP20 IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminal 6.3 x 0.8 mm
Bolt and nut M4
Nickel plated steel
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agreements by SCHURTER.
EMC Products
1
FMBB EP
1-Phase Line Filters
https://www.schurter.com /PG84
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: FMBB EP
Approval Logo
Certificates
Certification Body
Description
VDE Approvals
VDE
Certificate Number: 40051449
UL Approvals
UL
UR File Number: E495089
Design
Standard
Description
Designed according to
IEC 60939
Passive filters for suppressing electromagnetic interference
Designed according to
IEC 60127-6
Miniature fuses. Part 6. Fuse-holders for miniature fuse-links
Designed according to
UL 60939-3
Passive filters for suppressing electromagnetic interference
Designed according to
CSA C22.2 no. 42
General Use Receptacles, Attachment Plugs, and Similar Wiring Devices
Designed according to
CSA C22.2 no. 8
Electromagnetic interference (EMI) filters
Design
Standard
Description
Suitable for applications acc.
IEC/UL 62368-1
Audio/video, information and communication technology equipment - Part
1: Safety requirements
Suitable for applications acc.
IEC 60601-1
Medical electrical equipment - Part 1: General requirements for basic
safety and essential performance
Details
Initiator
Description
CE declaration of conformity
SCHURTER AG
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
UKCA declaration of conformity
SCHURTER AG
The UKCA marking declares that the product complies with the applicable
requirements laid down in the British Amendment of Regulation (EC)
765/2008.
RoHS
SCHURTER AG
Directive RoHS 2011/65/EU, Amendment (EU) 2015/863
China RoHS
SCHURTER AG
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH
SCHURTER AG
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
Medical Equipment
SCHURTER AG
Suitable for use in medical equipment according to IEC/UL 60601-1 (1
MOOP, 1 MOPP)
Product standards
Product standards that are referenced
Organization
Application standards
Application standards where the product can be used
Organization
Compliances
The product complies with following Guide Lines
Identification
2
EMC Products
FMBB EP
1-Phase Line Filters
https://www.schurter.com /PG84
Dimension [mm]
Case 09 with quick connect terminals
max. 77
max. 46
max. 52
17.5
7.5
12
max. 31
27
6.3x0.8
(5x)
4.8 ±0.3
(2x)
60.4 ±0.5
1)
2)
1) Line
2) Load
Case MB with bolt and nut M4
max. 160
27
max. 58
max. 131
15.2
12
5)
13
max. 46
4)
max. 156
144 ±0.5
140 ±0.5
1)
2)
M4
(4x)
4)
5.3 ±0.3
(2x)
3)
1) Line
2) Load
3) Nut torque 0.8...1 Nm, keep lock-nut fastened
4) Lock-nut do not unscrew
5) PE: M4x16, 1.2...1.5 Nm, keep lock-nut fastened
EMC Products
3
FMBB EP
1-Phase Line Filters
https://www.schurter.com /PG84
Case MC with quick connect terminals
max. 51
max. 66
21
6
12
max. 31
27
max. 90
75 ±0.5
5.3 ±0.3
(2x)
6.3x0.8
(5x)
1)
2)
1) Line
2) Load
Case UB with quick connect terminals
max. 51
max. 66
11.4
12
max.41
27
max. 90
75 ±0.5
5.3 ±0.3
(2x)
6.3x0.8
(5x)
1)
1) Line
2) Load
4
EMC Products
2)
10.4
FMBB EP
1-Phase Line Filters
https://www.schurter.com /PG84
Case ME with quick connect terminals
max. 52
max. 112
27
12
12
max. 46
13
max. 87
max. 115
104.5 ±0.5
97.5 ±0.5
5.3 ±0.3
(2x)
6.3x0.8
(5x)
1)
2)
1) Line
2) Load
Case MF with bolt and nut M4
max. 85
max. 98
40
16
max. 59
max. 130
max. 120
109 ±0.3
4.4 ±0.3
(4x)
3)
2)
54.5 ±0.5
1)
M4
(4x)
4)
47.5 ±0.5
5)
1) Line
2) Load
3) Nut torque 0.8...1 Nm, keep lock-nut fastened
4) Lock-nut do not unscrew
5) PE: M4x16, 1.2...1.5 Nm, keep lock-nut fastened
EMC Products
5
FMBB EP
1-Phase Line Filters
https://www.schurter.com /PG84
Diagrams
Standard and low leakage current
Medical M5
1)
2)
1)
2)
1) Line, 2) Load
Medical M80
1)
2)
1) Line, 2) Load
Attenuation Loss. . . . . 0.1/100Ω differential mode
........... 100/0.1Ω differential mode
- - - - 50Ω differential mode _____ 50Ω common mode
Standard version
1A
3A
6A
10 A
12 A
16 A
20 A
30 A
36 A
6
EMC Products
FMBB EP
1-Phase Line Filters
https://www.schurter.com /PG84
Medical version (M5)
1A
3A
6A
10 A
12 A
16 A
20 A
30 A
1A
3A
6A
10 A
12 A
16 A
20 A
30 A
36 A
Medical version (M80)
36 A
EMC Products
7
FMBB EP
1-Phase Line Filters
https://www.schurter.com /PG84
Low leakage current version
1A
3A
6A
10 A
12 A
16 A
20 A
30 A
36 A
All Variants
Rated
current
Filter-Type
Terminal
[A]
1
Standard version
Quick connect terminal 6.3 x 0.8 mm
Leakage
Ri
Power
Loss
Weight
Housing
Packaging
Order Number
[mA]
[mΩ]
[W]
[g]
1.47
600
1.2
125 g
09
15
3-123-509
[ST]
3
Standard version
Quick connect terminal 6.3 x 0.8 mm
1.47
168
3
128 g
09
15
3-123-510
6
Standard version
Quick connect terminal 6.3 x 0.8 mm
1.47
40
2.88
133 g
09
15
3-123-511
10
Standard version
Quick connect terminal 6.3 x 0.8 mm
6.91
8.6
4.4
198 g
MC
10
3-123-522
12
Standard version
Quick connect terminal 6.3 x 0.8 mm
3.14
6.2
4.15
201 g
MC
10
3-123-523
█
16
Standard version
Quick connect terminal 6.3 x 0.8 mm
3.14
8.0
4.1
265 g
UB
10
3-123-524
█
20
Standard version
Quick connect terminal 6.3 x 0.8 mm
3.14
6
4.8
390 g
ME
5
3-123-525
█
30
Standard version
Bolt and nut M4
3.14
6
10.8
855 g
MF
3
3-123-526
36
Standard version
Bolt and nut M4
3.14
4.2
10.4
890 g
MB
4
3-123-527
1
Low leakage current
Quick connect terminal 6.3 x 0.8 mm
0.15
600
1.2
125 g
09
15
3-123-537
3
Low leakage current
Quick connect terminal 6.3 x 0.8 mm
0.15
168
3
128 g
09
15
3-123-538
6
Low leakage current
Quick connect terminal 6.3 x 0.8 mm
0.15
40
2.88
133 g
09
15
3-123-539
10
Low leakage current
Quick connect terminal 6.3 x 0.8 mm
0.15
8.6
4.4
198 g
MC
10
3-123-540
12
Low leakage current
Quick connect terminal 6.3 x 0.8 mm
0.15
6.2
4.15
201 g
MC
10
3-123-541
16
Low leakage current
Quick connect terminal 6.3 x 0.8 mm
0.15
8.0
4.1
265 g
UB
10
3-123-542
20
Low leakage current
Quick connect terminal 6.3 x 0.8 mm
0.15
6
4.8
390 g
ME
5
3-123-543
30
Low leakage current
Bolt and nut M4
0.15
6
10.8
855 g
MF
3
3-123-544
36
Low leakage current
Bolt and nut M4
0.15
4.2
10.4
890 g
MB
4
3-123-545
1
Medical Version (M5)
Quick connect terminal 6.3 x 0.8 mm
0.005
600
1.2
125 g
09
15
3-123-528
3
Medical Version (M5)
Quick connect terminal 6.3 x 0.8 mm
0.005
168
3
128 g
09
15
3-123-529
6
Medical Version (M5)
Quick connect terminal 6.3 x 0.8 mm
0.005
40
2.88
133 g
09
15
3-123-530
10
Medical Version (M5)
Quick connect terminal 6.3 x 0.8 mm
0.005
8.6
4.4
198 g
MC
10
3-123-531
12
Medical Version (M5)
Quick connect terminal 6.3 x 0.8 mm
0.005
6.2
4.15
201 g
MC
10
3-123-532
16
Medical Version (M5)
Quick connect terminal 6.3 x 0.8 mm
0.005
8.0
4.1
265 g
UB
10
3-123-533
20
Medical Version (M5)
Quick connect terminal 6.3 x 0.8 mm
0.005
6
4.8
390 g
ME
5
3-123-534
8
EMC Products
FMBB EP
1-Phase Line Filters
https://www.schurter.com /PG84
Rated
current
Filter-Type
Terminal
[A]
Leakage
Ri
Power
Loss
Weight
[mA]
[mΩ]
[W]
[g]
Housing
Packaging
Order Number
[ST]
30
Medical Version (M5)
Bolt and nut M4
0.005
6
10.8
855 g
MF
3
36
Medical Version (M5)
Bolt and nut M4
0.005
4.2
10.4
890 g
MB
4
3-123-535
3-123-536
1
Medical Version (M80)
Quick connect terminal 6.3 x 0.8 mm
0.073
600
1.2
125 g
09
15
3-142-126
3
Medical Version (M80)
Quick connect terminal 6.3 x 0.8 mm
0.073
168
3
128 g
09
15
3-142-127
6
Medical Version (M80)
Quick connect terminal 6.3 x 0.8 mm
0.073
40
2.88
133 g
09
15
3-142-128
10
Medical Version (M80)
Quick connect terminal 6.3 x 0.8 mm
0.073
8.6
4.4
198 g
MC
10
3-142-129
12
Medical Version (M80)
Quick connect terminal 6.3 x 0.8 mm
0.073
6.2
4.15
201 g
MC
10
3-142-130
16
Medical Version (M80)
Quick connect terminal 6.3 x 0.8 mm
0.073
8.0
4.1
265 g
UB
10
3-142-131
20
Medical Version (M80)
Quick connect terminal 6.3 x 0.8 mm
0.073
6
4.8
390 g
ME
5
3-142-132
30
Medical Version (M80)
Bolt and nut M4
0.073
6
10.8
855 g
MF
3
3-142-133
36
Medical Version (M80)
Bolt and nut M4
0.073
4.2
10.4
890 g
MB
4
3-142-134
█ Most Popular.
Availability for all products can be searched real-time: https://www.schurter.com/en/info-center/support-tools/stock-check-distributors
Leakage current according IEC 60939-1
20A, 30A and 36A medical filter M5 and M80, are only suitable for medical equipment intended for permanently connection to the mains.
Accessories
Description
DIN_Rail_Kit
Mounting accessory for compact 1- and 3-phase filters
28.03.2024
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
EMC Products
9
很抱歉,暂时无法提供与“3-123-527”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+1053.940991+135.77175