T13-212
Thermal (T- and TA-Line)
https://www.schurter.com /PG17_20
Circuit Breaker for Equipment thermal, Threaded neck type, Reset type, Screw terminals
See below:
Approvals and Compliances
Description
Applications
- Threaded neck type
- Thermal circuit breaker
- 1‑pole
- Reset type
- Wide current range
- High breaking capacity
- Bolts and nuts
- Power supplies
- Uninterruptible power supply
- Power tools
- Household appliances
Weblinks
pdf data sheet, html datasheet, General Product Information, DistributorStock-Check, Detailed request for product, Product News
Unique Selling Proposition
- Compact design
- Positively trip-free release
- Available with cover
- Different mounting possibilities
Technical Data
Rated Voltage AC
Rated Voltage DC
Rated current range AC
Conditional short circuit capacity Inc
Short circuit capacity Icn
Degree of Protection
Dielectric Strength
Insulation Resistance
Endurance typical
Endurance minimum
AC 240/277 VAC, see approbations
28 VDC
0.05 - 30 A
IEC 60934: PC1, AC 240 V: 1 kA
IEC 60934: at In < 7 A/240 VAC : 8 x In
IEC 60934: at In ≥ 7 A/240 VAC : 400 A
AC/DC 28 V : 400 A
front side IP40 acc. to IEC 60529
50 Hz: 1.5 kV
Impulse 1.2/50 μs: > 2.5 kV
500 VDC > 100 MΩ
2 x Ir: 3000 switching cycles
Reset type
AC : 2 x Ir , cos φ 0.6 :
DC : 2 x Ir , L/R = 2 - 3 ms :
50 switching cycles
Overload
␣
Allowable Operation Temp.
Vibration Resistance
Shock Resistance
Tripping Type
Actuation Type
Weight
IEC: min. 40 trips
@ 6 x Ir, cos φ 0.6
UL / CSA: min. 50 trips
@ 1.5 x Ir, cos φ 0.75
-5 °C to 60 °C
± 1.5 mm @ 10 - 60 Hz
acc. to IEC 60068-2-6, test Fc
10 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
100 G / 6 ms
acc. to IEC 60068-2-27, test Ea
Thermal
Reset type
ca. 10 g
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agreements by SCHURTER.
Circuit Breakers
1
T13-212
Thermal (T- and TA-Line)
https://www.schurter.com /PG17_20
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: T13
Approval Logo
Certificates
Certification Body
Description
VDE Approvals
VDE
VDE Certificate Number: 123283
UL Approvals
UL
UR File Number: E71572
CSA Approvals
CSA
CSA Certification Record: LR 37712
CCC Approvals
CCC
CCC Certificate Number: 2020970307003503
Design
Standard
Description
Designed according to
IEC 60934
Circuit-breakers for equipment (CBE)
Designed according to
UL 1077
Standard for Supplementary Protectors for Use in Electrical Equipment
Designed according to
CSA C22.2 No. 235
Supplementary Protectors
Designed according to
GB 17701
Circuit-breaker for equipment
Design
Standard
Description
Suitable for applications acc.
IEC/UL 62368-1
Audio/video, information and communication technology equipment - Part
1: Safety requirements
Details
Initiator
Description
CE declaration of conformity
SCHURTER AG
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
UKCA declaration of conformity
SCHURTER AG
The UKCA marking declares that the product complies with the applicable
requirements laid down in the British Amendment of Regulation (EC)
765/2008.
RoHS
SCHURTER AG
Directive RoHS 2011/65/EU, Amendment (EU) 2015/863
China RoHS
SCHURTER AG
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH
SCHURTER AG
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
Product standards
Product standards that are referenced
Organization
Application standards
Application standards where the product can be used
Organization
Compliances
The product complies with following Guide Lines
Identification
2
Circuit Breakers
T13-212
Thermal (T- and TA-Line)
https://www.schurter.com /PG17_20
Dimension [mm]
T13-212
1
2
3/8-27UNS-2A
Ø 13
8.8
6.3
45 - 0.3
8
20
16
Ø5
M4
20.4
+0.4
11.5
11.5 - 0.2
31 - 0.0
16
Ø9
.6
8.9
+0.1
- 0.0
Diagrams
T13-...
1
2
Circuit Breakers
3
T13-212
Thermal (T- and TA-Line)
https://www.schurter.com /PG17_20
Approval
Rated current
Rated Voltage AC
Rated Voltage DC
UL 1077
0.05...30 A
277 V
28 V
CSA C22.2 No. 235
0.05...30 A
277 V
28 V
EN 60934
0.05...30 A
240 V
-
GB 17701
0.05...30 A
240 V
-
Typical internal resistance per pole
Rated Current [A]
Internal Resistance [Ω]
0.05
376.500
0.50
4.40
1.00
1.10
2.00
0.31
4
3.00
0.14
4.00
0.068
5.00
0.048
6.00
0.033
8.00
0.026
9.00
0.0125
10.00
0.0125
11.00
0.0085
12.00
0.0085
13.00
0.0085
14.00
0.007
15.00
0.007
16.00
0.007
17.00
0.0047
18.00
0.0047
19.00
0.0047
20.00
0.004
21.00
0.0035
22.00
0.003
23.00
0.003
24.00
0.003
25.00
0.003
26.00
0.0022
27.00
0.002
28.00
0.002
29.00
0.002
30.00
0.002
Circuit Breakers
T13-212
Thermal (T- and TA-Line)
https://www.schurter.com /PG17_20
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated current for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient Temperature [°C]
Correction factor
-5
0.88
0
0.90
10
0.95
23
1.00
30
1.05
40
1.10
50
1.18
60
1.26
Example: Rated current = 5 A, Environmental temperature = 40 °C, --> Correction factor =
1.1, Resulting current = 5.5 A --> Round to next higher rated current: 6 A
Time-Current-Curves
[ min ] [ sec]
10'000
< 7,0 A
> 7,0A
60
30
20
2`000
1`000
10
500
5
200
Time in Seconds
100
1
50
20
10
5
2
1
0,5
0, 3
0, 2
0,1
1,05 1,32
2
3
4
5
8
10
Multiple of Rated Current In
Ambient temperature +23°
Config. Code
T13|-|1|2|3|B|-|1.23|
The characters are placeholders for the correspondingly keys of selections from the key tables.
T13|-| 1 |2|3|B|-|1.23| = Mounting
Mounting
Threaded neck type with knurled nut
Terminal
Configuration
key
2
T13|-|1| 2 |3|B|-|1.23| = Actuation Type
Actuation Type
Reset type
Configuration
key
Screw clamp terminals
T13|-|1|2|3| B |-|1.23| = Setting indication
Setting indication
Configuration
key
1
2
Configuration
key
Setting indication
R
T13|-|1|2|3|B|-| 1.23 | = Rated current
T13|-|1|2| 3 |B|-|1.23| = Terminal
Circuit Breakers
5
T13-212
Thermal (T- and TA-Line)
https://www.schurter.com /PG17_20
Rated current
Configuration
key
0.05 A
Rated current
Configuration
key
0.05
3.5 A
0.1 A
0.1
4.0 A
4
0.15 A
0.15
4.5 A
4.5
0.2 A
0.2
5.0 A
5
0.3 A
0.3
5.5 A
5.5
0.4 A
0.4
6.0
0.5 A
0.5
6.5 A
0.6 A
0.6
7.0 A
7
0.7 A
0.7
7.5 A
7.5
0.8 A
0.8
8.0 A
8
0.9 A
0.9
8.5 A
8.5
1
9.0 A
9
1.1 A
1.1
9.5 A
9.5
1.2 A
1.2
10.0 A
10
1.3 A
1.3
11.0 A
11
1.4 A
1.4
12.0 A
12
1.5 A
1.5
13.0 A
13
1.6 A
1.6
14.0 A
14
1.7 A
1.7
15.0 A
15
1.8 A
1.8
16.0 A
16
1.9 A
1.9
17.0 A
17
2.0 A
2
18.0 A
18
2.1 A
2.1
19.0 A
19
2.3 A
2.3
20.0 A
20
2.5 A
2.5
22.0 A
22
2.8 A
2.8
25.0 A
25
3.0 A
3
28.0 A
28
3.3 A
3.3
30.0 A
30
1.0
Other rated currents on request
Other rated currents on request
Variants
Rated current
Setting indication
Config. Code
Order Number
16.0 A
T13-212-16
4411.0012
30.0 A
T13-212-30
4411.0067
T13-212-12
4411.0099
11.0 A
12.0 A
l
T13-212R-11
4411.0210
15.0 A
l
T13-212R-15
4411.0211
Availability for all products can be searched real-time:https://www.schurter.com/en/StockCheck/Stock-Check-SCHURTER
Packaging Unit
6
20 Pcs
Circuit Breakers
3.5
6
6.5
T13-212
Thermal (T- and TA-Line)
https://www.schurter.com /PG17_20
Accessories
Description
T-Line Accessories
Accessories to T-Line
14.06.2022
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
Circuit Breakers
7
很抱歉,暂时无法提供与“4411.0044”相匹配的价格&库存,您可以联系我们找货
免费人工找货