AS168XDC1
Thermal-magnetic (TM and AS-line)
https://www.schurter.com /PG20
OU
T
Circuit Breaker for Equipment thermal-magnetic, 1 pole
See below:
Approvals and Compliances
Description
- Thermal-magnetic circuit breaker
- High short circuit performance
- Availability of AC and DC in the same frame size
- DIN-Rail Mounting
Applications
- Industrial appliances
References
Last order possibility: 31.08.2018
Last delivery date: 30.09.2018
Weblinks
pdf datasheet, html-datasheet, General Product Information, DistributorStock-Check, Detailed request for product, Product News
General data
Rated Voltage DC
E-
Technical Data
AS
IEC 180 V
UL/CSA 120/180 V
Rated current
0.5 - 50 A , see approbations
Conditional short circuit capa- Icn: DC 180 V: 4.5 kA (no fuse)
city IEC 60934
Conditional short circuit capa- Icn: DC 120 V; DF/DG: 0.5A-40A: 10 kA
city UL 1077
(no fuse)
Icn: DC 120 V; DH: 0.5A-40A: 5 kA (no
fuse)
Icn: DC 180 V; 0.5A-50A: 2 kA (no fuse)
Degree of Protection
from front side IP 40 acc. to IEC 60529
Lifetime
1 x Ir 6000 switching cycles
Dielectric Strength
50 Hz: > 2 kV
Impulse 1.2/50 μs
Vibration Resistance
± 0.75 mm @ 5 - 60 Hz
acc. to IEC 60068-2-6, test Fc
10 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
Insulation Resistance
250/440 VAC > 5 MΩ
Shock Resistance
30 G / 18 ms
acc. to IEC 60068-2-27, test Ea
Ambient temperature
-10 °C to 55 °C
Weight
100 - 130 g
Tripping Type
Actuation Type
Permissible wire cross section
Switched neutral
Rated Voltage
Rated current
Function
Add-on modules
Add-on modules
Positively trip free
Manual ON/OFF
1.5 - 25 mm² / 16 - 4 AWG
AC 277 V
AC/DC 65 A
The switched neutral closes with manual closure of the poles and opens
automatically with thermal magnetic
tripping of the poles.
Technical data for the additional module
see separate data sheet
PH
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
Circuit Breakers
1
AS168XDC1
Thermal-magnetic (TM and AS-line)
https://www.schurter.com /PG20
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: AS168X
Certification Body
Description
VDE Approvals
VDE
VDE Certificate Number: 40005743
UL Approvals
UL
UL File Number: E216629 / E71572
UL Approvals
UL
UL File Number: E216629 / E71572
CQC Approvals
CQC
CCC Certificate Number: 2013010307594187
Product standards
Product standards that are referenced
Organization
Design
Standard
Designed according to
IEC 60934
Designed according to
UL 1077
Designed according to
CSA C22.2
Application standards
Application standards where the product can be used
Design
Standard
Designed for applications acc.
Standard for Supplementary Protectors for Use in Electrical Equipment
Supplementary Protectors
Description
IEC 60950-1 includes the basic requirements for the safety of information
technologyequipment.
Initiator
Description
SCHURTER AG
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
SCHURTER AG
EU Directive RoHS 2011/65/EU
China RoHS
SCHURTER AG
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH
SCHURTER AG
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
The product complies with following Guide Lines
Details
CE declaration of conformity
PH
AS
RoHS
2
Circuit-breakers for equipment (CBE)
IEC/UL 60950
Compliances
Identification
Description
E-
Organization
T
Certificates
OU
Approval Logo
Circuit Breakers
AS168XDC1
Thermal-magnetic (TM and AS-line)
https://www.schurter.com /PG20
Dimension [mm]
AS168X 1 pole
35
A)
1.9
90
B)
T
5.1
26.6
44.4
OU
68.4
61.6
45
17.5
A)
35 mm DIN rail EN 50022
B)
Max. torque
AS168X 1 pole and switched neutral pole
Max. torque
2.5 Nm
3.1 Nm
20 ... 22 lb –in
26 ... 28 lb –in
E-
Wire crosssection
1.5 ... 10 mm2
16 ... 25 mm2
AWG #16 ... 8
AWG #6 ... 4
68.4
A)
5.1
35
26.6
44.4
61.6
AS
45
35
PH
1.9
90
B)
A)
35 mm DIN rail EN 50022
B)
Max. torque
Wire crosssection
1.5 ... 10 mm2
16 ... 25 mm2
AWG #16 ... 8
AWG #6 ... 4
Circuit Breakers
Max. torque
2.5 Nm
3.1 Nm
20 ... 22 lb –in
26 ... 28 lb –in
3
AS168XDC1
Thermal-magnetic (TM and AS-line)
https://www.schurter.com /PG20
Diagrams
AS168X-CB1...N
OU
T
AS168X-CB1...
AS168X-CB1... / AS168X-ACBS2
AS
AS168X-CB1... / AS168X-ACBS1
AS168X-CB1... / AS168X-ACBH2
E-
AS168X-CB1... / AS168X-ACBH1
PH
AS168X-CB1... / AS168X-ACBA
4
Circuit Breakers
AS168XDC1
Thermal-magnetic (TM and AS-line)
https://www.schurter.com /PG20
Rated current
Rated voltage DC
Conditional short circuit capacity Icn
UL 508
CSA C22.2 no. 14
-
-
-
UL 1077
0.5 - 40 A
120 V
10 kA
CSA C22.2 no. 235
0.5 - 50 A
180 V
2 kA
EN 60934
0.5 - 50 A
180 V
4.5 kV
GB 17701
nur Art.-Nr.
4420.0386 (30 A)
4420.0526 (40 A)
4420.0897 (50 A)
120 V
T
Standard
3 kA
OU
Symbol
Effect of ambient temperature
AC-breaker are calibrated for an ambient temperature of +40°C, DC-breakers for +23°C. To determine the rated current for a lower or
higher ambient temperature, use a correction factor from the table below:
Ambient temperature [°C]
Correction factor AC version
Correction factor DC version
-20
0.78
0.80
-5
0.82
0
0.83
+10
0.87
+23
0.91
+30
0.95
+40
1.00
+50
1.05
+60
1.11
0.87
0.90
0.95
1.00
1.05
1.10
1.20
E-
1.30
Example DC version: Rated current = 10 A; Environmental temperature = 50 °C; --> Correction factor = 1.2; Resulting current = 12 A
Time-Current-Curves
Version DF / Magnetic 4.5-8 xln
Version DG / Magnetic 9-16 xln
AS
1hr
1000s
100s
100s
10s
10s
Time in Seconds
1000s
1s
0,1s
10ms
PH
Time in Seconds
1hr
1ms
10
100
0,1s
10ms
1ms
0,1ms
1
1s
0,1ms
1000 x In
1
10
Multiple of Rated Current In
Multiple of Rated Current In
Reference Temperature +23°
Reference Temperature +23°
Circuit Breakers
100
1000 x In
5
AS168XDC1
Thermal-magnetic (TM and AS-line)
https://www.schurter.com /PG20
Version DH / Magnetic 18-32 xln
T
1hr
1000s
100s
1s
0,1s
10ms
1ms
0,1ms
1
10
100
1000 x In
Multiple of Rated Current In
Config. Code
AS168X-CB|1|DG|200|N|
E-
Reference Temperature +23°
OU
Time in Seconds
10s
The characters are placeholders for the correspondingly keys of selections from the key tables.
AS168X-CB| 1 |DG|200|N| = Number of Poles
Configuration
key
Configuration
key
080
9.0 A
090
10.0 A
100
12.0 A
120
15.0 A
150
16.0 A
160
18.0 A
180
20.0 A
200
23.0 A
230
25.0 A
250
27.0 A
270
AS168X-CB|1|DG| 200 |N| = Rated current
30.0 A
300
32.0 A
320
Configuration
key
35.0 A
350
40.0 A
400
0.05 A
005
45.0 A
450
1.0 A
010
50.0 A
500
1.5 A
015
Other rated currents on request
2.0 A
020
3.0 A
030
4.0 A
040
5.0 A
050
6.0 A
060
7.0 A
070
AS
8.0 A
PH
Number of Poles
Rated current
1-pole
1
AS168X-CB|1| DG |200|N| = Tripping characteristics
Tripping characteristics
Configuration
key
1.05-1.35xIn / 4.5-8xIn / 0.5-50 A
DF
1.05-1.35xIn / 9-16xIn / 0.5-50 A
DG
1.05-1.35xIn / 18-32xIn / 6.0-50 A
DH
Rated current
Other rated currents on request
6
Circuit Breakers
AS168X-CB|1|DG|200| N | = Switched neutral
Switched neutral
Switched neutral pole
Configuration
key
N
AS168XDC1
Thermal-magnetic (TM and AS-line)
https://www.schurter.com /PG20
Variants
Rated current
Switched neutral
Config. Code
Order Number
1.05-1.35xIn / 9-16xIn / 0.5-50 A
0.05 A
AS168X-CB1DG005
4420.0460
1.05-1.35xIn / 9-16xIn / 0.5-50 A
1.0 A
AS168X-CB1DG010
4420.0625
T
Tripping characteristics
5.0 A
AS168X-CB1DG050
4420.0354
10.0 A
AS168X-CB1DG100
4420.0324
1.05-1.35xIn / 9-16xIn / 0.5-50 A
20.0 A
1.05-1.35xIn / 9-16xIn / 0.5-50 A
20.0 A
1.05-1.35xIn / 9-16xIn / 0.5-50 A
40.0 A
OU
1.05-1.35xIn / 9-16xIn / 0.5-50 A
1.05-1.35xIn / 9-16xIn / 0.5-50 A
AS168X-CB1DG200
4420.0332
Switched neutral pole
AS168X-CB1DG200N
4420.0823
AS168X-CB1DG400
4420.0530
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
1 Pcs
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
19.02.2018
PH
AS
E-
Packaging Unit
Circuit Breakers
7
很抱歉,暂时无法提供与“4420.0324”相匹配的价格&库存,您可以联系我们找货
免费人工找货