CIRCUIT BREAKERS FOR EQUIPMENT, 2 POLE, PUSH BUTTON
GERÄTESCHUTZSCHALTER, 2POLIG, DRUCKTASTENBETÄTIGT
TA45
Product description
Produktebeschreibung
The 2 pole, push button actuated version of the TA45 line of thermal
CBE’s can be used for various purposes. Basically it is a CBE for
automatic interruption of overloads with facilities for regular manual
ON/OFF switching operations under normal load conditions. It is
capable of interrupting moderate short circuit currents without the aid
of back-up protection.
Another available version of this line utilizes an under-voltage release
to protect persons against injuries caused by unexpected events like
the automatic restarting of motors after a power failure. This release
can be combined with the thermal release required for overcurrent
protection. Protection against injuries is also provided by another
CBE of this line, which prevents the starting of a machine should a
protective cover be removed from dangerous parts of the machine.
Die 2polige, drucktastenbetätigte Version der TA45-Linie ist ein thermischer Geräteschutzschalter, kurz CBE (Circuit Breaker for
Equipment) genannt, der für viele Zwecke eingesetzt werden kann. In
seiner Grundausführung ist dieser CBE für die automatische
Unterbrechung von Überlast-Strömen und das manuelle
Wiedereinschalten resp. für manuelles EIN/AUS-Schalten im Normalbetrieb bestimmt. Der CBE ist in der Lage, Überströme bis zu seinem
Schaltvermögen ohne back-up Unterstützung zu unterbrechen.
Eine spezielle Version ist erhältlich als «CBE-switch». Bei dieser
Ausführung fehlt der Thermo-Auslöser. Eine weitere Version der
TA45-Linie ist mit Unterspannungsauslösung ausgerüstet. Diese
schützt Personen vor möglichen Verletzungen wie sie z.B. durch
unbeabsichtigtes Wiederanlaufen von Geräten nach einem
Netzausfall verursacht werden könnten. Dieser Schutz kann mit dem
thermischen Überlast-Schutz kombiniert werden. Schutz gegen
Verletzungen wird auch gewährleistet durch eine weitere Version der
TA45-Reihe, die den Anlauf einer Maschine verhindert, bei der eine
wichtige Schutzabdeckung fehlt.
Available options
Erhältliche Versionen
• CBE for overcurrent protection
1 or 2 protected poles (thermal)
• Geräteschutzschalter mit Überstromauslösung:
Ein- oder zweipolig geschützt durch Thermo-Bimetall
• CBE with undervoltage release:
The CBE will open automatically when the voltage drops below the
trip level. Only when the supply voltage has reached the reset level,
the CBE can be reclosed manually.
• Geräteschutzschalter mit Unterspannungsauslöser:
Wiederanlaufschutz bei Spannungsausfall. Nach Unterschreiten
der Abfallspannung (Netzausfall) springt der Geräteschutzschalter
in die AUS-Stellung. Ein manuelles Einschalten ist erst dann
möglich, wenn die wiederkehrende Spannung den Anzugswert
des Auslösers erreicht.
A special version is available as a «CBE-switch», in which the means
for automatic overcurrent interruption (the bimetal relases), are
omitted.
• CBE switch with mechanical lock-out latch:
A spring loaded pin will trip the CBE if a protective cover of the
equipment is removed. The CBE can not be switched ON until the
protective cover is refitted.
• CBE with remote trip release:
The remote trip release permits the CBE to be tripped by a external
contact (sensor) energizing the trip coil.
• CBE with auxiliary contact:
All types of the line can be outfitted with an auxiliary contact
(changeover contact).
TA45 is positively trip-free. The rated current range is 0,05 to 20 A at
AC 240 V / DC 60 V . The CBE comes with snap-in mounting or
flange mounting. A locking device suitable for padlocks prevents
unauthorized switching ON of the CBE. The TA45 is approved in all
major industrial countries and complies with the CBE-standard
EN60934.
In conjunction with its accessories the TA45 product line of Schurter
paves the way for new unconventional applications.
Applications
•
•
•
•
Motors
Power supplies
Processing machines
etc.
70
www.schurter.com
• Geräteschutzschalter mit mechanischer Schaltsperre:
Ein unter Federdruck stehender Stift bewirkt ein automatisches
Auslösen, falls die Schutzabdeckung entfernt wird. Ein Wiedereinschalten in dieser Position ist nicht möglich, solange die Abdeckung fehlt.
• Geräteschutzschalter mit Fernauslösung:
Der Fernauslöser ermöglicht das Ausschalten durch einen
externen Schalter oder Sensor, der die Auslösespule aktiviert.
• Geräteschutzschalter mit Hilfskontakt:
Alle Typen sind mit einem Hilfskontakt (Wechselkontakt) erhältlich.
Der TA45 ist positiv freiauslösend. Sein Nennstrombereich beträgt
0,05 bis 20 A bei AC 240 V / DC 60 V . Die Montage erfolgt mittels
Schnappbefestigung oder Flanschbefestigung. Mit einer zusätzlichen
Abschliessvorrichtung für ein Vorhängeschloss lässt sich der TA45
gegen unbefugtes Einschalten sichern. Der TA45 ist in den wichtigsten Industrieländern approbiert und entspricht der neuen CBE
Europa Norm EN60934. In Verbindung mit dem vielfältigen Zubehör
ermöglicht der 2polige drucktastenbetätigte TA45 von Schurter neue,
unkonventionelle Anwendungen.
Anwendungen
•
•
•
•
Motoren
Netzgeräte
Be- und Verarbeitungsmaschinen
usw.
CIRCUIT BREAKERS FOR EQUIPMENT, 2 POLE, PUSH BUTTON
GERÄTESCHUTZSCHALTER, 2POLIG, DRUCKTASTENBETÄTIGT
Effect of ambient
temperature
Einfluß der
Umgebungstemperatur
The unit is calibrated for an ambient temperature of +23°C. To determine the rated
current for a lower or higher ambient
temperature, use a correction factor from
the table below:
Die Eichung gilt für eine Umgebungstemperatur von +23°C. Zur Bestimmung
des Nennstromes für eine tiefere oder
höhere Umgebungstemperatur ist ein
Korrekturfaktor gemäß untenstehender
Tabelle zu verwenden:
*Ambient
temperature [°C]
Correction factor
*Umgebungstemperatur [°C]
Korrekturfaktor
–10
0,89
–10
0,89
–5
0,91
–5
0,91
0
0,92
0
0,92
+23
1,00
+23
1,00
+30
1,03
+30
1,03
+40
1,08
+40
1,08
+55
1,16
+55
1,16
Example
Rated current at +23°C
Ambient temperature
Correction factor
Chosen rated current at
+40°C ambient temperature
5 A x 1,08 = 5,5 A
Beispiel
Nennstrom bei +23°C
Umgebungstemperatur
Korrekturfaktor
Gewählter Nennstrom bei
+40°C Umgebungstemperatur
5 A x 1,08 = 5,5 A
5,0 A
+40°C
1,08
5,0 A
+40°C
1,08
* Temperature must be measured at the rear of the
breaker next to the terminals after equipment operating
temperature has been reached.
* Die Temperatur wird in der Nähe der Schalteranschlüsse
ermittelt, nachdem das zu schützende System seine
Arbeitstemperatur erreicht hat.
Tripping characteristics
Auslösekennlinien
In