DF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
IEC Appliance Inlet C14 with Filter, Circuit Breaker TA45 (recessed)
Screw-on from front side
Rocker non-illuminated
white
Screw-on from front side
Rocker illuminated
orange
C14
See below:
Approvals and Compliances
70° C
Description
- Panel mount :
Screw-on mounting front side
- 3 Functions :
Appliance Inlet Protection class I , circuit breaker type TA45 2-pole
, Line filter in standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
Characteristics
- All single elements are already wired
- Circuit Breaker non-illuminated or illuminated
- Suitable for use in medical equipment according to IEC/UL 60601-1 (1
MOOP, 1 MOPP)
For applications according IEC/UL 62368-1 we recommend variants
with bleed resistor
Other versions on request
- Unwired versions
- Other rocker marking
- Medical Version (M80)
- Capacitance CX1
- Variant with notch for V-Lock mating Cordsets
References
Alternative: version without line filter DF11
Substitute for type 5145
Alternative: Standard version
Weblinks
pdf data sheet, html datasheet, General Product Information, Approvals,
Distributor-Stock-Check, Accessories, Detailed request for product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temperature
Climatic Category
IP-Protection
Protection Class
Terminal
Panel Thickness S
Material
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 15 A @ Ta 40 °C / 250 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-10 °C to 55 °C
10/055/21 acc. to IEC 60068-1
front side IP40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Appliance inlet/-outlet
Circuit Breakers
Line Filter
MTBF
C14 acc. to IEC 60320-1
UL 60320-1, CSA C22.2 no. 60320-1
(for cold conditions) pin-temperature 70
°C, 10 A, Protection Class I
Acc. IEC/EN 60934, UL 1077, CSA
22.2 no. 235
2-pole rocker switch, illuminated or nonilluminated. Optional with undervoltageor remote trip release
Short circuit capacity Icn:
at In < 3A/240VAC : 10 x In
at In ≥ 3A/240VAC : 300A
Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
> 100'000 h acc. to MIL-HB-217 F
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agreements by SCHURTER.
EMC Products
1
DF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: DF12
Approval Logo
Certificates
Certification Body
Description
VDE Approvals
VDE
Certificate Number: 40012935
UL Approvals
UL
UR File Number: E72928
Design
Standard
Description
Designed according to
IEC 60320-1
Appliance couplers for household and similar general purposes
Designed according to
IEC 60939
Passive filters for suppressing electromagnetic interference
Designed according to
IEC 61058-1
Switches for appliances. Part 1. General requirements
Designed according to
UL 60320-1
Standard for Attachment Plugs and Receptacles
Designed according to
UL 1283
Passive filters for suppressing electromagnetic interference
Designed according to
CSA C22.2 no. 60320-1
General Use Receptacles, Attachment Plugs, and Similar Wiring Devices
Designed according to
CSA C22.2 no. 8
Electromagnetic interference (EMI) filters
Design
Standard
Description
Suitable for applications acc.
IEC/UL 62368-1
Audio/video, information and communication technology equipment - Part
1: Safety requirements
Suitable for applications acc.
IEC 60601-1
Medical electrical equipment - Part 1: General requirements for basic
safety and essential performance
Details
Initiator
Description
CE declaration of conformity
SCHURTER AG
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
UKCA declaration of conformity
SCHURTER AG
The UKCA marking declares that the product complies with the applicable
requirements laid down in the British Amendment of Regulation (EC)
765/2008.
RoHS
SCHURTER AG
Directive RoHS 2011/65/EU, Amendment (EU) 2015/863
China RoHS
SCHURTER AG
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH
SCHURTER AG
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
SCHURTER AG
V-Lock system are based on a matching plug-dose combination. The
connector is equipped with a notch intended for use with the latching
cordset. The cord latching system prevents against accidental removal of
the cordset.
SCHURTER AG
Suitable for use in medical equipment according to IEC/UL 60601-1 (1
MOOP, 1 MOPP)
Product standards
Product standards that are referenced
Organization
Application standards
Application standards where the product can be used
Organization
Compliances
The product complies with following Guide Lines
Identification
Medical Equipment
2
EMC Products
DF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Dimension [mm]
Screw-on mounting
76.2
33.5
10.6
41.2
28.7
2.8
29.4
75.5 ±0.10
82.5 ±0.10
74.3
73.2
37.1
92.5
82.5
R
3.
05
36
R
Ø 6.4
9.7
47.2
29.8
3.
/M
3.5
0.8
Ø
±0.05
3
6
9.65
R6
.5
R
4.
7
5
3
3.
Ø 3.3
±0
R
9.2
R 2.8
10.15
9.7
21.1
.05
75
3.
30.8
±0.10
5.3
* --- Version TA45 with undervoltage release
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [MΩ]
1
Standard
2 x 11
100
2.2
1
2
Standard
2x4
100
2.2
1
3
Standard
2 x 2.5
100
2.2
1
4
Standard
2 x 1.6
100
2.2
1
6
Standard
2 x 0.7
100
2.2
1
8
Standard
2 x 0.6
100
2.2
1
10
Standard
2 x 0.4
100
2.2
1
15
Standard
2 x 0.1
100
2.2
1
2
Medical (M5)
2x4
100
-
1
3
Medical (M5)
2 x 2.5
100
-
1
4
Medical (M5)
2 x 1.6
100
-
1
6
Medical (M5)
2 x 0.7
100
-
1
8
Medical (M5)
2 x 0.6
100
-
1
10
Medical (M5)
2 x 0.4
100
-
1
15
Medical (M5)
2 x 0.1
100
-
1
EMC Products
3
DF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Diagrams
Medical Version (M5)
L’
L
P1
PE
Cy
Cx
N
L2
Cy
TA 45
L1
1)
PE’
N’
2)
PE
Cx
PE’
R
L2
N’
N
2)
P2
1) Line
2) Load
Attenuation Loss
- - - - 50Ω differential mode _____ 50Ω common mode
Standard version
1A
2A
3A
4A
6A
8A
10 A
15 A
1A
2A
3A
4A
6A
8A
10 A
15 A
Medical version (M5)
4
P1
L1
1)
P2
1) Line
2) Load
L’
L
TA 45
Standard version
EMC Products
DF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated current for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient Temperature [°C]
Correction factor
-10
0.89
-5
0.91
0
0.92
+23
1.00
+30
1.03
+40
1.08
+55
1.16
Example: With a nominal current of 5A and an ambient temperature of 40°C, a correction
factor of 1.08 results. This results in a nominal current of 5.5 A, which is rounded up to the
next higher nominal current 6 A.
Time-Current-Curves
Tripping Characteristics In ≥ 3 ... ≤ 15 A
Tripping Characteristics In < 3 A
[ min ] [ sec ]
10’000
[ min ] [ sec ]
10’000
Type
TA45
Rated current
In < 3 A
60
2000
30
20
1000
10
Ambient temp.
Type
TA45
I n > 3... < 15 A
Rated current
1-pole pr otected
60
2- pole protected
30
1-pole p rotected
2’000
20
+23 °C
10
500
2- pole protected
1’000
+23 °C
Ambient temp.
500
5
5
200
200
100
1
100
1
50
20
20
10
10
5
5
2
2
1
1
0,5
0,5
Tripping time
Tripping time
50
0,3
0,2
0,1
1,05 1,32
2
Multiple of rated curr ent
3
4
5
8
10
[ x In ]
0,3
0,2
0,1
1,05 1,32
2
3
4
Multiple of rated cur rent
EMC Products
5
8
10
[ x In ]
5
DF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Order number key
Configuration code TA45
Type
• Circuit Breaker of Equipment
• 2-pole, rocker actuated
• Quick connect terminal
Other types on request
Configuration code TA45
D F12- A B T WF 15 0C 0 - 0 0 0 - 1111 - 0 0 - 2 1
Without release: code C0
Undervoltage release
P2
P2
P1
Remote trip release
P1
b
U<
U<
P2
ba
P2
P1
c P1
U<
Rated
voltage Un
U
E
Z
A
Code
•
•
•
•
2
240 V AC
•
•
•
•
3
230 V AC
•
•
•
•
4
120 V AC
Rated current circuit breaker of equipment
In
Code
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1,0
1,1
1,2
J01
J02
J03
J04
J05
J06
J07
J08
J09
J10
J11
J12
In
1,3
1,4
1,5
1,6
1,7
1,8
1,9
2,0
2,1
2,2
2,3
2,5
Code
In
Code
In
Code
J13
J14
J15
J16
J17
J18
J19
J20
J21
J22
J23
J25
2,8
3,0
3,5
4,0
4,5
5,0
6,0
6,5
7,0
7,5
8,0
9,0
J28
030
035
040
045
050
060
065
070
075
080
090
10,0
11,0
12,0
13,0
14,0
15,0
20,0
100
110
120
130
140
150
200
Rocker legend
Surface
white
M
printed
black
P
printed
I
O
white
R
printed
I
O
black
printed
printed
ON ON
K
L
l
O OFF OFF O
printed
Colour of print
O
H
Illustration
l
embossed
l
F
Position of the rocker legend e.g F
white
black
Colours
Switch front
W
B
6
black
black
black
Rocker
white
black
–
–
–
orange transp.
Diagram
Thermal overload protection
1-pole
2-pole
P2
P2
P1
4
3
6
Without illumination
With illumination
6
EMC Products
220…240 V
110…120 V
P1
3
ABT
ABD
A12
A14
A32
A34
DF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Configuration code TA45
Type
• Circuit Breaker of Equipment
• 2-pole, rocker actuated
• Quick connect terminal
Other types on request
Configuration code TA45
D F 12-A B T WF 15 0C0 - 0 0 0 - 1111 - 0 0 - 2 1
Without release: code C0
Undervoltage release
P2
P2
P1
Remote trip release
P1
b
U<
U<
P2
ba
P2
P1
c P1
U<
Rated
voltage Un
U
E
Z
A
Code
•
•
•
•
2
240 V AC
•
•
•
•
3
230 V AC
•
•
•
•
4
120 V AC
Rated current circuit breaker of equipment
In
Code
In
Code
In
Code
In
Code
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1,0
1,1
1,2
J01
J02
J03
J04
J05
J06
J07
J08
J09
J10
J11
J12
1,3
1,4
1,5
1,6
1,7
1,8
1,9
2,0
2,1
2,2
2,3
2,5
J13
J14
J15
J16
J17
J18
J19
J20
J21
J22
J23
J25
2,8
3,0
3,5
4,0
4,5
5,0
6,0
6,5
7,0
7,5
8,0
9,0
J28
030
035
040
045
050
060
065
070
075
080
090
10,0
11,0
12,0
13,0
14,0
15,0
20,0
100
110
120
130
140
150
200
Rocker legend
Surface
printed
Colour of print
printed
printed
white
M
printed
black
P
printed
I
O
white
R
printed
I
O
black
l
ON ON
l
K
L
O OFF OFF O
H
Illustration
O
embossed
l
F
Position of the rocker legend e.g F
white
black
Colours
Switch front
W
B
6
black
black
black
Rocker
white
black
–
–
–
orange transp.
Diagram
Thermal overload protection
1-pole
2-pole
P2
P2
P1
4
3
6
Without illumination
With illumination
220…240 V
110…120 V
EMC Products
P1
3
ABT
ABD
A12
A14
A32
A34
7
DF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Configuration code (Order example)
Type
Configuration code TA45
DF11- ABTWF150C0 - 000 - 1111 - 00 - 21
Optional Variants
00 Standard
21 V-Lock notch
Colour
0 Black
Mounting
0 Screw mounting
Terminal PE
1 QC 6.3x0.8
Terminal L and N
1 QC 6.3x0.8, without connection to TA45
3 Connection to TA45 non insulated
Type of mains filter / capacitor / bleed resistor
1 Standard X2, Y2 with bleed resistor
3 Medical M5 X2 with bleed resistor
Rated current
11A
22A
33A
44A
56A
68A
7 10 A
9 15 A
The rated current of the mains filter must not be less than
the tripping current of the circuit breaker for equipment.
Only the rated filter current is shown in the item description on the packaging.
8
EMC Products
DF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Configuration code (Order example)
Type
Configuration code TA45
DF11- ABTWF150C0 - 000 - 1111 - 00 - 21
Optional Variants
00 Standard
21 V-Lock notch
Colour
0 Black
Mounting
0 Screw mounting
Terminal PE
1 QC 6.3x0.8
Terminal L and N
1 QC 6.3x0.8, without connection to TA45
3 Connection to TA45 non insulated
Type of mains filter / capacitor / bleed resistor
1 Standard X2, Y2 with bleed resistor
3 Medical M5 X2 with bleed resistor
Rated current
11A
22A
33A
44A
56A
68A
7 10 A
9 15 A
The rated current of the mains filter must not be less than
the tripping current of the circuit breaker for equipment.
Only the rated filter current is shown in the item description on the packaging.
Variants
Circuit Breakers
Filter
Connectors
Rated Current [A]
Rocker colour
Illumination
Add-on modules
Rated Current [A]
Filter Type
Protection
Class
1
black
non-illuminated
without
1
Standard
10
white
non-illuminated
without
10
15
white
non-illuminated
without
15
black
non-illuminated
without
V-Lock
Internally
wired
Config. Code
Order Number
I
prewired
DF12-ABDBLJ10C0-000-1131-00-00
DF12.1310.1110.1
Standard
I
prewired
DF12-ABDWF100C0-000-7131-00-00
DF12.0470.7110.1
15
Standard
I
prewired
DF12-ABDWF150C0-000-9131-00-00
DF12.0885.9110.1
15
Standard
I
prewired
DF12-ABDBL150C0-000-9131-00-00
DF12.1089.9110.1
EMC Products
9
DF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Circuit Breakers
Filter
Connectors
Rated Current [A]
Rocker colour
Illumination
Add-on modules
Rated Current [A]
Filter Type
Protection
Class
15
orange
illuminated
without
15
Standard
2
orange
illuminated
without
2
3
orange
illuminated
without
4
orange
illuminated
5
black
8
V-Lock
Internally
wired
Config. Code
Order Number
I
prewired
DF12A326F150C0-000-9131-00-00
DF12.2851.9110.1
Standard
I
prewired
DF12A326KJ20C0-000-2131-00-00
DF12.3803.2110.1
3
Standard
I
prewired
DF12A326K030C0-000-3131-00-00
DF12.3635.3110.1
without
4
Standard
I
prewired
DF12A346K040C0-000-4131-00-00
DF12.3945.4110.1
non-illuminated
without
6
Standard
I
prewired
DF12-ABTWF050C0-000-5131-00-00
DF12.0586.5110.1
white
non-illuminated
without
8
Standard
I
prewired
DF12-ABTWF080C0-000-6131-00-00
DF12.0423.6110.1
10
white
non-illuminated
without
10
Medical (M5)
I
prewired
DF12-ABDWF100C0-000-7331-00-00
DF12.0470.7310.1
10
black
non-illuminated
without
10
Medical (M5)
I
prewired
DF12-ABDBL100C0-000-7331-00-00
DF12.2078.7310.1
12
black
non-illuminated
without
15
Medical (M5)
I
prewired
DF12-ABDBL120C0-000-9331-00-00
DF12.2420.9310.1
15
white
non-illuminated
without
15
Medical (M5)
I
prewired
DF12-ABTWF150C0-000-9331-00-00
DF12.0031.9310.1
15
black
non-illuminated
Remote trip
release
15
Medical (M5)
I
prewired
DF12-ABDBH150A3-000-9331-00-00
DF12.4051.9310.1
2
black
non-illuminated
without
2
Medical (M5)
I
prewired
DF12-ABDWRJ20C0-000-2331-00-00
DF12.3171.2310.1
3
black
non-illuminated
without
3
Medical (M5)
I
prewired
DF12-ABDBL030C0-000-3331-00-21
DF12.2370.3310.121
4
orange
illuminated
without
4
Medical (M5)
I
prewired
DF12A326H040C0-000-4331-00-00
DF12.0723.4310.1
6
black
non-illuminated
without
6
Medical (M5)
I
prewired
DF12-ABDBP060C0-000-5331-00-21
DF12.1488.5310.121
7
orange
illuminated
without
8
Medical (M5)
I
prewired
DF12A346R070C0-000-6331-00-00
DF12.3737.6310.1
l
l
Availability for all products can be searched real-time: https://www.schurter.com/en/info-center/support-tools/stock-check-distributors
Packaging unit
20 Pcs
Accessories
Description
Assorted_Covers
Rear Cover
0859.0109
RC320
Rear Cover for Power Entry Module
10
EMC Products
DF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Mating Outlets/Connectors
Category / Description
Appliance Outlet Overview complete
4787, Mounting: Screw-on mounting, Appliance Outlet: IEC Solder terminals, 10 A, Suitable for appliances with protection class I
4787
4788, Mounting: Snap-in version, Appliance Outlet: IEC Solder / Quick Connect, 10 A, Suitable for appliances with
protection class I
4788
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal
5091
Connector Overview complete
4782 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4782
4785 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4785
4300-06 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4300-06
4781 Mounting: Power Cord, Cable, Connector: IEC C15
4781
4784 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C15
4784
Mating Outlets/Connectors shuttered
Connector Overview complete
4783 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4783
Power Cord Overview complete
VAC13KS, Overview, V-Lock cord retaining, diverse Connector IEC C13, diverse, black
VAC13KS
28.03.2024
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
EMC Products
11