EF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
IEC Appliance Inlet C20 with Filter, Circuit Breaker TA45 (recessed)
Screw-on from front side
Rocker illuminated
orange
Screw-on from front side
Rocker non-illuminated
white
C20
See below:
Approvals and Compliances
70° C
Description
- Panel mount :
Screw-on mounting front side
- 3 Functions :
Appliance Inlet Protection class I , circuit breaker type TA45 2-pole
, Line filter in standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
Characteristics
- All single elements are already wired
- Circuit Breaker non-illuminated or illuminated
- With EMC-shield
- For applications according IEC/UL 62368-1 we recommend variants
with bleed resistor
Suitable for use in medical equipment according to IEC/UL 60601-1 (1
MOOP, 1 MOPP)
Other versions on request
- Variant with notch for V-Lock mating Cordsets
References
Alternative: version without line filter EF11
Alternative: Standard version
Weblinks
pdf data sheet, html datasheet, General Product Information, Approvals,
Distributor-Stock-Check, Accessories, Detailed request for product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temperature
Climatic Category
IP-Protection
Protection Class
Terminal
Panel Thickness S
Material
12 - 16 A @ Ta 40 °C / 250 VAC; 50 Hz
12 - 20 A @ Ta 40 °C / 250 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-10 °C to 55 °C
10/055/21 acc. to IEC 60068-1
front side IP40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Appliance inlet/-outlet
Circuit Breakers
Line Filter
MTBF
C20 acc. to IEC 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 16 A,
Protection Class I
Acc. IEC/EN 60934, UL 1077, CSA
22.2 no. 235
2-pole rocker switch, illuminated or nonilluminated. Optional with undervoltageor remote trip release
Short circuit capacity Icn:
at In < 3A/240VAC : 10 x In
at In ≥ 3A/240VAC : 300A
Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
> 100'000 h acc. to MIL-HB-217 F
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agreements by SCHURTER.
EMC Products
1
EF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: EF12
Approval Logo
Certificates
Certification Body
Description
VDE Approvals
VDE
Certificate Number: 40001520
UL Approvals
UL
UR File Number: E72928
Design
Standard
Description
Designed according to
IEC 60320-1
Appliance couplers for household and similar general purposes
Designed according to
IEC 60939
Passive filters for suppressing electromagnetic interference
Designed according to
IEC 61058-1
Switches for appliances. Part 1. General requirements
Designed according to
UL 498
Standard for Attachment Plugs and Receptacles
Designed according to
UL 1283
Electromagnetic interference filters
Designed according to
CSA C22.2 no. 42
General Use Receptacles, Attachment Plugs, and Similar Wiring Devices
Designed according to
CSA C22.2 no. 8
Electromagnetic interference (EMI) filters
Design
Standard
Description
Suitable for applications acc.
IEC/UL 62368-1
Audio/video, information and communication technology equipment - Part
1: Safety requirements
Suitable for applications acc.
IEC 60601-1
Medical electrical equipment - Part 1: General requirements for basic
safety and essential performance
Details
Initiator
Description
CE declaration of conformity
SCHURTER AG
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
UKCA declaration of conformity
SCHURTER AG
The UKCA marking declares that the product complies with the applicable
requirements laid down in the British Amendment of Regulation (EC)
765/2008.
RoHS
SCHURTER AG
Directive RoHS 2011/65/EU, Amendment (EU) 2015/863
China RoHS
SCHURTER AG
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH
SCHURTER AG
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
SCHURTER AG
V-Lock system are based on a matching plug-dose combination. The
connector is equipped with a notch intended for use with the latching
cordset. The cord latching system prevents against accidental removal of
the cordset.
SCHURTER AG
Suitable for use in medical equipment according to IEC/UL 60601-1 (1
MOOP, 1 MOPP)
Product standards
Product standards that are referenced
Organization
Application standards
Application standards where the product can be used
Organization
Compliances
The product complies with following Guide Lines
Identification
Medical Equipment
2
EMC Products
EF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Dimension [mm]
37
2.8
76.2
10.6
32.2
41.2
32.9
ø3.6/M3
81±0.10
90 ±0.10
80.05
12.6
.5
R6
9.5
ø3.3
59.5
5.3
33.9 ±0.10
4.55 ±0.05
4.
7
05
3.
R
R
10.9
R 2.8
5.5
79.2
12.2
40.55
90
101
R
3.
55
±0
.0
5
0.8
ø6.4
* --- Version TA45 with undervoltage release
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [MΩ]
12
Standard version
2 x 0.8
100
2.2
1
16
Standard version
2 x 0.6
100
2.2
1
20
Standard version
2 x 0.3
100
2.2
1
12
Medical Version (M5)
2 x 0.8
100
-
1
16
Medical Version (M5)
2 x 0.6
100
-
1
20
Medical Version (M5)
2 x 0.3
100
-
1
Diagrams
Standard version
L’
L
P1
PE
N
1) Line
2) Load
Cx
TA 45
L1
1)
PE’
R
L2
N’
P2
L’
L
2)
P1
L1
1)
PE
Cx
Cy
R
L2
N
Cy
PE’
N’
2)
TA 45
Medical Version (M5)
P2
1) Line
2) Load
EMC Products
3
EF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Attenuation Loss
- - - - 50Ω differential mode _____ 50Ω common mode
Standard version
20 A
16 A
12 A
16 A
12 A
Medical version (M5)
20 A
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated current for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient Temperature [°C]
Correction factor
-10
0.89
-5
0.91
0
0.92
+23
1.00
+30
1.03
+40
1.08
+55
1.16
Example: With a nominal current of 5A and an ambient temperature of 40°C, a correction
factor of 1.08 results. This results in a nominal current of 5.5 A, which is rounded up to the
next higher nominal current 6 A.
4
EMC Products
EF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Time-Current-Curves
Tripping Characteristics In ≥ 3. . . < 18 A
Tripping Characteristics In ≥ 18 A
Tripping Characteristics In < 3 A
EMC Products
5
EF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Order number key
Configuration code (Order example)
Type
Configuration code TA45
EF12 - A 3 2 6 M 1 5 0 C 0 - 0 0 0 - 2 1 3 1 - 1 0 - 0 0
Color
0 black
Interlocking
0 without V-Lock
1 with V-Lock
Terminal PE
0 without (PCII)
1 QC 6.3x0.8
Terminal L and N
1 QC 6.3x0.8, without connection to TA45
3 Connection to TA45 non insulated
Type of mains fi lter / capacitor / bleed resistor
1 standard
X2,Y2
with bleed resistor
2 medical M5
X2
with bleed resistor
Rated current
1 20 A
2 16 A
3 12 A
The rated current of the mains filter must not be less than
the tripping current of the circuit breaker for equipment.
Only the rated filter current is shown in the item description on the packaging.
6
EMC Products
EF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Configuration code TA45
Type
• Circuit Breaker of Equipment
• 2-pole, rocker actuated
• Quick connect terminal
Other types on request
Configuration code TA45
EF12 - A 3 2 6 M 1 5 0 C 0 - 0 0 0 - 2 1 3 1 - 1 0 - 0 0
3
5
a
P1
Without release: code C0
Undervoltage release
P2
P1
P2
U<
Remote trip release
P1
b
P2
ba
P1
P2
c P1
U<
U<
U
E
Z
A
Code
Rated
voltage Un
•
•
•
•
2
240 V AC
•
•
•
•
3
230 V AC
•
•
•
•
4
120 V AC
Rated current circuit breaker of equipment
In
Code
In
Code
In
Code
In
Code
10,0
11,0
12,0
100
110
120
13,0
14,0
15,0
130
140
150
16,0
17,0
18,0
160
170
180
19,0
20,0
190
200
Other rated currents on request
Rocker legend
Colour of print
printed
L
printed
M
printed
black
P
printed
I
O
white
R
printed
I
O
black
white
white
l
ON
O
K
OFF OFF
printed
O
H
l
embossed
ON
F
O
Illustration
l
Surface
Position of the rocker legend e.g F
black
Colours
Switch front
W
B
6
Rocker
black
black
black
white
black
–
–
–
orange transp.
Diagram
Thermal overload protection
1-pole
P2
Without illumination
With illumination
P1
6
220…240 V
110…120 V
EMC Products
3
2-pole
P2
P1
4
3
ABT
ABD
A12
A14
A32
A34
7
EF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Configuration code (Order example)
Type
Configuration code TA45
EF12 - A 3 2 6 M 1 5 0 C 0 - 0 0 0 - 2 1 3 1 - 1 0 - 0 0
Color
0 black
Interlocking
0 without V-Lock
1 with V-Lock
Terminal PE
0 without (PCII)
1 QC 6.3x0.8
Terminal L and N
1 QC 6.3x0.8, without connection to TA45
3 Connection to TA45 non insulated
Type of mains fi lter / capacitor / bleed resistor
1 standard
X2,Y2
with bleed resistor
2 medical M5
X2
with bleed resistor
Rated current
1 20 A
2 16 A
3 12 A
The rated current of the mains filter must not be less than
the tripping current of the circuit breaker for equipment.
Only the rated filter current is shown in the item description on the packaging.
8
EMC Products
EF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Configuration code TA45
Type
• Circuit Breaker of Equipment
• 2-pole, rocker actuated
• Quick connect terminal
Other types on request
Configuration code TA45
EF12 - A 3 2 6 M 1 5 0 C 0 - 0 0 0 - 2 1 3 1 - 1 0 - 0 0
3
5
a
P1
Without release: code C0
Undervoltage release
P2
P1
P2
U<
Remote trip release
P1
b
P2
ba
P1
P2
c P1
U<
U<
U
E
Z
A
Code
Rated
voltage Un
•
•
•
•
2
240 V AC
•
•
•
•
3
230 V AC
•
•
•
•
4
120 V AC
Rated current circuit breaker of equipment
In
Code
In
Code
In
Code
In
Code
10,0
11,0
12,0
100
110
120
13,0
14,0
15,0
130
140
150
16,0
17,0
18,0
160
170
180
19,0
20,0
190
200
Other rated currents on request
Rocker legend
Colour of print
printed
L
printed
M
printed
black
P
printed
I
O
white
R
printed
I
O
black
white
white
l
ON
O
K
OFF OFF
printed
O
H
l
embossed
ON
F
O
Illustration
l
Surface
Position of the rocker legend e.g F
black
Colours
Switch front
W
B
6
Rocker
black
black
black
white
black
–
–
–
orange transp.
Diagram
Thermal overload protection
1-pole
P2
Without illumination
With illumination
P1
6
220…240 V
110…120 V
EMC Products
3
2-pole
P2
P1
4
3
ABT
ABD
A12
A14
A32
A34
9
EF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Variants
Circuit Breakers
Filter
Connectors
Rated Current [A]
Rocker colour
Illumination
Add-on modules
Rated Current [A]
Filter Type
Protection
Class
12
black
non-illuminated
-
12
Standard
version
15
black
non-illuminated
-
16
15
black
non-illuminated
-
16
black
non-illuminated
16
black
16
V-Lock
Internally
wired
Config. Code
Order Number
I
prewired
EF12-ABDWF120C0-000-3131-00-00
EF12.1034.3110.01
Standard
version
I
prewired
EF12-ABDWF150C0-000-2131-00-00
EF12.0885.2110.01
20
Standard
version
I
prewired
EF12-ABDBL150C0-000-1131-00-00
EF12.1089.1110.01
-
16
Standard
version
I
prewired
EF12-ABTWF160C0-000-2131-00-00
EF12.0034.2110.01
non-illuminated
-
16
Standard
version
I
prewired
EF12-ABDWF160C0-000-2131-00-00
EF12.0699.2110.01
black
non-illuminated
-
16
Standard
version
I
prewired
EF12-ABDBL160C0-000-2131-00-00
EF12.2105.2110.01
16
black
non-illuminated
-
16
Standard
version
I
prewired
EF12-ABTBP160C0-000-2131-00-00
EF12.3103.2110.01
20
black
non-illuminated
-
20
Standard
version
I
prewired
EF12-ABTWF200C0-000-1131-00-00
EF12.0035.1110.01
20
black
non-illuminated
-
20
Standard
version
I
prewired
EF12-ABDWF200C0-000-1131-00-00
EF12.0572.1110.01
20
black
non-illuminated
-
20
Standard
version
I
prewired
EF12-ABTWF200U2-000-1131-00-00
EF12.1164.1110.01
20
black
non-illuminated
-
20
Standard
version
I
prewired
EF12-ABDBL200C0-000-1131-00-00
EF12.2196.1110.01
20
black
non-illuminated
-
20
Standard
version
I
prewired
EF12A326K200C0-000-1131-00-00
EF12.2561.1110.01
20
black
non-illuminated
-
20
Standard
version
I
prewired
EF12-ABDWM200C0-000-1131-00-00
EF12.2961.1110.01
20
black
non-illuminated
-
20
Standard
version
I
prewired
EF12A126K200C0-000-1131-00-00
EF12.3197.1110.01
16
black
non-illuminated
-
16
Medical Version (M5)
I
prewired
EF12-ABDWF160C0-000-2231-00-00
EF12.0699.2210.01
20
black
non-illuminated
-
20
Medical Version (M5)
I
prewired
EF12-ABTWF200C0-000-1231-00-00
EF12.0035.1210.01
█ Most Popular.
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
Packaging unit
16 Pcs
Accessories
Description
Cord_retaining_kits
Cord retaining strain relief
Flat head, H
10
EMC Products
4700.0008
█
█
█
█
EF12
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Mating Outlets/Connectors
Category / Description
Connector Overview complete
4795, Mounting: Power Cord, Cable Connector: IEC C19
4795
4790, Mounting: Power Cord, Screw Connector: IEC C19
4790
0104U, Mounting: Power Supply Cord, Screw clamps Connector: IEC C19
0104U
Mating Outlets/Connectors shuttered
Power Cord Overview complete
VAC19KS, Overview, V-Lock cord retaining, diverse Connector IEC C19, diverse, black
VAC19KS
15.08.2023
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
EMC Products