KMF
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
IEC Appliance Inlet with Filter, Fuseholder 1- or 2-pole, Line Switch 2-pole
Protection class I with shield
C14
Protection class II without shield
C18
See below:
Approvals and Compliances
70° C
70° C
Description
- Panel mount :
Snap-in version front side
- 4 Functions :
Appliance Inlet protection class I or II , Line Switch 2-pole , Fuseholder
for fuse-links 5 x 20 mm 1‑ or 2‑pole , Line filter in standard and medical version
- Quick connect terminals 4.8 x 0.8 mm
Unique Selling Proposition
- Most compact solution on the market
- Innovative EMC-shielding
- Easy and flexible snap-in mounting
- Protection class I or II versions
Characteristics
- Ultra-compact design. Small dimensions in front of and behind the panel
- All single elements are already wired
- For added safety "Extra-Safe" fuse drawers are available
- Innovative EMC-shielding with flexible steel segments for an excellent
contact
- Suitable for use in medical equipment according to IEC/UL 60601-1 (1
MOOP, 1 MOPP)
For applications according IEC/UL 62368-1 we recommend variants
with bleed resistor
Other versions on request
- Fuse drawer 1-pole, plus spare fuse case
- Fuse drawer 2-pole, with shorting bar
- Other rocker marking
References
Alternative: version without line filter KM
Alternative: version for screw mounting DD12
Weblinks
pdf data sheet, html datasheet, General Product Information, Approvals,
Distributor-Stock-Check, Accessories, Detailed request for product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temperature
Climatic Category
IP-Protection
Protection Class
Terminal
Panel Thickness S
Material
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 250 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
front side IP40 acc. to IEC 60529
Suitable for appliances with protection
class I or II acc. to IEC 61140
Quick connect terminals 4.8 x 0.8 mm
Snap-in: 1/1.5/2/2.5 mm
(all steps with one variant)
Thermoplastic, black, UL 94V-0
Appliance inlet/-outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Switch
Line Filter
MTBF
C14 C18 acc. to IEC 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class I or II
1-/2-pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 2 W (1 pole)/ 1.6 W (2-pole) per
pole
Admissible power acceptance at higher
ambient temperature see derating curves
2-pole, non-illuminated, acc. to IEC
61058-1
Technical Details
Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
> 1'800'000 h acc. to MIL-HB-217 F
Approvals and Compliances
EMC Products
1
KMF
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agreements by SCHURTER.
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: KMF
Approval Logo
Certificates
Certification Body
Description
VDE Approvals
VDE
Certificate Number: 40035743
UL Approvals
UL
UR File Number: E72928
CQC Approvals
CQC
CQC Certificate Number: 18001186843, 22001363976
Design
Standard
Description
Designed according to
IEC 60320-1
Appliance couplers for household and similar general purposes
Designed according to
IEC 60939
Passive filters for suppressing electromagnetic interference
Designed according to
IEC 60127-6
Miniature fuses. Part 6. Fuse-holders for miniature fuse-links
Designed according to
IEC 61058-1
Switches for appliances. Part 1. General requirements
Designed according to
UL 498
Standard for Attachment Plugs and Receptacles
Designed according to
UL 1283
Electromagnetic interference filters
Designed according to
CSA C22.2 no. 42
General Use Receptacles, Attachment Plugs, and Similar Wiring Devices
Designed according to
CSA C22.2 no. 8
Electromagnetic interference (EMI) filters
Design
Standard
Description
Suitable for applications acc.
IEC/UL 62368-1
Audio/video, information and communication technology equipment - Part
1: Safety requirements
Suitable for applications acc.
IEC 60601-1
Medical electrical equipment - Part 1: General requirements for basic
safety and essential performance
Suitable for applications acc.
IEC 60335-1
Safety of electrical appliances for household and similar purposes. Meets
the requirements for appliances in unattended use. This includes the
enhanced requirements of glow wire tests acc. to IEC 60695-2-11 or -12
& -13.
Product standards
Product standards that are referenced
Organization
Application standards
Application standards where the product can be used
Organization
2
EMC Products
KMF
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Compliances
The product complies with following Guide Lines
Identification
Details
Initiator
Description
CE declaration of conformity
SCHURTER AG
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
UKCA declaration of conformity
SCHURTER AG
The UKCA marking declares that the product complies with the applicable
requirements laid down in the British Amendment of Regulation (EC)
765/2008.
RoHS
SCHURTER AG
Directive RoHS 2011/65/EU, Amendment (EU) 2015/863
China RoHS
SCHURTER AG
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH
SCHURTER AG
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
White Paper Glow wire test
SCHURTER AG
Meets the requirements of IEC 60335-1 for appliances in unattended use.
This includes the enhanced requirements of glow wire tests acc. to IEC
60695-2-11 or -12 &-13.
Medical Equipment
SCHURTER AG
Suitable for use in medical equipment according to IEC/UL 60601-1 (1
MOOP, 1 MOPP)
Dimension [mm]
30.4
Panel cut-out
+0.10
28 - 0.05
+0.10
10.7
ma
x.
R0
.3
32
50
46.8
47 - 0.05
25.7
.5
R1
S ±0.05
30.5
27.8
2.5
40.4
Mounting cut-out
Stepped snapper for
mounting panel thickness
S= 1.0 / 1.5 / 2.0 / 2.5
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [MΩ]
1
Standard version
2 x 11
47
2.2
-
2
Standard version
2x4
47
2.2
-
4
Standard version
2 x 1.6
47
2.2
-
6
Standard version
2 x 0.7
47
2.2
-
10
Standard version
2 x 0.4
47
2.2
-
1
Medical Version (M5)
2 x 11
47
-
1
2
Medical Version (M5)
2x4
47
-
1
4
Medical Version (M5)
2 x 1.6
47
-
1
6
Medical Version (M5)
2 x 0.7
47
-
1
EMC Products
3
KMF
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
10
Medical Version (M5)
2 x 0.4
47
-
1
Diagrams
Standard version
Medical Version (M5)
L
L
L’
F1
L1
1)
2)
Cy
PE
Cx
L2
F2
Cy
N
PE
PE’
L’
L1
1)
N’
F1
Cx
L2
PE’
F2
N’
N
1) Line
2) Load
2)
R
1) Line
2) Load
Medicalversion (M5), Protection Class II
L
L’
L1
1)
F1
2)
R
Cx
L2
F2
N’
N
1) Line
2) Load
Derating Curves
2-pole
Admissible power
acceptance in Watt
2.0
1.5
I = 1.0 In
I = 0.7 In
1.0
I =
很抱歉,暂时无法提供与“KMF1.1243.11”相匹配的价格&库存,您可以联系我们找货