Data sheet
US2:17CUB82NF10
Non-reversing motor starter Size 0 Three phase full voltage Solid-state
overload relay OLRelay amp range 0.75-3.4A 110VAC 50HZ / 120VAC
60HZ coil Combination type 30Amp fusible disconnect 30Amp / 250V fuse
clip Enclosure NEMA type 4/12 Water/dust tight weather proof Extra-wide
enclosure
product brand name
Class 17
design of the product
Non-reversing motor starter with fusible disconnect
special product feature
ESP200 overload relay
General technical data
weight [lb]
Height x Width x Depth [in]
47 lb
touch protection against electrical shock
NA for enclosed products
installation altitude [ft] at height above sea level maximum
6560 ft
24 × 20 × 8 in
ambient temperature [°F]
● during storage
-22 ... +149 °F
● during operation
-4 ... +104 °F
ambient temperature
● during storage
-30 ... +65 °C
● during operation
-20 ... +40 °C
country of origin
USA
Horsepower ratings
yielded mechanical performance [hp] for 3-phase AC
motor
● at 200/208 V rated value
0.5 hp
● at 220/230 V rated value
0.75 hp
● at 460/480 V rated value
0 hp
● at 575/600 V rated value
0 hp
Contactor
size of contactor
NEMA controller size 0
number of NO contacts for main contacts
3
operating voltage for main current circuit at AC at 60 Hz
maximum
600 V
operational current at AC at 600 V rated value
18 A
mechanical service life (switching cycles) of the main
contacts typical
10000000
Auxiliary contact
number of NC contacts at contactor for auxiliary contacts
0
number of NO contacts at contactor for auxiliary contacts
1
number of total auxiliary contacts maximum
8
contact rating of auxiliary contacts of contactor according
to UL
10A@600VAC (A600), 5A@600VDC (P600)
Coil
US2:17CUB82NF10
Page 1/2
1.21.2021
Subject to change without notice
© Copyright Siemens
type of voltage of the control supply voltage
AC
control supply voltage
● at AC at 50 Hz rated value
110 V
● at AC at 60 Hz rated value
120 V
holding power at AC minimum
8.6 W
apparent pick-up power of magnet coil at AC
218 V·A
apparent holding power of magnet coil at AC
25 V·A
operating range factor control supply voltage rated value
of magnet coil
0.85 ... 1.1
percental drop-out voltage of magnet coil related to the
input voltage
50 %
switch ON delay time
19 ... 29 ms
OFF delay time
10 ... 24 ms
Overload relay
product function
● overload protection
Yes
● phase failure detection
Yes
● asymmetry detection
Yes
● ground fault detection
Yes
● test function
Yes
● external reset
Yes
reset function
Manual, automatic and remote
trip class
Class 5 / 10 / 20 (factory set) / 30
adjustable current response value current of the currentdependent overload release
0.75 ... 3.4 A
tripping time at phase-loss maximum
3s
relative repeat accuracy
1%
product feature protective coating on printed-circuit board
Yes
number of NC contacts of auxiliary contacts of overload
relay
1
number of NO contacts of auxiliary contacts of overload
relay
1
operational current of auxiliary contacts of overload relay
● at AC at 600 V
5A
● at DC at 250 V
1A
contact rating of auxiliary contacts of overload relay
according to UL
5A@600VAC (B600), 1A@250VDC (R300)
insulation voltage
● with single-phase operation at AC rated value
600 V
● with multi-phase operation at AC rated value
300 V
Disconnect Switch
response value of switch disconnector
30A / 250V
design of fuse holder
Class R fuse clips
operating class of the fuse link
Class R
Enclosure
degree of protection NEMA rating
4, 12
design of the housing
Dust-tight, watertight & weather proof
Mounting/wiring
mounting position
vertical
fastening method
Surface mounting and installation
type of electrical connection for supply voltage line-side
Box lug
tightening torque [lbf·in] for supply
35 ... 35 lbf·in
type of connectable conductor cross-sections at line-side
at AWG cables single or multi-stranded
1x (14 ... 2 AWG)
temperature of the conductor for supply maximum
permissible
75 °C
material of the conductor for supply
AL or CU
type of electrical connection for load-side outgoing feeder
Screw-type terminals
tightening torque [lbf·in] for load-side outgoing feeder
20 ... 24 lbf·in
type of connectable conductor cross-sections at AWG
2x (14 ... 10 AWG)
US2:17CUB82NF10
Page 2/3
1.21.2021
Subject to change without notice
© Copyright Siemens
cables for load-side outgoing feeder single or multistranded
temperature of the conductor for load-side outgoing feeder
maximum permissible
75 °C
material of the conductor for load-side outgoing feeder
CU
type of electrical connection of magnet coil
Screw-type terminals
tightening torque [lbf·in] at magnet coil
5 ... 12 lbf·in
type of connectable conductor cross-sections of magnet
coil at AWG cables single or multi-stranded
2x (16 ... 12 AWG)
temperature of the conductor at magnet coil maximum
permissible
75 °C
material of the conductor at magnet coil
CU
type of electrical connection for auxiliary contacts
Screw-type terminals
tightening torque [lbf·in] at contactor for auxiliary contacts
10 ... 15 lbf·in
type of connectable conductor cross-sections at contactor
at AWG cables for auxiliary contacts single or multistranded
1x (12 AWG), 2x (16 ... 14 AWG), 2x (18 ... 16 AWG)
temperature of the conductor at contactor for auxiliary
contacts maximum permissible
75 °C
material of the conductor at contactor for auxiliary contacts
CU
type of electrical connection at overload relay for auxiliary
contacts
Screw-type terminals
tightening torque [lbf·in] at overload relay for auxiliary
contacts
7 ... 10 lbf·in
type of connectable conductor cross-sections at overload
relay at AWG cables for auxiliary contacts single or multistranded
2x (20 ... 14 AWG)
temperature of the conductor at overload relay for auxiliary
contacts maximum permissible
75 °C
material of the conductor at overload relay for auxiliary
contacts
CU
Short-circuit current rating
design of the fuse link for short-circuit protection of the
main circuit required
10kA@600V (Class H or K); 100kA@600V (Class R or J)
certificate of suitability
NEMA ICS 2; UL 508; CSA 22.2, No.14
Further information
Industrial Controls - Product Overview (Catalogs, Brochures,…)
www.usa.siemens.com/iccatalog
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/us/Catalog/product?mlfb=US2:17CUB82NF10
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/US/en/ps/US2:17CUB82NF10
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=US2:17CUB82NF10&lang=en
Certificates/approvals
https://support.industry.siemens.com/cs/US/en/ps/US2:17CUB82NF10/certificate
US2:17CUB82NF10
Page 3/4
1.21.2021
Subject to change without notice
© Copyright Siemens
US2:17CUB82NF10
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
US2:17CUB82NF10
Page 5/5
3/13/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“17CUB82NF10”相匹配的价格&库存,您可以联系我们找货