Data sheet
3LD2405-1TL11
SENTRON, Switch disconnector 3LD, main switch, 4-pole, Iu=250 A, Operating
power / at AC-23 A at 400 V: 132 kW, front-mounted, knob-operated mechanism,
black, 4-hole mounting of the handle
Model
product brand name
SENTRON
product designation
Switch disconnector
design of the product
Main switch
display version for switch position indicator manual operation
1 ON - 0 OFF
type of switch
front mounted
design of the actuating element
selector switch
color of the actuating element
black
design of handle
knob-operated mechanism, black
type of the driving mechanism motor drive
No
General technical data
number of poles
4
size of switch disconnector
5
mechanical service life (operating cycles) typical
100 000
electrical endurance (operating cycles)
● at AC-23 A at 690 V
6 000
operating frequency maximum
50 1/h
degree of pollution
3
Voltage
insulation voltage rated value
690 V
surge voltage resistance rated value
8 kV
operating voltage
● at AC rated value
690 V
operating frequency rated value
● minimum
50 Hz
● maximum
60 Hz
Protection class
protection class IP
IP65
degree of protection NEMA rating
1, 3R, 4X, 12
protection class IP on the front
IP65
Dissipation
power loss [W] for rated value of the current at AC in hot
operating state per pole
36 W
Main circuit
operational current
● at AC-21 at 690 V rated value
250 A
● at AC-21 A at 240 V rated value
250 A
● at AC-21 A at 400 V rated value
250 A
● at AC-21 A at 440 V rated value
250 A
● at AC-23 A at 400 V rated value
224 A
3LD24051TL11
Page 1/6
5/8/2024
Subject to change without notice
© Copyright Siemens
operating power
● at AC-23 A at 240 V rated value
75 kW
● at AC-23 A at 400 V rated value
132 kW
● at AC-23 A at 440 V rated value
132 kW
● at AC-23 A at 690 V rated value
55 kW
● at AC-3 at 240 V rated value
55 kW
● at AC-3 at 400 V rated value
110 kW
● at AC-3 at 690 V rated value
45 kW
Auxiliary circuit
number of CO contacts for auxiliary contacts
0
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
0
operating voltage of auxiliary contacts at AC maximum
500 V
continuous current of the auxiliary contact rated value
10 A
Suitability
suitability for use
● main switch
Yes
● switch disconnector
Yes
● EMERGENCY OFF switch
No
● safety switch
Yes
● maintenance/repair switch
Yes
Product details
product feature can be locked into OFF position
Yes
accessories
product extension optional
● motor drive
No
● voltage trigger
No
number of connectable NC contacts for auxiliary contacts
attachable maximum
2
number of connectable NO contacts for auxiliary contacts
attachable maximum
2
number of connectable CO contacts for auxiliary contacts
attachable maximum
0
number of bracket locks maximum
3
hasp thickness of the bracket locks
4 ... 6 mm
Short circuit
conditional short-circuit current with line-side fuse protection
● at 690 V by gG fuse rated value
50 kA
let-through current with closed switch
● at 240 V for combination switch + gG fuse maximum
15 kA
● at 440 V for combination switch + gG fuse maximum
15 kA
● at 690 V for combination switch + gG fuse maximum
permissible
15 kA
I2t value with closed switch
● at 240 V for combination switch + gG fuse maximum
557 kA2.s
● at 440 V for combination switch + gG fuse maximum
557 kA2.s
● at 690 V for combination switch + gG fuse maximum
557 kA2.s
design of the fuse link
● for short-circuit protection of the main circuit required
fuse gL/gG: 250 A
● for short-circuit protection of the auxiliary switch required
fuse gL/gG: 10 A
operational current of upstream fuse rated value
250 A
according UL
operational current at AC according to UL 508/UL 60947-4-1
rated value
250 A
operating voltage at AC at 50/60 Hz according to UL 508/UL
60947-4-1 rated value
600 V
active power [hp] at AC at 480 V according to UL 508/UL 609474-1 rated value
100
active power [hp] at AC at 600 V according to UL 508/UL 609474-1 rated value
75
short-time withstand current (SCCR) at 600 V according to UL
508/UL 60947-4-1
10 kA
continuous current of upstream fuse according to UL rated value
200 A
3LD24051TL11
Page 2/6
5/8/2024
Subject to change without notice
© Copyright Siemens
type of fuse according to UL
RK5
Connections
AWG number as coded connectable conductor cross section
solid maximum
●
1
●
4/0
type of connectable conductor cross-sections for copper
conductor
● solid
1x (16 ...185mm²)
● finely stranded with core end processing
1x (16...150mm²)
● stranded
1x (16...185mm²)
type of connectable conductor cross-sections for auxiliary
contacts
● solid
lateral auxiliary switch 2x (0,75 ... 2,5mm²), 1x 4mm²; front auxiliary switch 1x
(0,75 ... 2,5mm²)
● finely stranded with core end processing
lateral auxiliary switch 2x (0,75 ... 1,5mm²), 1x 2,5mm²; front auxiliary switch 1x
2,5mm²
● stranded
lateral auxiliary switch 2x (0,75 ... 2,5mm²), 1x 4mm²; front auxiliary switch 1x
(0,75 ... 2,5mm²)
type of electrical connection
● for main current circuit
box terminal
● for auxiliary contacts
connection terminals
Mechanical Design
height
169 mm
width
112 mm
depth
94 mm
type of device
fixed mounting
fastening method
Built-in unit fixed-mounted version
fastening method
● 4-hole front mounting
Yes
● front mounting with central attachment
No
● rail mounting
No
net weight
2 611 g
Environmental conditions
ambient temperature during operation
● minimum
-25 °C
● maximum
55 °C
ambient temperature during storage
● minimum
-25 °C
● maximum
55 °C
Approvals Certificates
General Product Approval
Confirmation
other
Miscellaneous
Environment
Confirmation
Environmental Confirmations
Environmental Confirmations
Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/lowvoltage/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3LD2405-1TL11
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3LD2405-1TL11
3LD24051TL11
Page 3/6
5/8/2024
Subject to change without notice
© Copyright Siemens
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3LD2405-1TL11
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications
3LD24051TL11
Page 4/6
5/8/2024
Subject to change without notice
© Copyright Siemens
3L2
5L3
4T2
6T3
N
1L1
2T1
N
-Q
-C
1L1
2T1
3L2
4T2
5L3
6T3
N
last modified:
3LD24051TL11
Page 5/6
N
6/20/2023
5/8/2024
Subject to change without notice
© Copyright Siemens
3LD24051TL11
Page 6/6
5/8/2024
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3LD2405-1TL11”相匹配的价格&库存,您可以联系我们找货