Data sheet
3RA2110-0CA15-1BB4
Load feeder fuseless, Direct-on-line starting 400 V AC, Size S00 0.18...0.25
A 24 V DC screw terminal for installation on standard mounting rail (also
fulfills type of coordination 1) Type of coordination 2, Iq = 150 kA 1 NO
(contactor)
product brand name
SIRIUS
product designation
Direct (on-line) starter
design of the product
for standard rail or screw mounting
product type designation
3RA21
manufacturer's article number
● of the supplied contactor
3RT2015-1BB41
● of the supplied circuit-breakers
3RV2011-0CA10
● of the supplied link module
3RA1921-1DA00
General technical data
size of the circuit-breaker
S00
size of load feeder
S00
insulation voltage with degree of pollution 3 at AC rated
value
690 V
surge voltage resistance rated value
6 kV
shock resistance acc. to IEC 60068-2-27
6g / 11 ms
mechanical service life (switching cycles) of contactor
typical
30 000 000
type of assignment
2
type of protection according to ATEX directive
2014/34/EU
Ex II (2) GD
certificate of suitability according to ATEX directive
2014/34/EU
DMT 02 ATEX F 001
Substance Prohibitance (Date)
01.10.2009 00:00:00
Ambient conditions
● ambient temperature during operation
-20 ... +60 °C
● ambient temperature during storage
-50 ... +80 °C
● ambient temperature during transport
-50 ... +80 °C
temperature compensation
-20 ... +60 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
design of the switching contact
electromechanical
adjustable current response value current of the
current-dependent overload release
0.18 ... 0.25 A
● operating voltage rated value
690 V
● operating voltage at AC-3 rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current at AC-3 at 400 V rated value
0.2 A
3RA21100CA151BB4
Page 1/2
1.21.2021
Subject to change without notice
© Copyright Siemens
operating power at AC-3
● at 400 V rated value
60 W
Control circuit/ Control
type of voltage of the control supply voltage
DC
control supply voltage at DC
● rated value
holding power of magnet coil at DC
24 V
4W
Auxiliary circuit
product extension auxiliary switch
Yes
Protective and monitoring functions
trip class
CLASS 10
design of the overload release
thermal (bimetallic)
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
0.25 A
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
conditional short-circuit current (Iq)
● at 400 V acc. to IEC 60947-4-1 rated value
150 000 A
Installation/ mounting/ dimensions
mounting position
vertical
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
height
167 mm
width
45 mm
depth
97 mm
required spacing
● for grounded parts
— forwards
20 mm
— backwards
0 mm
— upwards
50 mm
— at the side
20 mm
— downwards
10 mm
● for live parts
— forwards
20 mm
— backwards
0 mm
— upwards
50 mm
— downwards
10 mm
— at the side
20 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
type of connectable conductor cross-sections
● for main contacts
— stranded
0.5 ... 4 mm², 2x (0.75 ... 2.5 mm²)
● at AWG cables for main contacts
2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
● connectable conductor cross-section for main
contacts finely stranded with core end processing
0.5 ... 2.5 mm²
Safety related data
B10 value with high demand rate acc. to SN 31920
1 000 000
proportion of dangerous failures
● with high demand rate acc. to SN 31920
touch protection on the front acc. to IEC 60529
73 %
finger-safe, for vertical contact from the front
Certificates/ approvals
General Product Approval
3RA21100CA151BB4
Page 2/3
For use in
hazardous
locations
1.21.2021
Declaration of Conformity
Subject to change without notice
© Copyright Siemens
Miscellaneous
Test Certificates
Type Test
Certificates/Test
Report
Marine / Shipping
Marine / Shipping
Special Test
Certificate
other
Confirmation
Railway
Vibration and Shock
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RA2110-0CA15-1BB4
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RA2110-0CA15-1BB4
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RA2110-0CA15-1BB4
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RA2110-0CA15-1BB4&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RA2110-0CA15-1BB4/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RA2110-0CA15-1BB4&objecttype=14&gridview=view1
3RA21100CA151BB4
Page 3/4
1.21.2021
Subject to change without notice
© Copyright Siemens
3RA21100CA151BB4
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
3RA21100CA151BB4
Page 5/6
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RA21100CA151BB4
Page 6/6
12/15/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RA21100CA151BB4”相匹配的价格&库存,您可以联系我们找货
免费人工找货