Data sheet
3RA2110-1DA15-1AP6
Fuseless motor starter Direct start 600VAC Size S00 2.2-3.2A 220/240VAC
50/60HZ screw connection For screw mounting Or 35 mm rail-mounting
Type of coordination 2 IQ = 150 KA Also full fills type Of coordination 1
1NO (contactor)
product brand name
SIRIUS
product designation
non-fused motor starter 3RA2
design of the product
direct starter
manufacturer's article number
● of the supplied contactor
3RT2015-1AP61
● of the supplied circuit-breakers
3RV2011-1DA10
● of the supplied link module
3RA1921-1DA00
General technical data
size of the circuit-breaker
S00
size of load feeder
S00
product extension auxiliary switch
Yes
insulation voltage with degree of pollution 3 at AC rated
value
690 V
degree of pollution
3
surge voltage resistance rated value
6 kV
shock resistance according to IEC 60068-2-27
6g / 11 ms
mechanical service life (switching cycles) of contactor
typical
30 000 000
type of assignment
2
Ambient conditions
ambient temperature
● during operation
-20 ... +60 °C
● during storage
-50 ... +80 °C
● during transport
-55 ... +80 °C
Main circuit
number of poles for main current circuit
3
design of the switching contact
electromechanical
adjustable current response value current of the
current-dependent overload release
2.2 ... 3.2 A
operating voltage
● rated value
690 V
● at AC-3 rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current at AC-3 at 400 V rated value
2.7 A
operating power at AC-3
● at 400 V rated value
1 100 W
● at 500 V rated value
1 500 W
Control circuit/ Control
control supply voltage at AC
● at 50 Hz rated value
3RA21101DA151AP6
Page 1/4
220 V
7/8/2022
Subject to change without notice
© Copyright Siemens
● at 50 Hz rated value
187 ... 242 V
● at 60 Hz rated value
240 V
● at 60 Hz rated value
192 ... 264 V
apparent holding power of magnet coil at AC
4.8 VA
inductive power factor with the holding power of the
coil
0.25
Auxiliary circuit
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
1
Protective and monitoring functions
trip class
CLASS 10
design of the overload release
thermal (bimetallic)
response value current of instantaneous short-circuit trip
unit
41.6 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
2.8 A
● at 600 V rated value
3.16 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
0.1 hp
— at 230 V rated value
0.25 hp
● for 3-phase AC motor
— at 200/208 V rated value
0.5 hp
— at 220/230 V rated value
0.75 hp
— at 460/480 V rated value
1.5 hp
— at 575/600 V rated value
2 hp
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
conditional short-circuit current (Iq)
● at 400 V according to IEC 60947-4-1 rated value
153 000 A
● at 500 V according to IEC 60947-4-1 rated value
100 000 A
Installation/ mounting/ dimensions
mounting position
vertical
fastening method
Snap-mounted to DIN rail or screw-mounted with additional push-in lug
height
167.2 mm
width
45 mm
depth
97.1 mm
required spacing
● for grounded parts
— forwards
0 mm
— backwards
0 mm
— upwards
20 mm
— at the side
9 mm
— downwards
10 mm
● for live parts
— forwards
0 mm
— backwards
0 mm
— upwards
20 mm
— downwards
10 mm
— at the side
9 mm
Connections/ Terminals
type of electrical connection for main current circuit
screw-type terminals
type of connectable conductor cross-sections
● for main contacts stranded
0.5 ... 4 mm², 2x (0.75 ... 2.5 mm²)
● at AWG cables for main contacts
2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
connectable conductor cross-section for main contacts
finely stranded with core end processing
0.5 ... 2.5 mm²
Safety related data
3RA21101DA151AP6
Page 2/4
7/8/2022
Subject to change without notice
© Copyright Siemens
B10 value with high demand rate according to SN 31920
1 000 000
proportion of dangerous failures with high demand rate
according to SN 31920
73 %
protection class IP on the front according to IEC
60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
Certificates/ approvals
General Product Approval
For use in hazardous locations
Declaration of
Conformity
other
Railway
Confirmation
Declaration of
Conformity
Test Certificates
Special Test Certificate
Marine / Shipping
Type Test Certificates/Test Report
Marine / Shipping
Confirmation
Vibration and Shock
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RA2110-1DA15-1AP6
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RA2110-1DA15-1AP6
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RA2110-1DA15-1AP6
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RA2110-1DA15-1AP6&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RA2110-1DA15-1AP6/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RA2110-1DA15-1AP6&objecttype=14&gridview=view1
3RA21101DA151AP6
Page 3/4
7/8/2022
Subject to change without notice
© Copyright Siemens
13 NO
5/L3
3/L2
1/L1
A1
-Q
F
-Q1
I>
I>
I>
last modified:
3RA21101DA151AP6
Page 4/4
14 NO
6/T3
4/T2
2/T1
A2
-Q11
12/15/2020
7/8/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RA21101DA151AP6”相匹配的价格&库存,您可以联系我们找货