Data sheet
3RA2110-1DD15-1AP0
Load feeder fuseless, Direct-on-line starting 400 V AC, Size S00 2.20...3.20
A 230 V AC screw terminal for 60 mm busbar systems (also fulfills type of
coordination 1) Type of coordination 2, Iq = 150 kA 1 NO (contactor)
product brand name
SIRIUS
product designation
Direct (on-line) starter
design of the product
for 60 mm busbars
product type designation
3RA21
manufacturer's article number
● of the supplied contactor
3RT2015-1AP01
● of the supplied circuit-breakers
3RV2011-1DA10
● of the supplied busbar adapter
8US1251-5DS10
● of the supplied link module
3RA1921-1DA00
General technical data
size of the circuit-breaker
S00
size of load feeder
S00
insulation voltage with degree of pollution 3 at AC rated
value
690 V
surge voltage resistance rated value
6 kV
shock resistance acc. to IEC 60068-2-27
6g / 11 ms
mechanical service life (switching cycles) of contactor
typical
30 000 000
type of assignment
2
type of protection according to ATEX directive
2014/34/EU
Ex II (2) GD
certificate of suitability according to ATEX directive
2014/34/EU
DMT 02 ATEX F 001
Substance Prohibitance (Date)
01.10.2009 00:00:00
Ambient conditions
● ambient temperature during operation
-20 ... +60 °C
● ambient temperature during storage
-50 ... +80 °C
● ambient temperature during transport
-50 ... +80 °C
temperature compensation
-20 ... +60 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
design of the switching contact
electromechanical
adjustable current response value current of the
current-dependent overload release
2.2 ... 3.2 A
● operating voltage rated value
690 V
● operating voltage at AC-3 rated value maximum
690 V
operating frequency rated value
3RA21101DD151AP0
Page 1/2
50 ... 60 Hz
1.21.2021
Subject to change without notice
© Copyright Siemens
operational current at AC-3 at 400 V rated value
2.7 A
operating power at AC-3
● at 400 V rated value
1 100 W
Control circuit/ Control
type of voltage of the control supply voltage
AC
control supply voltage at AC
● at 50 Hz rated value
230 V
● at 60 Hz rated value
230 V
apparent holding power of magnet coil at AC
4.2 V·A
Auxiliary circuit
product extension auxiliary switch
Yes
Protective and monitoring functions
trip class
CLASS 10
design of the overload release
thermal (bimetallic)
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
3.2 A
yielded mechanical performance [hp]
● for 3-phase AC motor
— at 200/208 V rated value
0.5 hp
— at 220/230 V rated value
0.75 hp
— at 460/480 V rated value
1.5 hp
— at 575/600 V rated value
2 hp
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
conditional short-circuit current (Iq)
● at 400 V acc. to IEC 60947-4-1 rated value
150 000 A
Installation/ mounting/ dimensions
mounting position
vertical
fastening method
for snapping onto 60 mm busbar systems
height
200 mm
width
45 mm
depth
155 mm
required spacing
● for grounded parts
— forwards
20 mm
— backwards
0 mm
— upwards
50 mm
— at the side
20 mm
— downwards
10 mm
● for live parts
— forwards
20 mm
— backwards
0 mm
— upwards
50 mm
— downwards
10 mm
— at the side
20 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
Safety related data
B10 value with high demand rate acc. to SN 31920
1 000 000
proportion of dangerous failures
● with high demand rate acc. to SN 31920
touch protection on the front acc. to IEC 60529
73 %
finger-safe, for vertical contact from the front
Certificates/ approvals
General Product Approval
3RA21101DD151AP0
Page 2/3
For use in
1.21.2021
Declaration of Conformity
Subject to change without notice
© Copyright Siemens
hazardous
locations
Miscellaneous
Test Certificates
Special Test
Certificate
Marine / Shipping
Marine / Shipping
Type Test
Certificates/Test
Report
other
Confirmation
Railway
Vibration and Shock
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RA2110-1DD15-1AP0
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RA2110-1DD15-1AP0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RA2110-1DD15-1AP0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RA2110-1DD15-1AP0&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RA2110-1DD15-1AP0/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RA2110-1DD15-1AP0&objecttype=14&gridview=view1
3RA21101DD151AP0
Page 3/4
1.21.2021
Subject to change without notice
© Copyright Siemens
3RA21101DD151AP0
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
3RA21101DD151AP0
Page 5/6
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RA21101DD151AP0
Page 6/6
12/15/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RA21101DD151AP0”相匹配的价格&库存,您可以联系我们找货