Data sheet
3RA2120-4DA27-0AK6
FUSELESS LOAD FEEDER DIRECT START, AC 400V, SZ. S0, 18...25A,
AC 110/120V 50/60HZ SCREW TERMINAL FOR DIN RAIL MOUNTING,
TYPE OF ASSIGNMENT 2,IQ = 150KA (ALSO TYPE OF ASSIGNMENT 1)
1NO+1NC (CONTACTOR)
product brand name
SIRIUS
product designation
non-fused load feeders 3RA2
design of the product
direct starter
manufacturer's article number
● of the supplied contactor
3RT2027-1AK60
● of the supplied circuit-breakers
3RV2021-4DA10
● of the supplied link module
3RA2921-1AA00
General technical data
size of the circuit-breaker
S0
size of load feeder
S0
product extension auxiliary switch
Yes
insulation voltage with degree of pollution 3 at AC rated
value
690 V
degree of pollution
3
surge voltage resistance rated value
6 kV
shock resistance acc. to IEC 60068-2-27
6g / 11 ms
mechanical service life (switching cycles) of contactor
typical
10 000 000
type of assignment
2
Substance Prohibitance (Date)
01.05.2012 00:00:00
Ambient conditions
● ambient temperature during operation
-20 ... +60 °C
● ambient temperature during storage
-50 ... +80 °C
● ambient temperature during transport
-50 ... +80 °C
Main circuit
number of poles for main current circuit
3
design of the switching contact
electromechanical
adjustable current response value current of the
current-dependent overload release
20 ... 25 A
● operating voltage rated value
690 V
● operating voltage at AC-3 rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current at AC-3 at 400 V rated value
22 A
operating power at AC-3
● at 400 V rated value
11 000 W
● at 500 V rated value
15 000 W
● at 690 V rated value
22 000 W
Control circuit/ Control
3RA21204DA270AK6
Page 1/2
1.21.2021
Subject to change without notice
© Copyright Siemens
control supply voltage at AC
● at 50 Hz rated value
110 V
● at 60 Hz rated value
120 V
apparent holding power of magnet coil at AC
9.8 V·A
Protective and monitoring functions
trip class
CLASS 10
design of the overload release
thermal (bimetallic)
response value current of instantaneous short-circuit trip
unit
325 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
22.2 A
● at 600 V rated value
21.9 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
2 hp
— at 230 V rated value
3 hp
● for 3-phase AC motor
— at 200/208 V rated value
5 hp
— at 220/230 V rated value
7.5 hp
— at 460/480 V rated value
15 hp
— at 575/600 V rated value
20 hp
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
conditional short-circuit current (Iq)
● at 690 V acc. to IEC 60947-4-1 rated value
2 000 A
● at 400 V acc. to IEC 60947-4-1 rated value
153 000 A
● at 500 V acc. to IEC 60947-4-1 rated value
5 000 A
Installation/ mounting/ dimensions
mounting position
vertical
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
height
193.1 mm
width
45 mm
depth
97.1 mm
required spacing
● for grounded parts
— forwards
10 mm
— backwards
0 mm
— upwards
30 mm
— at the side
9 mm
— downwards
10 mm
● for live parts
— forwards
10 mm
— backwards
0 mm
— upwards
30 mm
— downwards
10 mm
— at the side
9 mm
Connections/ Terminals
type of electrical connection for main current circuit
screw-type terminals
type of connectable conductor cross-sections
● for main contacts stranded
1 ... 10 mm², 2x (2.5 ... 6 mm²)
● at AWG cables for main contacts
2x (16 ... 12), 2x (14 ... 8)
● connectable conductor cross-section for main
contacts finely stranded with core end processing
1 ... 6 mm²
Safety related data
B10 value with high demand rate acc. to SN 31920
1 000 000
proportion of dangerous failures with high demand rate
73 %
3RA21204DA270AK6
Page 2/3
1.21.2021
Subject to change without notice
© Copyright Siemens
acc. to SN 31920
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe, for vertical contact from the front
Certificates/ approvals
For use in
hazardous
locations
General Product Approval
Declaration of Conformity
Miscellaneous
Test Certificates
Special Test
Certificate
Marine / Shipping
Marine / Shipping
Type Test
Certificates/Test
Report
other
Confirmation
Railway
Vibration and Shock
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RA2120-4DA27-0AK6
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RA2120-4DA27-0AK6
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RA2120-4DA27-0AK6
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RA2120-4DA27-0AK6&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RA2120-4DA27-0AK6/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RA2120-4DA27-0AK6&objecttype=14&gridview=view1
3RA21204DA270AK6
Page 3/4
1.21.2021
Subject to change without notice
© Copyright Siemens
3RA21204DA270AK6
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
3RA21204DA270AK6
Page 5/6
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RA21204DA270AK6
Page 6/6
12/15/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RA21204DA270AK6”相匹配的价格&库存,您可以联系我们找货