Data sheet
3RA2120-4EA27-0AP6
Fuseless motor starter Direct start 600VAC Size S0 27-32A 220/240VAC
50/60HZ screw connection For screw mounting Or 35 mm rail-mounting
Type of coordination 2 IQ = 150 KA Also full fills type Of coordination 1
1NO+1NC (contactor)
product brand name
SIRIUS
product designation
non-fused motor starter 3RA2
design of the product
direct starter
manufacturer's article number
● of the supplied contactor
3RT2027-1AP60
● of the supplied circuit-breakers
3RV2021-4EA10
● of the supplied link module
3RA2921-1AA00
General technical data
size of the circuit-breaker
S0
size of load feeder
S0
product extension auxiliary switch
Yes
insulation voltage with degree of pollution 3 at AC rated
value
690 V
degree of pollution
3
surge voltage resistance rated value
6 kV
shock resistance acc. to IEC 60068-2-27
6g / 11 ms
mechanical service life (switching cycles) of contactor
typical
10 000 000
type of assignment
2
Ambient conditions
● ambient temperature during operation
-20 ... +60 °C
● ambient temperature during storage
-50 ... +80 °C
● ambient temperature during transport
-55 ... +80 °C
Main circuit
number of poles for main current circuit
3
design of the switching contact
electromechanical
adjustable current response value current of the
current-dependent overload release
27 ... 32 A
● operating voltage rated value
690 V
● operating voltage at AC-3 rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current at AC-3 at 400 V rated value
29 A
operating power at AC-3
● at 400 V rated value
15 000 W
● at 500 V rated value
18 500 W
Control circuit/ Control
control supply voltage at AC
● at 50 Hz rated value
3RA21204EA270AP6
Page 1/2
220 V
1.21.2021
Subject to change without notice
© Copyright Siemens
● at 50 Hz rated value
176 ... 242 V
● at 60 Hz rated value
240 V
● at 60 Hz rated value
192 ... 264 V
apparent holding power of magnet coil at AC
9.4 V·A
inductive power factor with the holding power of the
coil
0.28
Auxiliary circuit
number of NC contacts for auxiliary contacts
1
number of NO contacts for auxiliary contacts
1
Protective and monitoring functions
trip class
CLASS 10
design of the overload release
thermal (bimetallic)
response value current of instantaneous short-circuit trip
unit
416 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
27 A
● at 600 V rated value
27 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 230 V rated value
5 hp
● for 3-phase AC motor
— at 200/208 V rated value
10 hp
— at 220/230 V rated value
10 hp
— at 460/480 V rated value
20 hp
— at 575/600 V rated value
25 hp
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
conditional short-circuit current (Iq)
● at 400 V acc. to IEC 60947-4-1 rated value
153 000 A
● at 500 V acc. to IEC 60947-4-1 rated value
100 000 A
Installation/ mounting/ dimensions
mounting position
vertical
fastening method
Snap-mounted to DIN rail or screw-mounted with additional push-in lug
height
193.1 mm
width
45 mm
depth
97.1 mm
required spacing
● for grounded parts
— forwards
10 mm
— backwards
0 mm
— upwards
30 mm
— at the side
9 mm
— downwards
10 mm
● for live parts
— forwards
10 mm
— backwards
0 mm
— upwards
30 mm
— downwards
10 mm
— at the side
9 mm
Connections/ Terminals
type of electrical connection for main current circuit
screw-type terminals
type of connectable conductor cross-sections
● for main contacts stranded
1 ... 10 mm², 2x (2.5 ... 6 mm²)
● at AWG cables for main contacts
2x (16 ... 12), 2x (14 ... 8)
● connectable conductor cross-section for main
contacts finely stranded with core end processing
1 ... 6 mm²
3RA21204EA270AP6
Page 2/3
1.21.2021
Subject to change without notice
© Copyright Siemens
Safety related data
B10 value with high demand rate acc. to SN 31920
1 000 000
proportion of dangerous failures with high demand rate
acc. to SN 31920
73 %
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe, for vertical contact from the front
Certificates/ approvals
For use in
hazardous
locations
General Product Approval
Declaration of Conformity
Miscellaneous
Test Certificates
Special Test
Certificate
Marine / Shipping
Marine / Shipping
Type Test
Certificates/Test
Report
other
Confirmation
Railway
Vibration and Shock
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RA2120-4EA27-0AP6
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RA2120-4EA27-0AP6
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RA2120-4EA27-0AP6
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RA2120-4EA27-0AP6&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RA2120-4EA27-0AP6/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RA2120-4EA27-0AP6&objecttype=14&gridview=view1
3RA21204EA270AP6
Page 3/4
1.21.2021
Subject to change without notice
© Copyright Siemens
3RA21204EA270AP6
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
3RA21204EA270AP6
Page 5/6
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RA21204EA270AP6
Page 6/6
12/15/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RA21204EA270AP6”相匹配的价格&库存,您可以联系我们找货