Data sheet
3RA2210-0BD15-2AK6
FUSELESS LOAD FEEDER REVERSING OPERATION, 400 V AC, S00
0.14 TO 0.20A,110/120 V AC 50/60HZ SCREW TERMINAL FOR 60 MM
BUSBAR SYSTEMS TYPE OF COORDINATION 2, IQ = 150 KA (ALSO
FULFILLS TYPE OF COORDINATION 1)1NC (CONTACTOR)
product brand name
SIRIUS
product designation
non-fused load feeders 3RA2
design of the product
reversing starter
manufacturer's article number
● of the supplied contactor
3RT2015-1AK62
● of the supplied circuit-breakers
3RV2011-0BA10
● of the supplied RS assembly kit
8US1250-5AS10
● of the supplied busbar adapter
8US1251-5DS10
● of the supplied link module
3RA1921-1DA00
General technical data
size of the circuit-breaker
S00
size of load feeder
S00
product extension auxiliary switch
Yes
insulation voltage with degree of pollution 3 at AC rated
value
690 V
degree of pollution
3
surge voltage resistance rated value
6 kV
shock resistance acc. to IEC 60068-2-27
6g / 11 ms
mechanical service life (switching cycles) of contactor
typical
30 000 000
type of assignment
2
Substance Prohibitance (Date)
01.10.2009 00:00:00
Ambient conditions
● ambient temperature during operation
-20 ... +60 °C
● ambient temperature during storage
-50 ... +80 °C
● ambient temperature during transport
-50 ... +80 °C
Main circuit
number of poles for main current circuit
3
design of the switching contact
electromechanical
adjustable current response value current of the
current-dependent overload release
0.14 ... 0.2 A
● operating voltage rated value
690 V
● operating voltage at AC-3 rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current at AC-3 at 400 V rated value
0.2 A
operating power at AC-3
● at 400 V rated value
60 W
● at 500 V rated value
60 W
3RA22100BD152AK6
Page 1/2
1.21.2021
Subject to change without notice
© Copyright Siemens
● at 690 V rated value
90 W
Control circuit/ Control
control supply voltage at AC
● at 50 Hz rated value
110 V
● at 60 Hz rated value
120 V
apparent holding power of magnet coil at AC
4.2 V·A
Protective and monitoring functions
trip class
CLASS 10
design of the overload release
thermal (bimetallic)
response value current of instantaneous short-circuit trip
unit
2.6 A
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
conditional short-circuit current (Iq)
● at 690 V acc. to IEC 60947-4-1 rated value
100 000 A
● at 400 V acc. to IEC 60947-4-1 rated value
153 000 A
● at 500 V acc. to IEC 60947-4-1 rated value
100 000 A
Installation/ mounting/ dimensions
mounting position
vertical
fastening method
for snapping onto 60 mm busbar systems
height
200 mm
width
90 mm
depth
155.1 mm
required spacing
● for grounded parts
— forwards
0 mm
— backwards
0 mm
— upwards
20 mm
— at the side
9 mm
— downwards
10 mm
● for live parts
— forwards
0 mm
— backwards
0 mm
— upwards
20 mm
— downwards
10 mm
— at the side
9 mm
Connections/ Terminals
type of electrical connection for main current circuit
screw-type terminals
type of connectable conductor cross-sections
● for main contacts stranded
0.5 ... 4 mm², 2x (0.75 ... 2.5 mm²)
● at AWG cables for main contacts
2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12
● connectable conductor cross-section for main
contacts finely stranded with core end processing
0.5 ... 2.5 mm²
Safety related data
B10 value with high demand rate acc. to SN 31920
1 000 000
proportion of dangerous failures with high demand rate
acc. to SN 31920
73 %
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe, for vertical contact from the front
Certificates/ approvals
General Product Approval
3RA22100BD152AK6
Page 2/3
For use in
hazardous
locations
1.21.2021
Declaration of Conformity
Subject to change without notice
© Copyright Siemens
Miscellaneous
Test Certificates
Special Test
Certificate
Marine / Shipping
Marine / Shipping
Type Test
Certificates/Test
Report
other
Confirmation
Railway
Vibration and Shock
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RA2210-0BD15-2AK6
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RA2210-0BD15-2AK6
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RA2210-0BD15-2AK6
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RA2210-0BD15-2AK6&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RA2210-0BD15-2AK6/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RA2210-0BD15-2AK6&objecttype=14&gridview=view1
3RA22100BD152AK6
Page 3/4
1.21.2021
Subject to change without notice
© Copyright Siemens
3RA22100BD152AK6
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
3RA22100BD152AK6
Page 5/6
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RA22100BD152AK6
Page 6/6
12/15/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RA22100BD152AK6”相匹配的价格&库存,您可以联系我们找货