Data sheet
3RA2316-8XB30-1AK6
Reversing contactor assembly AC-3, 4 kW/400 V 110 V AC 50 Hz/120 V 60
Hz, 3-pole Size S00, screw terminal electrical and mechanical interlock
product brand name
SIRIUS
product designation
Reversing contactor assembly
product type designation
3RA23
manufacturer's article number
● 1 of the supplied contactor
3RT2016-1AK62
● 2 of the supplied contactor
3RT2016-1AK62
● of the supplied RH assembly kit
3RA2913-2AA1
General technical data
size of contactor
S00
product extension auxiliary switch
Yes
shock resistance at rectangular impulse
● at AC
6,7g / 5 ms, 4,2g / 10 ms
● at DC
6,7g / 5 ms, 4,2g / 10 ms
shock resistance with sine pulse
● at AC
10,5g / 5 ms, 6,6g / 10 ms
● at DC
10,5g / 5 ms, 6,6g / 10 ms
mechanical service life (switching cycles)
● of contactor typical
10 000 000
● of the contactor with added auxiliary switch block
typical
10 000 000
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
10/01/2009
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-25 ... +60 °C
● during storage
-55 ... +80 °C
Main circuit
number of poles for main current circuit
3
number of NO contacts for main contacts
3
number of NC contacts for main contacts
0
operating voltage at AC-3 rated value maximum
690 V
operational current at AC-3
● at 400 V rated value
9A
● at 500 V rated value
7.7 A
● at 690 V rated value
6.7 A
operating power
● at AC-3
— at 400 V rated value
3RA23168XB301AK6
Page 1/4
4 kW
7/6/2022
Subject to change without notice
© Copyright Siemens
— at 500 V rated value
4 kW
— at 690 V rated value
5.5 kW
● at AC-4 at 400 V rated value
operating frequency at AC-3 maximum
4 kW
750 1/h
Control circuit/ Control
type of voltage of the control supply voltage
AC
control supply voltage 1 at AC
● at 50 Hz rated value
110 V
● at 60 Hz rated value
120 V
operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
0.8 ... 1.1
● at 60 Hz
0.85 ... 1.1
apparent pick-up power of magnet coil at AC
● at 50 Hz
27 VA
inductive power factor with closing power of the coil
● at 50 Hz
0.8
apparent holding power of magnet coil at AC
● at 50 Hz
4.2 VA
inductive power factor with the holding power of the
coil
● at 50 Hz
0.25
Auxiliary circuit
contact reliability of auxiliary contacts
< 1 error per 100 million operating cycles
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
7.6 A
● at 600 V rated value
9A
yielded mechanical performance [hp] for 3-phase AC
motor
● at 200/208 V rated value
2 hp
● at 220/230 V rated value
3 hp
● at 460/480 V rated value
5 hp
● at 575/600 V rated value
7.5 hp
contact rating of auxiliary contacts according to UL
A600 / Q600
Short-circuit protection
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 35 A
— with type of assignment 2 required
gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 20 A
● for short-circuit protection of the auxiliary switch
required
fuse gG: 10 A
Installation/ mounting/ dimensions
mounting position
+/-180° rotation possible on vertical mounting surface; can be tilted
forward and backward by +/- 22.5° on vertical mounting surface
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
height
68 mm
width
90 mm
depth
73 mm
required spacing
● with side-by-side mounting
— forwards
6 mm
— backwards
0 mm
— upwards
6 mm
— downwards
6 mm
— at the side
6 mm
● for grounded parts
— forwards
6 mm
— backwards
0 mm
— upwards
6 mm
— at the side
6 mm
3RA23168XB301AK6
Page 2/4
7/6/2022
Subject to change without notice
© Copyright Siemens
— downwards
6 mm
● for live parts
— forwards
6 mm
— backwards
0 mm
— upwards
6 mm
— downwards
6 mm
— at the side
6 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
screw-type terminals
● at contactor for auxiliary contacts
Screw-type terminals
● of magnet coil
Screw-type terminals
type of connectable conductor cross-sections
● for main contacts
— solid
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
— solid or stranded
2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x (0,5 ... 4 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for main contacts
2x (20 ... 16), 2x (18 ... 14)
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14)
Safety related data
B10 value with high demand rate according to SN 31920
1 000 000
proportion of dangerous failures
● with low demand rate according to SN 31920
40 %
● with high demand rate according to SN 31920
75 %
failure rate [FIT] with low demand rate according to SN
31920
100 FIT
T1 value for proof test interval or service life according to
IEC 61508
20 y
protection class IP on the front according to IEC
60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
Communication/ Protocol
product function bus communication
Yes
protocol is supported AS-Interface protocol
No
product function control circuit interface with IO link
No
Certificates/ approvals
General Product Approval
Declaration of Conformity
Confirmation
Test Certificates
Special Test Certificate
Marine / Shipping
3RA23168XB301AK6
Page 3/4
Marine / Shipping
Type Test Certificates/Test Report
other
7/6/2022
Railway
Subject to change without notice
© Copyright Siemens
Confirmation
Vibration and Shock
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RA2316-8XB30-1AK6
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RA2316-8XB30-1AK6
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RA2316-8XB30-1AK6
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RA2316-8XB30-1AK6&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RA2316-8XB30-1AK6/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RA2316-8XB30-1AK6&objecttype=14&gridview=view1
last modified:
3RA23168XB301AK6
Page 4/4
2/8/2022
7/6/2022
Subject to change without notice
© Copyright Siemens