Data sheet
3RA2336-8XB30-1KB4
Reversing contactor assembly, AC-3, 22 kW 400 V, 0.7...1.25 US DC, 24 V
DC 3-pole, Size S2 screw terminal electrical and mechanical interlock 2 NO
integrated Varistor mounted
product brand name
SIRIUS
product designation
Reversing contactor assembly
product type designation
3RA23
manufacturer's article number
● 1 of the supplied contactor
3RT2036-1AL20
● 2 of the supplied contactor
3RT2036-1AL20
● of the supplied RS assembly kit
3RA2933-2AA1
General technical data
size of contactor
S2
product extension auxiliary switch
Yes
shock resistance at rectangular impulse
● at AC
11.8g / 5 ms, 11.6g / 10 ms
shock resistance with sine pulse
● at AC
18.5g / 5 ms, 11.6g / 10 ms
mechanical service life (switching cycles)
● of contactor typical
10 000 000
● of the contactor with added auxiliary switch block
typical
10 000 000
reference code acc. to IEC 81346-2
Q
Substance Prohibitance (Date)
01.10.2014 00:00:00
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
● ambient temperature during operation
-25 ... +60 °C
● ambient temperature during storage
-55 ... +80 °C
Main circuit
number of poles for main current circuit
3
number of NO contacts for main contacts
3
number of NC contacts for main contacts
0
● operating voltage at AC-3 rated value maximum
690 V
operational current at AC-3
● at 400 V rated value
50 A
operating power
● at AC-3
— at 400 V rated value
22 kW
— at 690 V rated value
22 kW
● at AC-4 at 400 V rated value
22 kW
operating frequency at AC-3 maximum
800 1/h
3RA23368XB301KB4
Page 1/2
1.21.2021
Subject to change without notice
© Copyright Siemens
Control circuit/ Control
type of voltage of the control supply voltage
DC
control supply voltage 1
● at DC rated value
design of the surge suppressor
24 V
with varistor
apparent pick-up power of magnet coil at AC
● at 50 Hz
210 V·A
● at 60 Hz
188 V·A
inductive power factor with closing power of the coil
● at 50 Hz
0.69
● at 60 Hz
0.65
apparent holding power of magnet coil at AC
● at 50 Hz
17.2 V·A
● at 60 Hz
16.5 V·A
inductive power factor with the holding power of the
coil
● at 50 Hz
0.36
● at 60 Hz
0.39
Auxiliary circuit
number of NC contacts for auxiliary contacts
● per direction of rotation
0
number of NO contacts for auxiliary contacts
● per direction of rotation
1
● instantaneous contact
2
contact reliability of auxiliary contacts
< 1 error per 100 million operating cycles
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
52 A
● at 600 V rated value
52 A
yielded mechanical performance [hp] for 3-phase AC
motor
● at 220/230 V rated value
15 hp
● at 460/480 V rated value
40 hp
● at 575/600 V rated value
50 hp
contact rating of auxiliary contacts according to UL
A600 / Q600
Short-circuit protection
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 160 A
— with type of assignment 2 required
gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 80 A
● for short-circuit protection of the auxiliary switch
required
fuse gG: 10 A
Installation/ mounting/ dimensions
mounting position
+/-180° rotation possible on vertical mounting surface; can be tilted
forward and backward by +/- 22.5° on vertical mounting surface
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
height
141 mm
width
120 mm
depth
130 mm
required spacing
● with side-by-side mounting
— forwards
10 mm
— backwards
0 mm
— upwards
10 mm
— downwards
10 mm
— at the side
10 mm
● for grounded parts
— forwards
10 mm
— backwards
0 mm
3RA23368XB301KB4
Page 2/3
1.21.2021
Subject to change without notice
© Copyright Siemens
— upwards
10 mm
— at the side
10 mm
— downwards
10 mm
● for live parts
— forwards
10 mm
— backwards
0 mm
— upwards
10 mm
— downwards
10 mm
— at the side
10 mm
Connections/ Terminals
type of electrical connection for main current circuit
screw-type terminals
type of connectable conductor cross-sections
● for main contacts
— solid
2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
— solid or stranded
2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
— finely stranded with core end processing
2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
● at AWG cables for main contacts
2x (18 ... 2), 1x (18 ... 1)
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded
2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14)
Safety related data
B10 value with high demand rate acc. to SN 31920
1 000 000
proportion of dangerous failures
● with low demand rate acc. to SN 31920
40 %
● with high demand rate acc. to SN 31920
73 %
failure rate [FIT] with low demand rate acc. to SN 31920
100 FIT
T1 value for proof test interval or service life acc. to
IEC 61508
20 y
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe, for vertical contact from the front
Communication/ Protocol
product function bus communication
Yes
protocol is supported AS-Interface protocol
No
product function control circuit interface with IO link
No
Certificates/ approvals
General Product Approval
Declaration of Conformity
Marine / Shipping
Miscellaneous
Marine / Shipping
other
Confirmation
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RA2336-8XB30-1KB4
Cax online generator
3RA23368XB301KB4
Page 3/4
1.21.2021
Subject to change without notice
© Copyright Siemens
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RA2336-8XB30-1KB4
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RA2336-8XB30-1KB4
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RA2336-8XB30-1KB4&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RA2336-8XB30-1KB4/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RA2336-8XB30-1KB4&objecttype=14&gridview=view1
3RA23368XB301KB4
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RA23368XB301KB4
Page 5/5
12/15/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RA23368XB301KB4”相匹配的价格&库存,您可以联系我们找货