Data sheet
3RA6120-1BB34
SIRIUS Compact load feeder DOL starter 690 V 24 V AC/DC 50...60 Hz
0.32...1.25 A IP20 Connection main circuit: screw terminal Connection
auxiliary circuit: plug-in, without terminals
product brand name
SIRIUS
product designation
compact starter
design of the product
direct starter
product type designation
3RA61
General technical data
product function control circuit interface to parallel wiring
Yes
product extension auxiliary switch
Yes
power loss [W] for rated value of the current at AC in hot
operating state
0.1 W
● per pole
0.03 W
power loss [W] for rated value of the current without
load current share typical
2.9 W
insulation voltage rated value
690 V
degree of pollution
3
surge voltage resistance rated value
6 000 V
maximum permissible voltage for safe isolation
● between main and auxiliary circuit
400 V
● between auxiliary and auxiliary circuit
250 V
● between control and auxiliary circuit
300 V
degree of protection NEMA rating
other
shock resistance
a=60 m/s2 (6g) with 10 ms per 3 shocks in all axes
vibration resistance
f= 4 ... 5.8 Hz, d= 15 mm; f= 5.8 ... 500 Hz, a= 20 m/s²; 10 cycles
mechanical service life (switching cycles)
● of the main contacts typical
10 000 000
● of auxiliary contacts typical
10 000 000
● of the signaling contacts typical
10 000 000
electrical endurance (switching cycles) of auxiliary
contacts
● at DC-13 at 6 A at 24 V typical
30 000
● at AC-15 at 6 A at 230 V typical
200 000
type of assignment
continous operation according to IEC 60947-6-2
reference code acc. to IEC 81346-2
Q
Substance Prohibitance (Date)
01.05.2012 00:00:00
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
● ambient temperature during operation
-20 ... +60 °C
● ambient temperature during storage
-55 ... +80 °C
● ambient temperature during transport
-55 ... +80 °C
3RA61201BB34
Page 1/2
1.21.2021
Subject to change without notice
© Copyright Siemens
relative humidity during operation
10 ... 90 %
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the
current-dependent overload release
0.32 ... 1.25 A
formula for making capacity limit current
38.4 x Ie
formula for breaking capacity limit current
32 x Ie
yielded mechanical performance for 4-pole AC motor
● at 400 V rated value
0.37 kW
● at 500 V rated value
0.55 kW
● at 690 V rated value
0.75 kW
● operating voltage at AC-3 rated value maximum
690 V
operational current
● at AC at 400 V rated value
1.25 A
● at AC-43
— at 400 V rated value
1.1 A
— at 500 V rated value
1.2 A
— at 690 V rated value
1.1 A
operating power
● at AC-3 at 400 V rated value
370 W
● at AC-43
— at 400 V rated value
370 W
— at 500 V rated value
550 W
— at 690 V rated value
750 W
no-load switching frequency
3 600 1/h
operating frequency
● at AC-41 acc. to IEC 60947-6-2 maximum
750 1/h
● at AC-43 acc. to IEC 60947-6-2 maximum
250 1/h
Control circuit/ Control
type of voltage
AC/DC
control supply voltage 1 at AC
● at 50 Hz rated value
24 V
● at 60 Hz rated value
24 V
control supply voltage frequency
● 1 rated value
50 Hz
● 2 rated value
60 Hz
control supply voltage 1
● at DC rated value
24 V
holding power
● at AC maximum
2.8 W
● at DC maximum
2.9 W
Auxiliary circuit
number of NC contacts for auxiliary contacts
1
number of NO contacts for auxiliary contacts
1
number of NO contacts of instantaneous short-circuit trip
unit for signaling contact
1
number of CO contacts of the current-dependent overload
release for signaling contact
1
operational current of auxiliary contacts at AC-12
maximum
10 A
operational current of auxiliary contacts at DC-13 at 250 V
0.27 A
Protective and monitoring functions
trip class
CLASS 10 and 20 adjustable
breaking capacity operating short-circuit current (Ics)
● at 400 V
53 kA
● at 500 V rated value
3 kA
● at 690 V rated value
3 kA
UL/CSA ratings
3RA61201BB34
Page 2/3
1.21.2021
Subject to change without notice
© Copyright Siemens
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
1.25 A
● at 600 V rated value
1.25 A
yielded mechanical performance [hp] for 3-phase AC
motor
● at 460/480 V rated value
0.5 hp
● at 575/600 V rated value
0.5 hp
contact rating of auxiliary contacts according to UL
contacts 21-22, 13-14, 43-44 Q600 / A600, contacts 77-78 R300 / B300,
contacts 95-96-98 R300 / D300
Short-circuit protection
product function short circuit protection
Yes
design of short-circuit protection
electromagnetic
design of the fuse link
● for short-circuit protection of the auxiliary switch
required
fuse gL/gG: 10 A
● for short-circuit protection of the signaling switch of
the short-circuit release required
6A gL/gG/400V
● for short-circuit protection of the signaling switch of
the overload release required
4A gL/gG/400V
Installation/ mounting/ dimensions
mounting position
● recommended
any
vertical, on horizontal standard mounting rail
fastening method
screw and snap-on mounting
height
170 mm
width
45 mm
depth
165 mm
Connections/ Terminals
product function
● removable terminal for main circuit
Yes
● removable terminal for auxiliary and control circuit
Yes
type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
plug-in without terminals
type of connectable conductor cross-sections
● for main contacts
— solid
2x (1.5 ... 6 mm²), 1x 10 mm²
— finely stranded with core end processing
2x (1.5 ... 6 mm²)
● at AWG cables for main contacts
2x (16 ... 10), 1x 8
type of connectable conductor cross-sections
● for auxiliary contacts
— solid
0.5 ... 4 mm², 2x (0.5 ... 2.5 mm²)
— finely stranded with core end processing
0.5 ... 2.5 mm², 2x (0.5 ... 1.5 mm²)
● at AWG cables for auxiliary contacts
2x (20 ... 14)
Safety related data
B10 value with high demand rate acc. to SN 31920
3 000 000
proportion of dangerous failures
● with low demand rate acc. to SN 31920
40 %
● with high demand rate acc. to SN 31920
50 %
failure rate [FIT] with low demand rate acc. to SN 31920
100 FIT
T1 value for proof test interval or service life acc. to
IEC 61508
20 y
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe
Communication/ Protocol
product function bus communication
No
protocol is supported
● AS-Interface protocol
No
● IO-Link protocol
No
product function control circuit interface with IO link
3RA61201BB34
Page 3/4
No
1.21.2021
Subject to change without notice
© Copyright Siemens
Electromagnetic compatibility
conducted interference
● due to burst acc. to IEC 61000-4-4
4 kV main contacts, 2 kV auxiliary contacts
● due to conductor-earth surge acc. to IEC 61000-4-5
4 kV main contacts, 2 kV auxiliary contacts
● due to conductor-conductor surge acc. to IEC
61000-4-5
2 kV main contacts, 1 kV auxiliary contacts
● due to high-frequency radiation acc. to IEC 610004-6
0.15-80Mhz at 10V
field-based interference acc. to IEC 61000-4-3
10 V/m
electrostatic discharge acc. to IEC 61000-4-2
8 kV
conducted HF interference emissions acc. to CISPR11
150 kHz ... 30 MHz Class A
field-bound HF interference emission acc. to CISPR11
30 ... 1000 MHz Class A
Supply voltage
Supply voltage required Auxiliary voltage
No
Display
number of LEDs
2
Certificates/ approvals
General Product Approval
Declaration of Conformity
Miscellaneous
Functional
Safety/Safety of
Machinery
EMC
Test Certificates
Marine / Shipping
Type Test
Certificates/Test
Report
Marine / Shipping
other
Confirmation
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RA6120-1BB34
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RA6120-1BB34
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RA6120-1BB34
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RA6120-1BB34&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RA6120-1BB34/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RA6120-1BB34&objecttype=14&gridview=view1
3RA61201BB34
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
3RA61201BB34
Page 5/6
1.21.2021
Subject to change without notice
© Copyright Siemens
3RA61201BB34
Page 6/7
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
1/20/2021
3RA61201BB34
Page 7/7
1.21.2021
Subject to change without notice
© Copyright Siemens