Data sheet
3RB2153-4FC2
Overload relay 50...200 A for motor protection Size S6, CLASS 5...30E
Contactor mounting/stand-alone installation Main circuit: busbar connection
Auxiliary circuit: Screw terminal Manual-Automatic-Reset Internal ground
fault detection
product brand name
SIRIUS
product designation
solid-state overload relay
product type designation
3RB2
General technical data
size of overload relay
S6
size of contactor can be combined company-specific
S6
insulation voltage with degree of pollution 3 at AC rated
value
1 000 V
surge voltage resistance rated value
8 kV
maximum permissible voltage for safe isolation in
networks with grounded star point
● between auxiliary and auxiliary circuit
300 V
● between auxiliary and auxiliary circuit
300 V
● between main and auxiliary circuit
600 V
● between main and auxiliary circuit
690 V
shock resistance
● according to IEC 60068-2-27
15g / 11 ms
15g / 11 ms
vibration resistance
1-6 Hz, 15 mm; 6-500 Hz, 20 m/s²; 10 cycles
thermal current
200 A
type of protection according to ATEX directive
2014/34/EU
Ex II (2) G [Ex e] [Ex d] [Ex px] ; Ex II (2) D [Ex t] [Ex p]
certificate of suitability according to ATEX directive
2014/34/EU
PTB 06 ATEX 3001
reference code according to IEC 81346-2
F
Substance Prohibitance (Date)
07/01/2006
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-25 ... +60 °C
● during storage
-40 ... +80 °C
● during transport
-40 ... +80 °C
temperature compensation
-25 ... +60 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the
current-dependent overload release
50 ... 200 A
operating voltage
● rated value
1 000 V
● for remote-reset function at DC
24 V
3RB21534FC2
Page 1/4
7/4/2022
Subject to change without notice
© Copyright Siemens
● at AC-3e rated value maximum
1 000 V
operating frequency rated value
50 ... 60 Hz
operational current rated value
200 A
operational current at AC-3e at 400 V rated value
200 A
operating power
● for 3-phase motors at 400 V at 50 Hz
30 ... 90 kW
● for AC motors at 500 V at 50 Hz
30 ... 132 kW
● for AC motors at 690 V at 50 Hz
55 ... 160 kW
Auxiliary circuit
design of the auxiliary switch
integrated
number of NC contacts for auxiliary contacts
1
● note
number of NO contacts for auxiliary contacts
● note
number of CO contacts for auxiliary contacts
for contactor disconnection
1
for message "tripped"
0
operational current of auxiliary contacts at AC-15
● at 24 V
4A
● at 110 V
4A
● at 120 V
4A
● at 125 V
4A
● at 230 V
3A
operational current of auxiliary contacts at DC-13
● at 24 V
2A
● at 60 V
0.55 A
● at 110 V
0.3 A
● at 125 V
0.3 A
● at 220 V
0.11 A
Protective and monitoring functions
trip class
CLASS 5E, 10E, 20E and 30E adjustable
design of the overload release
electronic
response value current of the grounding protection
minimum
0.75 x IMotor
response time of the grounding protection in settled
state
1 000 ms
operating range of the grounding protection relating
to current set value
● minimum
IMotor > lower current setting value
● maximum
IMotor < upper current setting value x 3.5
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
200 A
● at 600 V rated value
200 A
contact rating of auxiliary contacts according to UL
B600 / R300
Short-circuit protection
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 355 A, Class L: 601 A
— with type of assignment 2 required
gG: 315 A
● for short-circuit protection of the auxiliary switch
required
fuse gG: 6 A
Installation/ mounting/ dimensions
mounting position
any
fastening method
Contactor mounting/stand-alone installation
height
119 mm
width
120 mm
depth
155 mm
Connections/ Terminals
product component removable terminal for auxiliary
and control circuit
Yes
type of electrical connection
3RB21534FC2
Page 2/4
7/4/2022
Subject to change without notice
© Copyright Siemens
● for main current circuit
busbar connection
● for auxiliary and control circuit
screw-type terminals
arrangement of electrical connectors for main current
circuit
Top and bottom
type of connectable conductor cross-sections
● for auxiliary contacts
— solid
1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
— solid or stranded
1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²)
— finely stranded with core end processing
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
● at AWG cables for auxiliary contacts
2x (20 ... 14)
tightening torque
● for main contacts with screw-type terminals
10 ... 12 N·m
● for auxiliary contacts with screw-type terminals
0.8 ... 1.2 N·m
design of the thread of the connection screw
● for main contacts
M10
● of the auxiliary and control contacts
M3
Safety related data
protection class IP on the front according to IEC
60529
IP00; IP20 with box terminal/cover
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front with box terminal/cover
Communication/ Protocol
type of voltage supply via input/output link master
No
Electromagnetic compatibility
conducted interference
● due to burst according to IEC 61000-4-4
2 kV (power ports), 1 kV (signal ports) corresponds to degree of severity
3
● due to conductor-earth surge according to IEC
61000-4-5
2 kV (line to earth) corresponds to degree of severity 3
● due to conductor-conductor surge according to IEC
61000-4-5
1 kV (line to line) corresponds to degree of severity 3
● due to high-frequency radiation according to IEC
61000-4-6
10 V in frequency range 0.15 to 80 MHz, modulation 80 % AM with 1
kHz
field-based interference according to IEC 61000-4-3
10 V/m
electrostatic discharge according to IEC 61000-4-2
6 kV contact discharge / 8 kV air discharge
Display
display version for switching status
Slide switch
Certificates/ approvals
General Product Approval
EMC
Confirmation
For use in hazardous locations
Declaration of
Conformity
Test Certificates
Special Test Certificate
Marine / Shipping
Marine / Shipping
Type Test Certificates/Test Report
other
Confirmation
3RB21534FC2
Page 3/4
7/4/2022
Miscellaneous
Subject to change without notice
© Copyright Siemens
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RB2153-4FC2
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RB2153-4FC2
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RB2153-4FC2
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RB2153-4FC2&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RB2153-4FC2/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RB2153-4FC2&objecttype=14&gridview=view1
last modified:
2/9/2022
3RB21534FC2
Page 4/4
7/4/2022
Subject to change without notice
© Copyright Siemens