Data sheet
3RB2153-4FX2
Overload relay 50...200 A for motor protection Size S6, CLASS 5...30E
Contactor mounting/stand-alone installation Main circuit: straight-through
transformer Auxiliary circuit: Spring-type terminal Manual-Automatic-Reset
Internal ground fault detection
product brand name
SIRIUS
product designation
solid-state overload relay
product type designation
3RB2
General technical data
size of overload relay
S6
size of contactor can be combined company-specific
S6
insulation voltage with degree of pollution 3 at AC rated
value
1 000 V
surge voltage resistance rated value
8 kV
maximum permissible voltage for safe isolation in
networks with grounded star point
● between auxiliary and auxiliary circuit
300 V
● between auxiliary and auxiliary circuit
300 V
● between main and auxiliary circuit
600 V
● between main and auxiliary circuit
690 V
shock resistance
● acc. to IEC 60068-2-27
15g / 11 ms
15g / 11 ms
vibration resistance
1-6 Hz, 15 mm; 6-500 Hz, 20 m/s²; 10 cycles
thermal current
200 A
recovery time after overload trip
● with automatic reset typical
3 min
● with remote-reset
0 min
● with manual reset
0 min
type of protection according to ATEX directive
2014/34/EU
Ex II (2) G [Ex e] [Ex d] [Ex px] ; Ex II (2) D [Ex t] [Ex p]
certificate of suitability according to ATEX directive
2014/34/EU
PTB 06 ATEX 3001
reference code acc. to IEC 81346-2
F
Substance Prohibitance (Date)
01.07.2006 00:00:00
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
● ambient temperature during operation
-25 ... +60 °C
● ambient temperature during storage
-40 ... +80 °C
● ambient temperature during transport
-40 ... +80 °C
temperature compensation
-25 ... +60 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3RB21534FX2
Page 1/2
3
1.21.2021
Subject to change without notice
© Copyright Siemens
adjustable current response value current of the
current-dependent overload release
50 ... 200 A
● operating voltage rated value
1 000 V
● operating voltage for remote-reset function at DC
24 V
● operating voltage at AC-3 rated value maximum
1 000 V
operating frequency rated value
50 ... 60 Hz
operational current rated value
200 A
operating power
● for 3-phase motors at 400 V at 50 Hz
30 ... 90 kW
● for AC motors at 500 V at 50 Hz
30 ... 132 kW
● for AC motors at 690 V at 50 Hz
55 ... 160 kW
Auxiliary circuit
design of the auxiliary switch
integrated
number of NC contacts for auxiliary contacts
1
● note
number of NO contacts for auxiliary contacts
● note
number of CO contacts for auxiliary contacts
for contactor disconnection
1
for message "tripped"
0
operational current of auxiliary contacts at AC-15
● at 24 V
4A
● at 110 V
4A
● at 120 V
4A
● at 125 V
4A
● at 230 V
3A
operational current of auxiliary contacts at DC-13
● at 24 V
2A
● at 60 V
0.55 A
● at 110 V
0.3 A
● at 125 V
0.3 A
● at 220 V
0.11 A
Protective and monitoring functions
trip class
CLASS 5E, 10E, 20E and 30E adjustable
design of the overload release
electronic
response value current of the grounding protection
minimum
0.75 x IMotor
response time of the grounding protection in settled
state
1 000 ms
operating range of the grounding protection relating
to current set value
● minimum
IMotor > lower current setting value
● maximum
IMotor < upper current setting value x 3.5
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
200 A
● at 600 V rated value
200 A
contact rating of auxiliary contacts according to UL
B600 / R300
Short-circuit protection
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 355 A, Class L: 601 A
— with type of assignment 2 required
gG: 315 A
● for short-circuit protection of the auxiliary switch
required
fuse gG: 6 A
Installation/ mounting/ dimensions
mounting position
any
fastening method
Contactor mounting/stand-alone installation
height
119 mm
width
120 mm
depth
155 mm
3RB21534FX2
Page 2/3
1.21.2021
Subject to change without notice
© Copyright Siemens
Connections/ Terminals
product function removable terminal for auxiliary and
control circuit
Yes
type of electrical connection
● for main current circuit
straight-through transformers
● for auxiliary and control circuit
spring-loaded terminals
arrangement of electrical connectors for main current
circuit
Top and bottom
type of connectable conductor cross-sections
● for auxiliary contacts
— solid
2x (0.25 ... 1.5 mm²)
— solid or stranded
2x (0,25 ... 1,5 mm²)
— finely stranded with core end processing
2x (0.25 ... 1.5 mm²)
— finely stranded without core end processing
2x (0.25 ... 1.5 mm²)
● at AWG cables for auxiliary contacts
2x (24 ... 16)
Safety related data
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe, for vertical contact from the front
Communication/ Protocol
type of voltage supply via input/output link master
No
Electromagnetic compatibility
conducted interference
● due to burst acc. to IEC 61000-4-4
2 kV (power ports), 1 kV (signal ports) corresponds to degree of severity
3
● due to conductor-earth surge acc. to IEC 61000-4-5
2 kV (line to earth) corresponds to degree of severity 3
● due to conductor-conductor surge acc. to IEC
61000-4-5
1 kV (line to line) corresponds to degree of severity 3
● due to high-frequency radiation acc. to IEC 610004-6
10 V in frequency range 0.15 to 80 MHz, modulation 80 % AM with 1
kHz
field-based interference acc. to IEC 61000-4-3
10 V/m
electrostatic discharge acc. to IEC 61000-4-2
6 kV contact discharge / 8 kV air discharge
Display
display version for switching status
Slide switch
Certificates/ approvals
General Product Approval
Declaration of Conformity
Miscellaneous
Marine / Shipping
Test Certificates
Type Test
Certificates/Test
Report
Marine / Shipping
Special Test
Certificate
other
Confirmation
3RB21534FX2
Page 3/4
For use in
hazardous
locations
EMC
Miscellaneous
1.21.2021
Subject to change without notice
© Copyright Siemens
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RB2153-4FX2
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RB2153-4FX2
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RB2153-4FX2
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RB2153-4FX2&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RB2153-4FX2/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RB2153-4FX2&objecttype=14&gridview=view1
3RB21534FX2
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RB21534FX2
Page 5/5
12/15/2020
1.21.2021
Subject to change without notice
© Copyright Siemens