Data sheet
3RB3016-1PE0
Overload relay 1...4 A Electronic For motor protection Size S00, Class 10E
Contactor mounting Main circuit: Spring-type terminal Auxiliary circuit: Spring-type
terminal Manual-Automatic-Reset
product brand name
SIRIUS
product designation
solid-state overload relay
product type designation
3RB3
General technical data
size of overload relay
S00
size of contactor can be combined company-specific
S00
power loss [W] for rated value of the current at AC in hot
operating state
0.1 W
● per pole
0.03 W
insulation voltage with degree of pollution 3 at AC rated value
690 V
surge voltage resistance rated value
6 kV
maximum permissible voltage for protective separation in
networks with grounded star point
● between auxiliary and auxiliary circuit
300 V
● between auxiliary and auxiliary circuit
300 V
● between main and auxiliary circuit
600 V
● between main and auxiliary circuit
690 V
shock resistance
● according to IEC 60068-2-27
15g / 11 ms
15g / 11 ms; Signaling contact 97 / 98 in position "Tripped": 9g / 11 ms
thermal current
4A
reference code according to IEC 81346-2
F
Substance Prohibitance (Date)
10/01/2009
SVHC substance name
Lead monoxide (lead oxide) - 1317-36-8
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-25 ... +60 °C
● during storage
-40 ... +80 °C
● during transport
-40 ... +80 °C
temperature compensation
-25 ... +60 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the currentdependent overload release
1 ... 4 A
operating voltage
● rated value
690 V
● at AC-3e rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current rated value
4A
operational current at AC-3e at 400 V rated value
4A
3RB30161PE0
Page 1/5
4/29/2024
Subject to change without notice
© Copyright Siemens
operating power
● for 3-phase motors at 400 V at 50 Hz
0.37 ... 1.5 kW
● for AC motors at 500 V at 50 Hz
0.37 ... 2.2 kW
● for AC motors at 690 V at 50 Hz
0.55 ... 3 kW
Auxiliary circuit
design of the auxiliary switch
integrated
number of NC contacts for auxiliary contacts
1
● note
number of NO contacts for auxiliary contacts
● note
number of CO contacts for auxiliary contacts
for contactor disconnection
1
for message "tripped"
0
operational current of auxiliary contacts at AC-15
● at 24 V
4A
● at 110 V
4A
● at 120 V
4A
● at 125 V
4A
● at 230 V
3A
operational current of auxiliary contacts at DC-13
● at 24 V
2A
● at 60 V
0.55 A
● at 110 V
0.3 A
● at 125 V
0.3 A
● at 220 V
0.11 A
Protective and monitoring functions
trip class
CLASS 10E
design of the overload release
electronic
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
4A
● at 600 V rated value
4A
contact rating of auxiliary contacts according to UL
B600 / R300
Short-circuit protection
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 35 A, RK5: 15 A
— with type of assignment 2 required
gG: 20 A
● for short-circuit protection of the auxiliary switch required
fuse gG: 6 A
Installation/ mounting/ dimensions
mounting position
any
fastening method
Contactor mounting
height
72 mm
width
45 mm
depth
90 mm
Connections/ Terminals
product component removable terminal for auxiliary and
control circuit
Yes
type of electrical connection
● for main current circuit
spring-loaded terminals
● for auxiliary and control circuit
spring-loaded terminals
arrangement of electrical connectors for main current
circuit
Top and bottom
type of connectable conductor cross-sections for main contacts
● solid
1x (0.5 ... 4 mm²)
● solid or stranded
1x (0,5 ... 4 mm²)
● finely stranded with core end processing
1x (0.5 ... 2.5 mm²)
● finely stranded without core end processing
1x (0.5 ... 2.5 mm²)
type of connectable conductor cross-sections
● for auxiliary contacts
— solid
2x (0.25 ... 1.5 mm²)
— solid or stranded
2x (0,25 ... 1,5 mm²)
— finely stranded with core end processing
2x (0.25 ... 1.5 mm²)
3RB30161PE0
Page 2/5
4/29/2024
Subject to change without notice
© Copyright Siemens
— finely stranded without core end processing
2x (0.25 ... 1.5 mm²)
● for AWG cables for auxiliary contacts
1x (24 ... 16), 2x (24 ... 16)
design of screwdriver shaft
Diameter 5 to 6 mm
size of the screwdriver tip
Pozidriv PZ 2
Electrical Safety
protection class IP on the front according to IEC 60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
Communication/ Protocol
type of voltage supply via input/output link master
No
Electromagnetic compatibility
conducted interference
● due to burst according to IEC 61000-4-4
2 kV (power ports), 1 kV (signal ports) corresponds to degree of severity 3
● due to conductor-earth surge according to IEC 61000-4-5
2 kV (line to earth) corresponds to degree of severity 3
● due to conductor-conductor surge according to IEC
61000-4-5
1 kV (line to line) corresponds to degree of severity 3
● due to high-frequency radiation according to IEC 610004-6
10 V in frequency range 0.15 to 80 MHz, modulation 80 % AM with 1 kHz
field-based interference according to IEC 61000-4-3
10 V/m
electrostatic discharge according to IEC 61000-4-2
6 kV contact discharge / 8 kV air discharge
Display
display version for switching status
Slide switch
Approvals Certificates
General Product Approval
Confirmation
General Product Approval
For use in hazardous locations
EMV
KC
Test Certificates
Special Test Certificate
Type Test Certificates/Test Report
Marine / Shipping
other
Confirmation
Environment
Environmental Confirmations
Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RB3016-1PE0
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RB3016-1PE0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RB3016-1PE0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
3RB30161PE0
Page 3/5
4/29/2024
Subject to change without notice
© Copyright Siemens
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RB3016-1PE0&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RB3016-1PE0/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RB3016-1PE0&objecttype=14&gridview=view1
3RB30161PE0
Page 4/5
4/29/2024
Subject to change without notice
© Copyright Siemens
95 NC
97 NO
96 NC
98 NO