Data sheet
3RH2122-1BB40
Contactor relay, 2 NO + 2 NC, 24 V DC, Size S00, screw terminal
product brand name
SIRIUS
product designation
Auxiliary contactor
product type designation
3RH2
General technical data
size of contactor
S00
product extension auxiliary switch
Yes
power loss [W] for rated value of the current without load current
share typical
4W
insulation voltage with degree of pollution 3 at AC rated value
690 V
degree of pollution
3
surge voltage resistance rated value
6 kV
shock resistance at rectangular impulse
● at DC
10g / 5 ms, 5g / 10 ms
shock resistance with sine pulse
● at DC
15g / 5 ms, 8g / 10 ms
mechanical service life (operating cycles)
● of contactor typical
30 000 000
● of the contactor with added electronically optimized
auxiliary switch block typical
5 000 000
● of the contactor with added auxiliary switch block typical
10 000 000
reference code according to IEC 81346-2
K
Substance Prohibitance (Date)
10/01/2009
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-25 ... +60 °C
● during storage
-55 ... +80 °C
relative humidity minimum
10 %
relative humidity at 55 °C according to IEC 60068-2-30
maximum
95 %
Environmental footprint
Environmental Product Declaration(EPD)
Yes
Global Warming Potential [CO2 eq] total
133 kg
Global Warming Potential [CO2 eq] during manufacturing
1.3 kg
Global Warming Potential [CO2 eq] during operation
132 kg
Global Warming Potential [CO2 eq] after end of life
-0.227 kg
Main circuit
no-load switching frequency
● at AC
10 000 1/h
● at DC
10 000 1/h
Control circuit/ Control
3RH21221BB40
Page 1/7
5/13/2024
Subject to change without notice
© Copyright Siemens
type of voltage of the control supply voltage
DC
control supply voltage at DC rated value
●
24 V
operating range factor control supply voltage rated value of
magnet coil at DC
● initial value
0.8
● full-scale value
1.1
closing power of magnet coil at DC
4W
holding power of magnet coil at DC
4W
closing delay
● at DC
30 ... 100 ms
opening delay
● at DC
arcing time
7 ... 13 ms
10 ... 15 ms
Auxiliary circuit
number of NC contacts for auxiliary contacts
● instantaneous contact
number of NO contacts for auxiliary contacts
● instantaneous contact
2
2
2
2
identification number and letter for switching elements
22 E
operational current at AC-12 maximum
10 A
operational current at AC-15
● at 230 V rated value
10 A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
operational current at 1 current path at DC-12
● at 24 V rated value
10 A
● at 110 V rated value
3A
● at 220 V rated value
1A
● at 440 V rated value
0.3 A
● at 600 V rated value
0.15 A
operational current with 2 current paths in series at DC-12
● at 24 V rated value
10 A
● at 60 V rated value
10 A
● at 110 V rated value
4A
● at 220 V rated value
2A
● at 440 V rated value
1.3 A
● at 600 V rated value
0.65 A
operational current with 3 current paths in series at DC-12
● at 24 V rated value
10 A
● at 60 V rated value
10 A
● at 110 V rated value
10 A
● at 220 V rated value
3.6 A
● at 440 V rated value
2.5 A
● at 600 V rated value
1.8 A
operating frequency at DC-12 maximum
1 000 1/h
operational current at 1 current path at DC-13
● at 24 V rated value
10 A
● at 110 V rated value
1A
● at 220 V rated value
0.3 A
● at 440 V rated value
0.14 A
● at 600 V rated value
0.1 A
operational current with 2 current paths in series at DC-13
● at 24 V rated value
10 A
● at 60 V rated value
3.5 A
● at 110 V rated value
1.3 A
● at 220 V rated value
0.9 A
● at 440 V rated value
0.2 A
● at 600 V rated value
0.1 A
operational current with 3 current paths in series at DC-13
3RH21221BB40
Page 2/7
5/13/2024
Subject to change without notice
© Copyright Siemens
● at 24 V rated value
10 A
● at 60 V rated value
4.7 A
● at 110 V rated value
3A
● at 220 V rated value
1.2 A
● at 440 V rated value
0.5 A
● at 600 V rated value
0.26 A
operating frequency at DC-13 maximum
1 000 1/h
design of the miniature circuit breaker for short-circuit protection
of the auxiliary circuit up to 230 V
C characteristic: 6 A; 0.4 kA
contact reliability of auxiliary contacts
1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
contact rating of auxiliary contacts according to UL
A600 / Q600
Short-circuit protection
design of the fuse link for short-circuit protection of the auxiliary
switch required
fuse gL/gG: 10 A
Installation/ mounting/ dimensions
mounting position
+/-180° rotation possible on vertical mounting surface; can be tilted forward and
backward by +/- 22.5° on vertical mounting surface
fastening method
screw and snap-on mounting onto 35 mm DIN rail
height
57.5 mm
width
45 mm
depth
73 mm
required spacing
● with side-by-side mounting
— forwards
10 mm
— upwards
10 mm
— downwards
10 mm
— at the side
0 mm
● for grounded parts
— forwards
10 mm
— upwards
10 mm
— at the side
6 mm
— downwards
10 mm
● for live parts
— forwards
10 mm
— upwards
10 mm
— downwards
10 mm
— at the side
6 mm
Connections/ Terminals
type of electrical connection for auxiliary and control circuit
screw-type terminals
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● for AWG cables for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14), 2x 12
Safety related data
product function positively driven operation according to IEC
60947-5-1
Yes
proportion of dangerous failures
● with low demand rate according to SN 31920
40 %
● with high demand rate according to SN 31920
73 %
B10 value with high demand rate according to SN 31920
1 000 000; With 0.3 x Ie
failure rate [FIT] with low demand rate according to SN
31920
100 FIT
IEC 61508
T1 value
● for proof test interval or service life according to IEC
61508
20 a
Electrical Safety
protection class IP on the front according to IEC 60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
Approvals Certificates
3RH21221BB40
Page 3/7
5/13/2024
Subject to change without notice
© Copyright Siemens
General Product Approval
Confirmation
General Product Approval
EMV
Functional Saftey
KC
Test Certificates
Type Examination Certificate
Test Certificates
Type Test Certificates/Test Report
Special Test Certificate
Marine / Shipping
Miscellaneous
Marine / Shipping
other
Miscellaneous
Confirmation
Railway
Dangerous Good
Special Test Certificate
Transport Information
Environment
Environmental Confirmations
Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RH2122-1BB40
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RH2122-1BB40
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RH2122-1BB40
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RH2122-1BB40&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RH2122-1BB40/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RH2122-1BB40&objecttype=14&gridview=view1
3RH21221BB40
Page 4/7
5/13/2024
Subject to change without notice
© Copyright Siemens
3RH21221BB40
Page 5/7
5/13/2024
Subject to change without notice
© Copyright Siemens
3RH21221BB40
Page 6/7
5/13/2024
Subject to change without notice
© Copyright Siemens
31
32
43
21
22
13
A1 (+)
last modified:
3RH21221BB40
Page 7/7
44
14
A2 (-)
-K
10/31/2023
5/13/2024
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RH2122-1BB40”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格
- 1+262.73740
- 2+248.41170
- 国内价格
- 1+391.78732
- 10+330.15786
- 25+309.02775
- 50+297.58228