Data sheet
3RH2262-1BB40
contactor relay, 6 NO + 2 NC, 24 V DC, size S00, screw terminal, captive
auxiliary switch
product brand name
SIRIUS
product designation
Auxiliary contactor
product type designation
3RH2
General technical data
size of contactor
S00
product extension auxiliary switch
No
insulation voltage with degree of pollution 3 at AC rated
value
690 V
degree of pollution
3
surge voltage resistance rated value
6 kV
shock resistance at rectangular impulse
● at DC
10g / 5 ms, 5g / 10 ms
shock resistance with sine pulse
● at DC
15g / 5 ms, 8g / 10 ms
mechanical service life (switching cycles)
● of contactor typical
10 000 000
reference code according to IEC 81346-2
K
Substance Prohibitance (Date)
10/01/2009
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-25 ... +60 °C
● during storage
-55 ... +80 °C
relative humidity minimum
10 %
relative humidity at 55 °C according to IEC 60068-2-30
maximum
95 %
Main circuit
no-load switching frequency
● at AC
10 000 1/h
● at DC
10 000 1/h
Control circuit/ Control
type of voltage of the control supply voltage
DC
control supply voltage at DC
● rated value
24 V
operating range factor control supply voltage rated
value of magnet coil at DC
● initial value
0.8
● full-scale value
1.1
closing power of magnet coil at DC
4W
holding power of magnet coil at DC
4W
3RH22621BB40
Page 1/5
7/4/2022
Subject to change without notice
© Copyright Siemens
closing delay
● at DC
30 ... 100 ms
opening delay
● at DC
arcing time
7 ... 13 ms
10 ... 15 ms
Auxiliary circuit
number of NC contacts for auxiliary contacts
● instantaneous contact
number of NO contacts for auxiliary contacts
● instantaneous contact
2
2
6
6
identification number and letter for switching
elements
62 E
operational current at AC-12 maximum
10 A
operational current at AC-15
● at 230 V rated value
6A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
operational current at 1 current path at DC-12
● at 24 V rated value
10 A
● at 110 V rated value
3A
● at 220 V rated value
1A
● at 440 V rated value
0.3 A
● at 600 V rated value
0.15 A
operational current with 2 current paths in series at
DC-12
● at 24 V rated value
10 A
● at 60 V rated value
10 A
● at 110 V rated value
4A
● at 220 V rated value
2A
● at 440 V rated value
1.3 A
● at 600 V rated value
0.65 A
operational current with 3 current paths in series at
DC-12
● at 24 V rated value
10 A
● at 60 V rated value
10 A
● at 110 V rated value
10 A
● at 220 V rated value
3.6 A
● at 440 V rated value
2.5 A
● at 600 V rated value
1.8 A
operating frequency at DC-12 maximum
1 000 1/h
operational current at 1 current path at DC-13
● at 24 V rated value
6A
● at 110 V rated value
1A
● at 220 V rated value
0.3 A
● at 440 V rated value
0.14 A
● at 600 V rated value
0.1 A
operational current with 2 current paths in series at
DC-13
● at 24 V rated value
10 A
● at 60 V rated value
3.5 A
● at 110 V rated value
1.3 A
● at 220 V rated value
0.9 A
● at 440 V rated value
0.2 A
● at 600 V rated value
0.1 A
operational current with 3 current paths in series at
DC-13
● at 24 V rated value
10 A
● at 60 V rated value
4.7 A
● at 110 V rated value
3A
● at 220 V rated value
1.2 A
3RH22621BB40
Page 2/5
7/4/2022
Subject to change without notice
© Copyright Siemens
● at 440 V rated value
0.5 A
● at 600 V rated value
0.26 A
operating frequency at DC-13 maximum
1 000 1/h
design of the miniature circuit breaker for short-circuit
protection of the auxiliary circuit up to 230 V
C characteristic: 6 A; 0.4 kA
contact reliability of auxiliary contacts
1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
contact rating of auxiliary contacts according to UL
A600 / Q600
Short-circuit protection
design of the fuse link for short-circuit protection of the
auxiliary switch required
fuse gL/gG: 10 A
Installation/ mounting/ dimensions
mounting position
+/-180° rotation possible on vertical mounting surface; can be tilted
forward and backward by +/- 22.5° on vertical mounting surface
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
height
57.5 mm
width
45 mm
depth
117 mm
required spacing
● with side-by-side mounting
— forwards
10 mm
— upwards
10 mm
— downwards
10 mm
— at the side
0 mm
● for grounded parts
— forwards
10 mm
— upwards
10 mm
— at the side
6 mm
— downwards
10 mm
● for live parts
— forwards
10 mm
— upwards
10 mm
— downwards
10 mm
— at the side
6 mm
Connections/ Terminals
type of electrical connection for auxiliary and control circuit
screw-type terminals
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14), 2x 12
Safety related data
B10 value with high demand rate according to SN 31920
1 000 000; With 0.3 x Ie
proportion of dangerous failures
● with low demand rate according to SN 31920
40 %
● with high demand rate according to SN 31920
73 %
failure rate [FIT] with low demand rate according to SN
31920
100 FIT
T1 value for proof test interval or service life according to
IEC 61508
20 y
protection class IP on the front according to IEC
60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
Certificates/ approvals
General Product Approval
Confirmation
3RH22621BB40
Page 3/5
7/4/2022
KC
Subject to change without notice
© Copyright Siemens
EMC
Functional
Safety/Safety of
Machinery
Declaration of Conformity
Type Examination
Certificate
Test Certificates
Special Test Certificate
Type Test Certificates/Test Report
Marine / Shipping
Marine / Shipping
other
Confirmation
Dangerous Good
Transport Information
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RH2262-1BB40
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RH2262-1BB40
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RH2262-1BB40
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RH2262-1BB40&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RH2262-1BB40/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RH2262-1BB40&objecttype=14&gridview=view1
3RH22621BB40
Page 4/5
7/4/2022
Subject to change without notice
© Copyright Siemens
last modified:
3RH22621BB40
Page 5/5
12/1/2021
7/4/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RH22621BB40”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+1535.848711+190.52132
- 10+1341.6103910+166.42615
- 25+1271.3253125+157.70732
- 50+1220.6090650+151.41599