Data sheet
3RM1107-2AA04
Fail-safe direct starter, 3RM1, 500 V, 0.55 - 3 kW, 1.6 - 7 A, 24 V DC,
spring-type terminals
product brand name
SIRIUS
product category
Motor starter
product designation
Fail-safe direct starter
design of the product
With electronic overload protection and safety-related disconnection
product type designation
3RM1
General technical data
trip class
CLASS 10A
product function
● intrinsic device protection
Yes
suitability for operation device connector 3ZY12
Yes
power loss [W] for rated value of the current at AC in hot
operating state per pole
1.13 W
insulation voltage rated value
500 V
surge voltage resistance rated value
6 kV
maximum permissible voltage for safe isolation
● between main and auxiliary circuit
500 V
● between control and auxiliary circuit
250 V
shock resistance
6g / 11 ms
vibration resistance
1 ... 6 Hz, 15 mm; 20 m/s², 500 Hz
operating frequency maximum
1 1/s
mechanical service life (switching cycles) typical
15 000 000
reference code acc. to IEC 81346-2
Q
Substance Prohibitance (Date)
01.03.2017 00:00:00
product function
● direct start
Yes
● reverse starting
No
product function short circuit protection
No
Electromagnetic compatibility
conducted interference
● due to burst acc. to IEC 61000-4-4
3 kV / 5 kHz
● due to conductor-earth surge acc. to IEC 61000-4-5
4 kV signal lines 2 kV
● due to conductor-conductor surge acc. to IEC
61000-4-5
2 kV
● due to high-frequency radiation acc. to IEC 610004-6
10 V
electrostatic discharge acc. to IEC 61000-4-2
6 kV contact discharge / 8 kV air discharge
conducted HF interference emissions acc. to CISPR11
Class B for the domestic, business and commercial environments
field-bound HF interference emission acc. to CISPR11
Class B for the domestic, business and commercial environments
3RM11072AA04
Page 1/2
1.20.2021
Subject to change without notice
© Copyright Siemens
Safety related data
safety device type acc. to IEC 61508-2
Type B
Safety Integrity Level (SIL) acc. to IEC 61508
3
performance level (PL) acc. to EN ISO 13849-1
e
category acc. to EN ISO 13849-1
4
stop category acc. to DIN EN 60204-1
0
Safe failure fraction (SFF)
99.4 %
average diagnostic coverage level (DCavg)
99 %
diagnostics test interval by internal test function
maximum
600 s
function test interval maximum
1y
failure rate [FIT]
● at rate of recognizable hazardous failures (λdd)
1 400 FIT
● at rate of non-recognizable hazardous failures (λdu)
16 FIT
PFHD with high demand rate acc. to EN 62061
0.00000002 1/h
PFDavg with low demand rate acc. to IEC 61508
0.000018
MTTFd
75 y
hardware fault tolerance acc. to IEC 61508
1
T1 value for proof test interval or service life acc. to
IEC 61508
20 y
safe state
Load circuit open
OFF delay time with safety-related request
● when switched off via control inputs maximum
43 ms
● when switched off via supply voltage maximum
120 ms
hardware fault tolerance acc. to IEC 61508 relating to
ATEX
0
PFDavg with low demand rate acc. to IEC 61508
relating to ATEX
0.0005
PFHD with high demand rate acc. to EN 62061 relating
to ATEX
0.00000005 1/h
Safety Integrity Level (SIL) acc. to IEC 61508 relating
to ATEX
SIL2
T1 value for proof test interval or service life acc. to
IEC 61508 relating to ATEX
3y
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the
current-dependent overload release
1.6 ... 7 A
minimum load [%]
20 %
type of the motor protection
solid-state
● operating voltage rated value
48 ... 500 V
relative symmetrical tolerance of the operating
voltage
10 %
operating frequency 1 rated value
50 Hz
operating frequency 2 rated value
60 Hz
relative symmetrical tolerance of the operating
frequency
10 %
operational current
● at AC at 400 V rated value
7A
● at AC-53a at 400 V at ambient temperature 40 °C
rated value
7A
ampacity when starting maximum
56 A
operating power for 3-phase motors at 400 V at 50 Hz
0.55 ... 3 kW
derating temperature
40 °C
Inputs/ Outputs
input voltage at digital input
● at DC rated value
24 V
● with signal at DC
0 ... 5 V
● for signal at DC
15 ... 30
input current at digital input
3RM11072AA04
Page 2/3
1.20.2021
Subject to change without notice
© Copyright Siemens
● for signal at DC
8 mA
● with signal at DC
1 mA
number of CO contacts for auxiliary contacts
1
operational current of auxiliary contacts at AC-15 at
230 V maximum
3A
operational current of auxiliary contacts at DC-13 at
24 V maximum
1A
Control circuit/ Control
type of voltage of the control supply voltage
● control supply voltage 1 at DC rated value
DC
24 V
operating range factor control supply voltage rated
value at DC
● initial value
0.8
● full-scale value
1.25
control current at DC
● in standby mode of operation
13 mA
● when switching on
150 mA
● during operation
57 mA
Response times
switch ON delay time
65 ... 76 ms
OFF delay time
30 ... 43 ms
Installation/ mounting/ dimensions
mounting position
vertical, horizontal, standing (observe derating)
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
height
100 mm
width
22.5 mm
depth
141.6 mm
required spacing
● with side-by-side mounting
— forwards
0 mm
— backwards
0 mm
— upwards
50 mm
— downwards
50 mm
— at the side
0 mm
● for grounded parts
— forwards
0 mm
— backwards
0 mm
— upwards
50 mm
— at the side
3.5 mm
— downwards
50 mm
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
relative humidity during operation
10 ... 95 %
● air pressure acc. to SN 31205
900 ... 1 060 hPa
Communication/ Protocol
product function bus communication
No
Connections/ Terminals
type of electrical connection
spring-loaded terminals (push-in) for main circuit, spring-loaded
terminals (push-in) for control circuit
● for main current circuit
spring-loaded terminals (push-in)
● for auxiliary and control circuit
spring-loaded terminals (push-in)
type of electrical wiring
● for main current circuit
1 or 2 conductors
● for auxiliary and control circuit
1 or 2 conductors
type of connectable conductor cross-sections
● for main contacts
— solid
1x (0.5 ... 4 mm²)
— finely stranded with core end processing
1x (0.5 ... 2.5 mm²)
3RM11072AA04
Page 3/4
1.20.2021
Subject to change without notice
© Copyright Siemens
— finely stranded without core end processing
● at AWG cables for main contacts
1x (0.5 ... 4 mm²)
1x (20 ... 12)
connectable conductor cross-section for main
contacts
● solid or stranded
0.5 ... 4 mm²
● finely stranded with core end processing
0.5 ... 2.5 mm²
● finely stranded without core end processing
0.5 ... 4 mm²
connectable conductor cross-section for auxiliary
contacts
● solid or stranded
0.5 ... 1.5 mm²
● finely stranded with core end processing
0.5 ... 1 mm²
● finely stranded without core end processing
0.5 ... 1.5 mm²
type of connectable conductor cross-sections
● for auxiliary contacts
— solid
1x (0.5 ... 1.5 mm²), 2x (0.5 ... 1.5 mm²)
— finely stranded with core end processing
1x (0,5 ... 1,0 mm²), 2x (0,5 ... 1,0 mm²)
— finely stranded without core end processing
1x (0.5 ... 1.5 mm²), 2x (0.5 ... 1.5 mm²)
● at AWG cables for auxiliary contacts
1x (20 ... 16), 2x (20 ... 16)
● AWG number as coded connectable conductor
cross section for main contacts
20 ... 12
● AWG number as coded connectable conductor
cross section for auxiliary contacts
20 ... 16
UL/CSA ratings
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
0.25 hp
— at 230 V rated value
0.5 hp
● for 3-phase AC motor
— at 200/208 V rated value
1 hp
— at 220/230 V rated value
1.5 hp
— at 460/480 V rated value
3 hp
Certificates/ approvals
General Product Approval
Functional
Safety/Safety of
Machinery
Type Examination
Certificate
Declaration of Conformity
Test Certificates
Miscellaneous
Type Test
Certificates/Test
Report
EMC
For use in
hazardous
locations
other
Railway
Confirmation
Special Test
Certificate
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RM1107-2AA04
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RM1107-2AA04
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RM1107-2AA04
3RM11072AA04
Page 4/5
1.20.2021
Subject to change without notice
© Copyright Siemens
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RM1107-2AA04&lang=en
3RM11072AA04
Page 5/6
1.20.2021
Subject to change without notice
© Copyright Siemens
3RM11072AA04
Page 6/7
1.20.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RM11072AA04
Page 7/7
12/23/2020
1.20.2021
Subject to change without notice
© Copyright Siemens