Data sheet
3RM1107-3AA04
Fail-safe direct starter, 3RM1, 500 V, 0.55 - 3 kW, 1.6 - 7 A, 24 V DC,
screw/spring-type terminals
product brand name
SIRIUS
product category
Motor starter
product designation
Fail-safe direct starter
design of the product
With electronic overload protection and safety-related disconnection
product type designation
3RM1
General technical data
trip class
CLASS 10A
equipment variant according to IEC 60947-4-2
3
product function
fail-safe direct starter
● intrinsic device protection
Yes
● for power supply reverse polarity protection
Yes
suitability for operation device connector 3ZY12
Yes
insulation voltage rated value
500 V
overvoltage category
III
surge voltage resistance rated value
6 kV
maximum permissible voltage for safe isolation
● between main and auxiliary circuit
500 V
● between control and auxiliary circuit
250 V
shock resistance
6g / 11 ms
vibration resistance
1 ... 6 Hz, 15 mm; 20 m/s², 500 Hz
operating frequency maximum
1 1/s
mechanical service life (switching cycles) typical
15 000 000
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
03/01/2017
product function
● direct start
Yes
● reverse starting
No
product function short circuit protection
No
Electromagnetic compatibility
EMC emitted interference according to IEC 60947-1
class A
EMC immunity according to IEC 60947-1
Class A
conducted interference
● due to burst according to IEC 61000-4-4
3 kV / 5 kHz
● due to conductor-earth surge according to IEC
61000-4-5
4 kV signal lines 2 kV
● due to conductor-conductor surge according to IEC
61000-4-5
2 kV
● due to high-frequency radiation according to IEC
61000-4-6
10 V
field-based interference according to IEC 61000-4-3
3RM11073AA04
Page 1/5
10 V/m
7/8/2022
Subject to change without notice
© Copyright Siemens
electrostatic discharge according to IEC 61000-4-2
6 kV contact discharge / 8 kV air discharge
conducted HF interference emissions according to
CISPR11
Class B for the domestic, business and commercial environments
field-bound HF interference emission according to
CISPR11
Class B for the domestic, business and commercial environments
Safety related data
safety device type according to IEC 61508-2
Type B
Safety Integrity Level (SIL) according to IEC 61508
3
SIL Claim Limit (subsystem) according to EN 62061
SILCL 3
performance level (PL) according to EN ISO 13849-1
e
category according to EN ISO 13849-1
4
stop category according to EN 60204-1
0
Safe failure fraction (SFF)
99.4 %
average diagnostic coverage level (DCavg)
99 %
diagnostics test interval by internal test function
maximum
600 s
function test interval maximum
1y
failure rate [FIT]
● at rate of recognizable hazardous failures (λdd)
1 400 FIT
● at rate of non-recognizable hazardous failures (λdu)
16 FIT
PFHD with high demand rate according to EN 62061
0.00000002 1/h
PFDavg with low demand rate according to IEC 61508
0.000018
MTTFd
75 y
hardware fault tolerance according to IEC 61508
1
safe state
Load circuit open
protection class IP on the front according to IEC
60529
IP20
touch protection on the front according to IEC 60529
finger-safe
hardware fault tolerance according to IEC 61508
relating to ATEX
0
PFDavg with low demand rate according to IEC 61508
relating to ATEX
0.0005
PFHD with high demand rate according to EN 62061
relating to ATEX
0.00000005 1/h
Safety Integrity Level (SIL) according to IEC 61508
relating to ATEX
SIL2
T1 value for proof test interval or service life
according to IEC 61508 relating to ATEX
3y
Main circuit
number of poles for main current circuit
3
design of the switching contact
Hybrid
adjustable current response value current of the
current-dependent overload release
1.6 ... 7 A
minimum load [%]
20 %; from set rated current
type of the motor protection
solid-state
operating voltage rated value
48 ... 500 V
relative symmetrical tolerance of the operating
voltage
10 %
operating frequency 1 rated value
50 Hz
operating frequency 2 rated value
60 Hz
relative symmetrical tolerance of the operating
frequency
10 %
operational current
● at AC at 400 V rated value
7A
● at AC-3 at 400 V rated value
7A
● at AC-53a at 400 V at ambient temperature 40 °C
rated value
7A
ampacity when starting maximum
56 A
operating power for 3-phase motors at 400 V at 50 Hz
0.55 ... 3 kW
derating temperature
40 °C
Inputs/ Outputs
input voltage at digital input
● at DC rated value
3RM11073AA04
Page 2/5
24 V
7/8/2022
Subject to change without notice
© Copyright Siemens
● with signal at DC
0 ... 5 V
● for signal at DC
15 ... 30
input current at digital input
● for signal at DC
8 mA
● with signal at DC
1 mA
number of CO contacts for auxiliary contacts
1
operational current of auxiliary contacts at AC-15 at
230 V maximum
3A
operational current of auxiliary contacts at DC-13 at
24 V maximum
1A
Control circuit/ Control
type of voltage of the control supply voltage
DC
control supply voltage at DC rated value
19.2 ... 30 V
relative negative tolerance of the control supply
voltage at DC
20 %
relative positive tolerance of the control supply
voltage at DC
25 %
control supply voltage 1 at DC rated value
24 V
operating range factor control supply voltage rated
value at DC
● initial value
0.8
● full-scale value
1.25
control current at DC
● in standby mode of operation
13 mA
● when switching on
150 mA
● during operation
57 mA
inrush current peak
● at DC at 24 V
300 mA
● at DC at 24 V at switching on of motor
130 mA
duration of inrush current peak
● at DC at 24 V
80 ms
● at DC at 24 V at switching on of motor
20 ms
power loss [W] in auxiliary and control circuit
● in switching state OFF
— with bypass circuit
0.35 W
● in switching state ON
— with bypass circuit
1.37 W
Response times
ON-delay time
65 ... 76 ms
OFF-delay time
30 ... 43 ms
Power Electronics
operational current
● at 40 °C rated value
7A
● at 50 °C rated value
6.1 A
● at 55 °C rated value
5.2 A
● at 60 °C rated value
4.6 A
Installation/ mounting/ dimensions
mounting position
vertical, horizontal, standing (observe derating)
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
height
100 mm
width
22.5 mm
depth
141.6 mm
required spacing
● with side-by-side mounting
— forwards
0 mm
— backwards
0 mm
— upwards
50 mm
— downwards
50 mm
— at the side
0 mm
● for grounded parts
— forwards
3RM11073AA04
Page 3/5
0 mm
7/8/2022
Subject to change without notice
© Copyright Siemens
— backwards
0 mm
— upwards
50 mm
— at the side
3.5 mm
— downwards
50 mm
Ambient conditions
installation altitude at height above sea level maximum
4 000 m; For derating see manual
ambient temperature
● during operation
-25 ... +60 °C
● during storage
-40 ... +70 °C
● during transport
-40 ... +70 °C
environmental category during operation according to IEC
60721
3K6 (no ice formation, only occasional condensation), 3C3 (no salt
mist), 3S2 (sand must not get into the devices), 3M6
relative humidity during operation
10 ... 95 %
air pressure according to SN 31205
900 ... 1 060 hPa
Communication/ Protocol
protocol is supported
● PROFINET IO protocol
No
● PROFIsafe protocol
No
product function bus communication
No
protocol is supported AS-Interface protocol
No
Connections/ Terminals
type of electrical connection
screw-type terminals for main circuit, spring-loaded terminals (push-in)
for control circuit
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
spring-loaded terminals (push-in)
wire length for motor unshielded maximum
100 m
type of connectable conductor cross-sections
● for main contacts
— solid
1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²)
— finely stranded with core end processing
1x (0,5 … 4 mm²), 2x (0,5 … 1,5 mm²)
● at AWG cables for main contacts
1x (20 ... 12), 2x (20 ... 14)
connectable conductor cross-section for main
contacts
● solid or stranded
0.5 ... 4 mm²
● finely stranded with core end processing
0.5 ... 4 mm²
connectable conductor cross-section for auxiliary
contacts
● solid or stranded
0.5 ... 1.5 mm²
● finely stranded with core end processing
0.5 ... 1 mm²
● finely stranded without core end processing
0.5 ... 1.5 mm²
type of connectable conductor cross-sections
● for auxiliary contacts
— solid
1x (0.5 ... 1.5 mm²), 2x (0.5 ... 1.5 mm²)
— finely stranded with core end processing
1x (0,5 ... 1,0 mm²), 2x (0,5 ... 1,0 mm²)
— finely stranded without core end processing
1x (0.5 ... 1.5 mm²), 2x (0.5 ... 1.5 mm²)
● at AWG cables for auxiliary contacts
1x (20 ... 16), 2x (20 ... 16)
AWG number as coded connectable conductor cross
section
● for main contacts
20 ... 12
● for auxiliary contacts
20 ... 16
UL/CSA ratings
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
0.25 hp
— at 230 V rated value
0.5 hp
● for 3-phase AC motor
— at 200/208 V rated value
1 hp
— at 220/230 V rated value
1.5 hp
— at 460/480 V rated value
3 hp
operating voltage at AC
● according to UL rated value
3RM11073AA04
Page 4/5
480 V
7/8/2022
Subject to change without notice
© Copyright Siemens
● according to CSA rated value
400 V
Certificates/ approvals
General Product Approval
EMC
Confirmation
For use in hazardous locations
Functional
Safety/Safety of
Machinery
Declaration of
Conformity
other
Type Examination
Certificate
Confirmation
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RM1107-3AA04
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RM1107-3AA04
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RM1107-3AA04
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RM1107-3AA04&lang=en
last modified:
3RM11073AA04
Page 5/5
6/21/2022
7/8/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RM11073AA04”相匹配的价格&库存,您可以联系我们找货
免费人工找货