Data sheet
3RP2005-1BW30
Timing relay, electronic Multifunction, 16 functions 2 change-over contacts
24 to 240 V AC/DC at 50/60 Hz AC 0.05 s to 100 h Overall width 45 mm
screw terminal
product brand name
SIRIUS
product designation
timing relay
design of the product
Multifunctional
product type designation
3RP20
General technical data
product component
● relay output
Yes
● semi-conductor output
No
product extension required remote control
No
product extension optional remote control
No
power loss [W] maximum
2W
insulation voltage for overvoltage category III according to
IEC 60664 with degree of pollution 3 rated value
300 V
test voltage for isolation test
2 kV
degree of pollution
3
surge voltage resistance rated value
4 000 V
shock resistance according to IEC 60068-2-27
11g / 15 ms
vibration resistance according to IEC 60068-2-6
10 ... 55 Hz / 0.35 mm
mechanical service life (switching cycles) typical
10 000 000
electrical endurance (switching cycles) at AC-15 at 230 V
typical
100 000
adjustable time
0.05 ... 100 s
relative setting accuracy relating to full-scale value
5 %; +/-
thermal current
5A
minimum ON period
35 ms
recovery time
150 ms
reference code according to IEC 81346-2
K
relative repeat accuracy
1 %; +/-
influence of the surrounding temperature
±5 %
power supply influence
±1 %
Substance Prohibitance (Date)
05/01/2012
Control circuit/ Control
type of voltage of the control supply voltage
AC/DC
control supply voltage 1 at AC
● at 50 Hz
24 ... 240 V
● at 60 Hz
24 ... 240 V
control supply voltage frequency 1
50 ... 60 Hz
control supply voltage 1
● at DC
24 ... 240 V
operating range factor control supply voltage rated
3RP20051BW30
Page 1/5
7/5/2022
Subject to change without notice
© Copyright Siemens
value at DC
● initial value
0.85
● full-scale value
1.1
operating range factor control supply voltage rated
value at AC at 50 Hz
● initial value
0.8
● full-scale value
1.1
operating range factor control supply voltage rated
value at AC at 60 Hz
● initial value
0.8
● full-scale value
1.1
Switching Function
switching function
● ON-delay
Yes
● ON-delay/instantaneous contact
Yes
● passing make contact
Yes
● passing make contact/instantaneous contact
Yes
● OFF delay
No
switching function
● flashing symmetrically with interval
start/instantaneous
Yes
● flashing symmetrically with interval start
Yes
● flashing symmetrically with pulse
start/instantaneous
No
● flashing symmetrically with pulse start
No
● flashing asymmetrically with interval start
No
● flashing asymmetrically with pulse start
No
switching function
● star-delta circuit with delay time
No
● star-delta circuit
Yes
switching function with control signal
● additive ON-delay
Yes
● passing break contact
Yes
● passing break contact/instantaneous
Yes
● OFF delay
Yes
● OFF delay/instantaneous
Yes
● pulse delayed
No
● pulse delayed/instantaneous
No
● pulse-shaping
Yes
● pulse-shaping/instantaneous
Yes
● additive ON-delay/instantaneous
Yes
● ON-delay/OFF-delay/instantaneous
Yes
● passing make contact
No
● passing make contact/instantaneous contact
Yes
switching function of interval relay with control signal
● retrotriggerable with deactivated control
signal/instantaneous contact
No
● retrotriggerable with switched-on control signal
No
● retrotriggerable with switched-on control
signal/instantaneous contact
No
● retriggerable with deactivated control signal
No
design of the control terminal non-floating
Yes
Short-circuit protection
design of the fuse link for short-circuit protection of the
auxiliary switch required
fuse gL/gG: 4 A
Auxiliary circuit
material of switching contacts
AgSnO2
number of NC contacts
● delayed switching
0
● instantaneous contact
0
number of NO contacts
3RP20051BW30
Page 2/5
7/5/2022
Subject to change without notice
© Copyright Siemens
● delayed switching
0
● instantaneous contact
0
number of CO contacts
● delayed switching
2
● instantaneous contact
0
operational current of auxiliary contacts at AC-15
● at 24 V
3A
● at 250 V
3A
operational current of auxiliary contacts at DC-13
● at 24 V
1A
● at 125 V
0.2 A
● at 250 V
0.1 A
operating frequency with 3RT2 contactor maximum
5 000 1/h
contact reliability of auxiliary contacts
one incorrect switching operation of 100 million switching operations (17
V, 5 mA)
contact rating of auxiliary contacts according to UL
R300 / B300
Inputs/ Outputs
product function
● non-volatile
No
Electromagnetic compatibility
EMC emitted interference according to IEC 61812-1
EN 61000-6-4(3)
EMC immunity according to IEC 61812-1
EN 61000-6-2
conducted interference
● due to burst according to IEC 61000-4-4
2 kV network connection / 1 kV control connection
● due to conductor-earth surge according to IEC
61000-4-5
2 kV
● due to conductor-conductor surge according to IEC
61000-4-5
1 kV
field-based interference according to IEC 61000-4-3
10 V/m
electrostatic discharge according to IEC 61000-4-2
4 kV contact discharge / 8 kV air discharge
Safety related data
protection class IP on the front according to IEC
60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
type of insulation
Basic insulation
category according to EN 954-1
none
Connections/ Terminals
product component removable terminal for auxiliary
and control circuit
No
type of electrical connection for auxiliary and control circuit
screw-type terminals
type of connectable conductor cross-sections
● solid
2x (0,5 ...1,5 mm²), 2x (0,75 ... 2,5 mm²)
● finely stranded with core end processing
2x (0,5 ...1,5 mm²), 2x (0,75 ... 2,5 mm²)
● at AWG cables solid
2x (18 ... 14)
● at AWG cables stranded
2x (18 ... 14)
connectable conductor cross-section
● solid
0.5 ... 2.5 mm²
● finely stranded with core end processing
0.5 ... 2.5 mm²
AWG number as coded connectable conductor cross
section
● solid
18 ... 14
● stranded
18 ... 14
tightening torque
0.8 ... 1.2 N·m
design of the thread of the connection screw
M3
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
height
57 mm
width
45 mm
depth
73 mm
required spacing
3RP20051BW30
Page 3/5
7/5/2022
Subject to change without notice
© Copyright Siemens
● with side-by-side mounting
— forwards
0 mm
— backwards
0 mm
— upwards
0 mm
— downwards
0 mm
— at the side
0 mm
● for grounded parts
— forwards
0 mm
— backwards
0 mm
— upwards
0 mm
— at the side
0 mm
— downwards
0 mm
● for live parts
— forwards
0 mm
— backwards
0 mm
— upwards
0 mm
— downwards
0 mm
— at the side
0 mm
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-25 ... +60 °C
● during storage
-40 ... +85 °C
● during transport
-40 ... +85 °C
relative humidity during operation
10 ... 95 %
Certificates/ approvals
General Product Approval
EMC
Declaration of
Conformity
Confirmation
Declaration of
Conformity
Test Certificates
Marine / Shipping
Type Test Certificates/Test Report
Marine / Shipping
other
Confirmation
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RP2005-1BW30
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RP2005-1BW30
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RP2005-1BW30
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
3RP20051BW30
Page 4/5
7/5/2022
Subject to change without notice
© Copyright Siemens
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RP2005-1BW30&lang=en
Characteristic: Derating
https://support.industry.siemens.com/cs/ww/en/ps/3RP2005-1BW30/manual
last modified:
3RP20051BW30
Page 5/5
12/9/2021
7/5/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RP2005-1BW30”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格
- 1+1380.99976
- 25+1346.48831
- 50+1325.23367