Data sheet
3RP2511-2AW30
Timing relay, electronic ansprechverzögert 1 change-over contact, 1 time
range 0.5...10 s 12-240 V AC/DC at 50/60 Hz AC with LED, Spring-type
terminal (push-in)
product brand name
SIRIUS
product designation
timing relay
design of the product
slow-operating
product type designation
3RP25
General technical data
product component
● relay output
Yes
● semi-conductor output
No
product extension required remote control
No
product extension optional remote control
No
insulation voltage for overvoltage category III according to
IEC 60664 with degree of pollution 3 rated value
300 V
test voltage for isolation test
2.5 kV
degree of pollution
3
surge voltage resistance rated value
4 000 V
protection class IP
IP20
shock resistance acc. to IEC 60068-2-27
11g / 15 ms
vibration resistance acc. to IEC 60068-2-6
10 ... 55 Hz / 0.35 mm
mechanical service life (switching cycles) typical
10 000 000
electrical endurance (switching cycles) at AC-15 at 230 V
typical
100 000
adjustable time
0.5 ... 10 s
relative setting accuracy relating to full-scale value
5%
thermal current
5A
recovery time
250 ms
reference code acc. to IEC 81346-2
K
relative repeat accuracy
1%
Control circuit/ Control
type of voltage of the control supply voltage
AC/DC
control supply voltage 1 at AC
● at 50 Hz
12 ... 240 V
● at 60 Hz
12 ... 240 V
control supply voltage frequency 1
● control supply voltage 1 at DC
50 ... 60 Hz
12 ... 240 V
operating range factor control supply voltage rated
value at DC
● initial value
0.8
● full-scale value
1.1
3RP25112AW30
Page 1/2
12.19.2020
Subject to change without notice
© Copyright Siemens
operating range factor control supply voltage rated
value at AC at 50 Hz
● initial value
0.8
● full-scale value
1.1
operating range factor control supply voltage rated
value at AC at 60 Hz
● initial value
0.8
● full-scale value
1.1
inrush current peak
● at 24 V
0.4 A
● at 240 V
5A
duration of inrush current peak
● at 24 V
0.3 ms
● at 240 V
0.5 ms
Switching Function
switching function
● ON-delay
Yes
● ON-delay/instantaneous contact
No
● passing make contact
No
● passing make contact/instantaneous contact
No
● OFF delay
No
switching function
● flashing symmetrically with interval
start/instantaneous
No
● flashing symmetrically with interval start
No
● flashing symmetrically with pulse
start/instantaneous
No
● flashing symmetrically with pulse start
No
● flashing asymmetrically with interval start
No
● flashing asymmetrically with pulse start
No
switching function
● star-delta circuit with delay time
No
● star-delta circuit
No
switching function with control signal
● additive ON-delay
No
● passing break contact
No
● passing break contact/instantaneous
No
● OFF delay
No
● OFF delay/instantaneous
No
● pulse delayed
No
● pulse delayed/instantaneous
No
● pulse-shaping
No
● pulse-shaping/instantaneous
No
● additive ON-delay/instantaneous
No
● ON-delay/OFF-delay/instantaneous
No
● passing make contact
No
● passing make contact/instantaneous contact
No
switching function of interval relay with control signal
● retrotriggerable with deactivated control
signal/instantaneous contact
No
● retrotriggerable with switched-on control signal
No
● retrotriggerable with switched-on control
signal/instantaneous contact
No
● retriggerable with deactivated control signal
No
Short-circuit protection
design of the fuse link for short-circuit protection of the
auxiliary switch required
fuse gL/gG: 4 A
Auxiliary circuit
material of switching contacts
AgSnO2
number of NC contacts delayed switching
0
3RP25112AW30
Page 2/3
12.19.2020
Subject to change without notice
© Copyright Siemens
number of NO contacts delayed switching
0
number of CO contacts delayed switching
1
operational current of auxiliary contacts at AC-15
● at 24 V
3A
● at 250 V
3A
operational current of auxiliary contacts at DC-13
● at 24 V
1A
● at 125 V
0.2 A
● at 250 V
0.1 A
operating frequency with 3RT2 contactor maximum
5 000 1/h
contact reliability of auxiliary contacts
one incorrect switching operation of 100 million switching operations (17
V, 5 mA)
contact rating of auxiliary contacts according to UL
R300 / B300
influence of the surrounding temperature
1% in the whole temperature range to the set runtime
power supply influence
1% in the whole voltage range to the set runtime
switching capacity current with inductive load
0.01 ... 3 A
Inputs/ Outputs
product function
● at the relay outputs switchover delayed/without
delay
No
● non-volatile
No
Electromagnetic compatibility
EMC immunity acc. to IEC 61812-1
EN 61000-6-2
conducted interference
● due to burst acc. to IEC 61000-4-4
2 kV network connection / 1 kV control connection
● due to conductor-earth surge acc. to IEC 61000-4-5
2 kV
● due to conductor-conductor surge acc. to IEC
61000-4-5
1 kV
field-based interference acc. to IEC 61000-4-3
10 V/m
electrostatic discharge acc. to IEC 61000-4-2
4 kV contact discharge / 8 kV air discharge
Safety related data
touch protection against electrical shock
finger-safe
type of insulation
Basic insulation
category acc. to EN 954-1
none
Connections/ Terminals
product function removable terminal for auxiliary and
control circuit
Yes
type of electrical connection for auxiliary and control circuit
spring-loaded terminals (push-in)
type of connectable conductor cross-sections
● solid
0.5 ... 4 mm²
● finely stranded with core end processing
0.5 ... 2.5 mm²
● finely stranded without core end processing
0.5 ... 4 mm²
● at AWG cables solid
20 ... 12
● at AWG cables stranded
20 ... 12
● connectable conductor cross-section solid
0.5 ... 4 mm²
● connectable conductor cross-section finely stranded
with core end processing
0.5 ... 2.5 mm²
● connectable conductor cross-section finely stranded
without core end processing
0.5 ... 4 mm²
● AWG number as coded connectable conductor
cross section solid
20 ... 12
● AWG number as coded connectable conductor
cross section stranded
20 ... 12
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
height
100 mm
width
17.5 mm
depth
90 mm
3RP25112AW30
Page 3/4
12.19.2020
Subject to change without notice
© Copyright Siemens
required spacing
● with side-by-side mounting
— forwards
0 mm
— backwards
0 mm
— upwards
0 mm
— downwards
0 mm
— at the side
0 mm
● for grounded parts
— forwards
0 mm
— backwards
0 mm
— upwards
0 mm
— at the side
0 mm
— downwards
0 mm
● for live parts
— forwards
0 mm
— backwards
0 mm
— upwards
0 mm
— downwards
0 mm
— at the side
0 mm
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
● ambient temperature during operation
-25 ... +60 °C
● ambient temperature during storage
-40 ... +85 °C
● ambient temperature during transport
-40 ... +85 °C
relative humidity during operation
10 ... 95 %
Certificates/ approvals
General Product Approval
Declaration of
Conformity
Miscellaneous
Marine / Shipping
Test Certificates
EMC
Declaration of
Conformity
Marine / Shipping
Type Test
Certificates/Test
Report
other
Confirmation
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RP2511-2AW30
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RP2511-2AW30
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
3RP25112AW30
Page 4/5
12.19.2020
Subject to change without notice
© Copyright Siemens
https://support.industry.siemens.com/cs/ww/en/ps/3RP2511-2AW30
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RP2511-2AW30&lang=en
Characteristic: Derating
https://support.industry.siemens.com/cs/ww/en/ps/3RP2511-2AW30/manual
3RP25112AW30
Page 5/6
12.19.2020
Subject to change without notice
© Copyright Siemens
last modified:
5/15/2020
3RP25112AW30
Page 6/6
12.19.2020
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RP25112AW30”相匹配的价格&库存,您可以联系我们找货