Data sheet
3RT1075-2XJ46-0LA2
Traction contactor, AC-3 400 A, 200 kW / 400 V Coil 72 V DC x (0.7-1.25)
PLC input 24-110 V DC Auxiliary contacts 2 NO + 2 NC 3-pole size S12
Busbar connections Coil connection: Spring-type terminal
product brand name
SIRIUS
product designation
Contactor
design of the product
With extended operating range
product type designation
3RT1
General technical data
size of contactor
S12
product extension
● function module for communication
No
● auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
105 W
● at AC in hot operating state per pole
35 W
● without load current share typical
3.6 W
insulation voltage
● of main circuit with degree of pollution 3 rated value
1 000 V
● of auxiliary circuit with degree of pollution 3 rated
value
500 V
surge voltage resistance
● of main circuit rated value
8 kV
● of auxiliary circuit rated value
6 kV
maximum permissible voltage for safe isolation between
coil and main contacts according to EN 60947-1
690 V
shock resistance for railway applications according to EN
61373
Category 1, Class B
shock resistance at rectangular impulse
● at DC
8,5g / 5 ms, 4,2g / 10 ms
shock resistance with sine pulse
● at DC
13,4g / 5 ms, 6,5g / 10 ms
mechanical service life (switching cycles)
● of contactor typical
10 000 000
● of the contactor with added electronically optimized
auxiliary switch block typical
5 000 000
● of the contactor with added auxiliary switch block
typical
10 000 000
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
09/06/2016
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-40 ... +70 °C
● during storage
-55 ... +80 °C
3RT10752XJ460LA2
Page 1/6
7/8/2022
Subject to change without notice
© Copyright Siemens
relative humidity minimum
10 %
relative humidity at 55 °C according to IEC 60068-2-30
maximum
95 %
Main circuit
number of poles for main current circuit
3
number of NO contacts for main contacts
3
number of NC contacts for main contacts
0
operating voltage
● at AC-3 rated value maximum
1 000 V
● at AC-3e rated value maximum
1 000 V
operational current
● at AC-1 at 400 V at ambient temperature 40 °C
rated value
430 A
● at AC-1
— up to 690 V at ambient temperature 40 °C
rated value
430 A
— up to 690 V at ambient temperature 60 °C
rated value
400 A
— up to 1000 V at ambient temperature 60 °C
rated value
200 A
● at AC-2 at 400 V rated value
400 A
● at AC-3
— at 400 V rated value
400 A
— at 500 V rated value
400 A
— at 690 V rated value
400 A
— at 1000 V rated value
180 A
● at AC-3e
— at 400 V rated value
400 A
— at 500 V rated value
400 A
— at 690 V rated value
400 A
— at 1000 V rated value
180 A
● at AC-4 at 400 V rated value
350 A
minimum cross-section in main circuit
● at maximum AC-1 rated value
300 mm²
● at maximum Ith rated value
300 mm²
operational current for approx. 200000 operating
cycles at AC-4
● at 400 V rated value
150 A
● at 690 V rated value
135 A
operating power
● at AC-2 at 400 V rated value
200 kW
● at AC-3
— at 230 V rated value
132 kW
— at 400 V rated value
200 kW
— at 500 V rated value
250 kW
— at 690 V rated value
400 kW
— at 1000 V rated value
250 kW
● at AC-3e
— at 230 V rated value
132 kW
— at 400 V rated value
200 kW
— at 500 V rated value
250 kW
— at 690 V rated value
400 kW
— at 1000 V rated value
250 kW
operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value
85 kW
● at 690 V rated value
133 kW
short-time withstand current in cold operating state
up to 40 °C
● limited to 1 s switching at zero current maximum
6 600 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 5 s switching at zero current maximum
5 761 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 10 s switching at zero current maximum
4 143 A; Use minimum cross-section acc. to AC-1 rated value
3RT10752XJ460LA2
Page 2/6
7/8/2022
Subject to change without notice
© Copyright Siemens
● limited to 30 s switching at zero current maximum
2 635 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 60 s switching at zero current maximum
2 088 A; Use minimum cross-section acc. to AC-1 rated value
no-load switching frequency
● at DC
500 1/h
operating frequency
● at AC-1 maximum
500 1/h
● at AC-2 maximum
200 1/h
● at AC-3 maximum
500 1/h
● at AC-3e maximum
500 1/h
● at AC-2 at AC-3e maximum
200 1/h
● at AC-4 maximum
130 1/h
operating frequency
● at DC-1 maximum
250 1/h
● at DC-3 maximum
250 1/h
● at DC-5 maximum
250 1/h
Ratings for railway applications
thermal current (Ith) up to 690 V
● up to 40 °C according to IEC 60077 rated value
430 A
● up to 70 °C according to IEC 60077 rated value
350 A
Control circuit/ Control
type of voltage
DC
type of voltage of the control supply voltage
DC
control supply voltage at DC
● rated value
72 V
consumed current at PLC-control input according to
IEC 60947-1 maximum
2 mA
voltage at PLC-control input rated value
24 V
operating range factor control supply voltage rated
value of magnet coil at DC
● initial value
0.7
● full-scale value
1.25
design of the surge suppressor
with varistor
closing power of magnet coil at DC
800 W
holding power of magnet coil at DC
3.6 W
closing delay
● at DC
60 ... 90 ms
opening delay
● at DC
80 ... 100 ms
arcing time
10 ... 15 ms
control version of the switch operating mechanism
PLC-IN or Standard A1 - A2 (adjustable)
Auxiliary circuit
number of NC contacts for auxiliary contacts
● instantaneous contact
number of NO contacts for auxiliary contacts
● instantaneous contact
operational current at AC-12 maximum
2
2
2
2
10 A
operational current at AC-15
● at 230 V rated value
6A
● at 400 V rated value
3A
● at 500 V rated value
2A
operational current at DC-12
● at 24 V rated value
10 A
● at 48 V rated value
6A
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 125 V rated value
2A
● at 220 V rated value
1A
● at 600 V rated value
0.15 A
operational current at DC-13
● at 24 V rated value
3RT10752XJ460LA2
Page 3/6
6A
7/8/2022
Subject to change without notice
© Copyright Siemens
● at 48 V rated value
2A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 125 V rated value
0.9 A
● at 220 V rated value
0.3 A
● at 600 V rated value
0.1 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
361 A
● at 600 V rated value
382 A
yielded mechanical performance [hp]
● for 3-phase AC motor
— at 200/208 V rated value
125 hp
— at 220/230 V rated value
150 hp
— at 460/480 V rated value
300 hp
— at 575/600 V rated value
400 hp
contact rating of auxiliary contacts according to UL
A600 / Q600
Short-circuit protection
product function short circuit protection
No
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 630 A (690 V, 100 kA)
— with type of assignment 2 required
gG: 500 A (690 V, 100 kA), aM: 400 A (690 V, 50 kA), BS88: 450 A (415
V, 50 kA)
● for short-circuit protection of the auxiliary switch
required
gG: 10 A (500 V, 1 kA)
Installation/ mounting/ dimensions
mounting position
with vertical mounting surface +/-90° rotatable, with vertical mounting
surface +/- 22.5° tiltable to the front and back
fastening method
screw fixing
● side-by-side mounting
Yes
height
214 mm
width
160 mm
depth
225 mm
required spacing
● with side-by-side mounting
— forwards
20 mm
— upwards
10 mm
— downwards
10 mm
— at the side
10 mm
● for grounded parts
— forwards
20 mm
— upwards
10 mm
— at the side
10 mm
— downwards
10 mm
● for live parts
— forwards
20 mm
— upwards
10 mm
— downwards
10 mm
— at the side
10 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
spring-loaded terminals
width of connection bar
25 mm
thickness of connection bar
6 mm
diameter of holes
11 mm
number of holes
1
type of connectable conductor cross-sections
● for main contacts
3RT10752XJ460LA2
Page 4/6
7/8/2022
Subject to change without notice
© Copyright Siemens
— solid or stranded
2x (70 ... 240 mm²)
● at AWG cables for main contacts
2/0 ... 500 kcmil
type of connectable conductor cross-sections
● for auxiliary contacts
— solid
2x (0.25 ... 2.5 mm²)
— solid or stranded
2x (0,25 ... 2,5 mm²)
— finely stranded with core end processing
2x (0.25 ... 1.5 mm²)
— finely stranded without core end processing
2x (0.25 ... 2.5 mm²)
● at AWG cables for auxiliary contacts
2x (24 ... 14)
AWG number as coded connectable conductor cross
section
● for auxiliary contacts
24 ... 14
Safety related data
product function
● mirror contact according to IEC 60947-4-1
Yes
● positively driven operation according to IEC 609475-1
No
B10 value with high demand rate according to SN 31920
1 000 000
protection class IP on the front according to IEC
60529
IP00; IP20 with box terminal/cover
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front with box terminal/cover
Communication/ Protocol
product function bus communication
No
Certificates/ approvals
General Product Approval
EMC
Confirmation
Functional
Safety/Safety of
Machinery
Declaration of Conformity
Test Certificates
Type Examination
Certificate
Special Test Certificate
other
Confirmation
other
Type Test Certificates/Test Report
Miscellaneous
Railway
Miscellaneous
Special Test Certificate
Type Test Certificates/Test Report
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT1075-2XJ46-0LA2
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT1075-2XJ46-0LA2
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RT1075-2XJ46-0LA2
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT1075-2XJ46-0LA2&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RT1075-2XJ46-0LA2/char
3RT10752XJ460LA2
Page 5/6
7/8/2022
Subject to change without notice
© Copyright Siemens
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RT1075-2XJ46-0LA2&objecttype=14&gridview=view1
last modified:
3RT10752XJ460LA2
Page 6/6
3/26/2022
7/8/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RT10752XJ460LA2”相匹配的价格&库存,您可以联系我们找货