Data sheet
3RT2015-1AP02
power contactor, AC-3e/AC-3, 7 A, 3 kW / 400 V, 3-pole, 230 V AC, 50/60 Hz,
auxiliary contacts: 1 NC, screw terminal, size: S00
product brand name
SIRIUS
product designation
Power contactor
product type designation
3RT2
General technical data
size of contactor
S00
product extension
● function module for communication
No
● auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
0.6 W
● at AC in hot operating state per pole
0.2 W
● without load current share typical
1.1 W
type of calculation of power loss depending on pole
quadratic
insulation voltage
● of main circuit with degree of pollution 3 rated value
690 V
● of auxiliary circuit with degree of pollution 3 rated value
690 V
surge voltage resistance
● of main circuit rated value
6 kV
● of auxiliary circuit rated value
6 kV
maximum permissible voltage for protective separation between
coil and main contacts according to EN 60947-1
400 V
shock resistance at rectangular impulse
● at AC
6,7g / 5 ms, 4,2g / 10 ms
shock resistance with sine pulse
● at AC
10,5g / 5 ms, 6,6g / 10 ms
mechanical service life (operating cycles)
● of contactor typical
30 000 000
● of the contactor with added electronically optimized
auxiliary switch block typical
5 000 000
● of the contactor with added auxiliary switch block typical
10 000 000
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
10/01/2009
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-25 ... +60 °C
● during storage
-55 ... +80 °C
relative humidity minimum
10 %
relative humidity at 55 °C according to IEC 60068-2-30
maximum
95 %
Environmental footprint
3RT20151AP02
Page 1/9
5/22/2024
Subject to change without notice
© Copyright Siemens
Environmental Product Declaration(EPD)
Yes
Global Warming Potential [CO2 eq] total
39.6 kg
Global Warming Potential [CO2 eq] during manufacturing
1.18 kg
Global Warming Potential [CO2 eq] during operation
38.5 kg
Global Warming Potential [CO2 eq] after end of life
-0.155 kg
Main circuit
number of poles for main current circuit
3
number of NO contacts for main contacts
3
operating voltage
● at AC-3 rated value maximum
690 V
● at AC-3e rated value maximum
690 V
operational current
● at AC-1 at 400 V at ambient temperature 40 °C rated
value
18 A
● at AC-1
— up to 690 V at ambient temperature 40 °C rated
value
18 A
— up to 690 V at ambient temperature 60 °C rated
value
16 A
● at AC-3
— at 400 V rated value
7A
— at 500 V rated value
6A
— at 690 V rated value
4.9 A
● at AC-3e
— at 400 V rated value
7A
— at 500 V rated value
6A
— at 690 V rated value
4.9 A
● at AC-4 at 400 V rated value
6.5 A
● at AC-5a up to 690 V rated value
15.8 A
● at AC-5b up to 400 V rated value
5.8 A
● at AC-6a
— up to 230 V for current peak value n=20 rated value
4A
— up to 400 V for current peak value n=20 rated value
4A
— up to 500 V for current peak value n=20 rated value
3.8 A
— up to 690 V for current peak value n=20 rated value
3.6 A
● at AC-6a
— up to 230 V for current peak value n=30 rated value
2.7 A
— up to 400 V for current peak value n=30 rated value
2.7 A
— up to 500 V for current peak value n=30 rated value
2.5 A
— up to 690 V for current peak value n=30 rated value
2.4 A
minimum cross-section in main circuit at maximum AC-1 rated
value
2.5 mm²
operational current for approx. 200000 operating cycles at
AC-4
● at 400 V rated value
2.6 A
● at 690 V rated value
1.8 A
operational current
● at 1 current path at DC-1
— at 24 V rated value
15 A
— at 60 V rated value
15 A
— at 110 V rated value
1.5 A
— at 220 V rated value
0.6 A
— at 440 V rated value
0.42 A
— at 600 V rated value
0.42 A
● with 2 current paths in series at DC-1
— at 24 V rated value
15 A
— at 60 V rated value
15 A
— at 110 V rated value
8.4 A
— at 220 V rated value
1.2 A
— at 440 V rated value
0.6 A
— at 600 V rated value
0.5 A
● with 3 current paths in series at DC-1
3RT20151AP02
Page 2/9
5/22/2024
Subject to change without notice
© Copyright Siemens
— at 24 V rated value
15 A
— at 60 V rated value
15 A
— at 110 V rated value
15 A
— at 220 V rated value
15 A
— at 440 V rated value
0.9 A
— at 600 V rated value
0.7 A
● at 1 current path at DC-3 at DC-5
— at 24 V rated value
15 A
— at 60 V rated value
0.35 A
— at 110 V rated value
0.1 A
● with 2 current paths in series at DC-3 at DC-5
— at 24 V rated value
15 A
— at 60 V rated value
3.5 A
— at 110 V rated value
0.25 A
● with 3 current paths in series at DC-3 at DC-5
— at 24 V rated value
15 A
— at 60 V rated value
15 A
— at 110 V rated value
15 A
— at 220 V rated value
1.2 A
— at 440 V rated value
0.14 A
— at 600 V rated value
0.14 A
operating power
● at AC-3
— at 230 V rated value
1.5 kW
— at 400 V rated value
3 kW
— at 500 V rated value
3 kW
— at 690 V rated value
4 kW
● at AC-3e
— at 230 V rated value
1.5 kW
— at 400 V rated value
3 kW
— at 500 V rated value
3 kW
— at 690 V rated value
4 kW
operating power for approx. 200000 operating cycles at AC4
● at 400 V rated value
1.15 kW
● at 690 V rated value
1.15 kW
operating apparent power at AC-6a
● up to 230 V for current peak value n=20 rated value
1.5 kVA
● up to 400 V for current peak value n=20 rated value
2.7 kVA
● up to 500 V for current peak value n=20 rated value
3.3 kVA
● up to 690 V for current peak value n=20 rated value
4.3 kVA
operating apparent power at AC-6a
● up to 230 V for current peak value n=30 rated value
1 kVA
● up to 400 V for current peak value n=30 rated value
1.8 kVA
● up to 500 V for current peak value n=30 rated value
2.2 kVA
● up to 690 V for current peak value n=30 rated value
2.9 kVA
short-time withstand current in cold operating state up to
40 °C
● limited to 1 s switching at zero current maximum
120 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 5 s switching at zero current maximum
86 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 10 s switching at zero current maximum
67 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 30 s switching at zero current maximum
52 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 60 s switching at zero current maximum
43 A; Use minimum cross-section acc. to AC-1 rated value
no-load switching frequency
● at AC
10 000 1/h
operating frequency
● at AC-1 maximum
1 000 1/h
● at AC-2 maximum
750 1/h
● at AC-3 maximum
750 1/h
● at AC-3e maximum
750 1/h
● at AC-4 maximum
250 1/h
3RT20151AP02
Page 3/9
5/22/2024
Subject to change without notice
© Copyright Siemens
Control circuit/ Control
type of voltage of the control supply voltage
AC
control supply voltage at AC
● at 50 Hz rated value
230 V
● at 60 Hz rated value
230 V
operating range factor control supply voltage rated value of
magnet coil at AC
● at 50 Hz
0.8 ... 1.1
● at 60 Hz
0.85 ... 1.1
apparent pick-up power of magnet coil at AC
● at 50 Hz
27 VA
● at 60 Hz
24.3 VA
inductive power factor with closing power of the coil
● at 50 Hz
0.8
● at 60 Hz
0.75
apparent holding power of magnet coil at AC
● at 50 Hz
4.2 VA
● at 60 Hz
3.3 VA
inductive power factor with the holding power of the coil
● at 50 Hz
0.25
● at 60 Hz
0.25
closing delay
● at AC
9 ... 35 ms
opening delay
● at AC
4 ... 15 ms
arcing time
10 ... 15 ms
control version of the switch operating mechanism
Standard A1 - A2
Auxiliary circuit
number of NC contacts for auxiliary contacts instantaneous
contact
1
operational current at AC-12 maximum
10 A
operational current at AC-15
● at 230 V rated value
10 A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
operational current at DC-12
● at 24 V rated value
10 A
● at 48 V rated value
6A
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 125 V rated value
2A
● at 220 V rated value
1A
● at 600 V rated value
0.15 A
operational current at DC-13
● at 24 V rated value
10 A
● at 48 V rated value
2A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 125 V rated value
0.9 A
● at 220 V rated value
0.3 A
● at 600 V rated value
0.1 A
contact reliability of auxiliary contacts
1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
4.8 A
● at 600 V rated value
6.1 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
0.25 hp
— at 230 V rated value
0.75 hp
3RT20151AP02
Page 4/9
5/22/2024
Subject to change without notice
© Copyright Siemens
● for 3-phase AC motor
— at 200/208 V rated value
1.5 hp
— at 220/230 V rated value
2 hp
— at 460/480 V rated value
3 hp
— at 575/600 V rated value
5 hp
contact rating of auxiliary contacts according to UL
A600 / Q600
Short-circuit protection
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
— with type of assignment 2 required
gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
● for short-circuit protection of the auxiliary switch required
gG: 10 A (500 V, 1 kA)
Installation/ mounting/ dimensions
mounting position
+/-180° rotation possible on vertical mounting surface; can be tilted forward and
backward by +/- 22.5° on vertical mounting surface
fastening method
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
height
58 mm
width
45 mm
depth
73 mm
required spacing
● with side-by-side mounting
— forwards
10 mm
— upwards
10 mm
— downwards
10 mm
— at the side
0 mm
● for grounded parts
— forwards
10 mm
— upwards
10 mm
— at the side
6 mm
— downwards
10 mm
● for live parts
— forwards
10 mm
— upwards
10 mm
— downwards
10 mm
— at the side
6 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
screw-type terminals
● at contactor for auxiliary contacts
Screw-type terminals
● of magnet coil
Screw-type terminals
type of connectable conductor cross-sections
● for main contacts
— solid
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
— solid or stranded
2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x 4 mm²
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● for AWG cables for main contacts
2x (20 ... 16), 2x (18 ... 14), 2x 12
connectable conductor cross-section for main contacts
● solid
0.5 ... 4 mm²
● stranded
0.5 ... 4 mm²
● finely stranded with core end processing
0.5 ... 2.5 mm²
connectable conductor cross-section for auxiliary contacts
● solid or stranded
0.5 ... 4 mm²
● finely stranded with core end processing
0.5 ... 2.5 mm²
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● for AWG cables for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14), 2x 12
AWG number as coded connectable conductor cross
section
3RT20151AP02
Page 5/9
5/22/2024
Subject to change without notice
© Copyright Siemens
● for main contacts
20 ... 12
● for auxiliary contacts
20 ... 12
Safety related data
product function
● mirror contact according to IEC 60947-4-1
Yes
suitability for use safety-related switching OFF
Yes; applies only to contactor operating mechanism
proportion of dangerous failures
● with low demand rate according to SN 31920
40 %
● with high demand rate according to SN 31920
73 %
B10 value with high demand rate according to SN 31920
1 000 000
failure rate [FIT] with low demand rate according to SN
31920
100 FIT
IEC 61508
T1 value
● for proof test interval or service life according to IEC
61508
20 a
Electrical Safety
protection class IP on the front according to IEC 60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
Approvals Certificates
General Product Approval
Confirmation
General Product Approval
EMV
Functional Saftey
KC
Type Examination Certificate
Test Certificates
Type Test Certificates/Test Report
Special Test Certificate
Marine / Shipping
Marine / Shipping
other
Miscellaneous
Railway
Confirmation
Confirmation
Environment
Special Test Certificate
Environment
Environmental Confirmations
Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT2015-1AP02
3RT20151AP02
Page 6/9
5/22/2024
Subject to change without notice
© Copyright Siemens
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT2015-1AP02
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RT2015-1AP02
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT2015-1AP02&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RT2015-1AP02/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RT2015-1AP02&objecttype=14&gridview=view1
3RT20151AP02
Page 7/9
5/22/2024
Subject to change without notice
© Copyright Siemens
3RT20151AP02
Page 8/9
5/22/2024
Subject to change without notice
© Copyright Siemens
5/L3
6/T3
21
3/L2
1/L1
2/T1
4/T2
A1
A2
last modified:
3RT20151AP02
Page 9/9
22
-Q
3/15/2024
5/22/2024
Subject to change without notice
© Copyright Siemens