Data sheet
3RT2017-1BB41
power contactor, AC-3e/AC-3, 12 A, 5.5 kW / 400 V, 3-pole, 24 V DC, auxiliary
contacts: 1 NO, screw terminal, size: S00
product brand name
SIRIUS
product designation
Power contactor
product type designation
3RT2
General technical data
size of contactor
S00
product extension
● function module for communication
No
● auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
1.5 W
● at AC in hot operating state per pole
0.5 W
● without load current share typical
4W
type of calculation of power loss depending on pole
quadratic
insulation voltage
● of main circuit with degree of pollution 3 rated value
690 V
● of auxiliary circuit with degree of pollution 3 rated value
690 V
surge voltage resistance
● of main circuit rated value
6 kV
● of auxiliary circuit rated value
6 kV
maximum permissible voltage for protective separation between
coil and main contacts according to EN 60947-1
400 V
shock resistance at rectangular impulse
● at DC
7.3g / 5 ms, 4.7g / 10 ms
shock resistance with sine pulse
● at DC
11,4g / 5 ms, 7,3g / 10 ms
mechanical service life (operating cycles)
● of contactor typical
30 000 000
● of the contactor with added electronically optimized
auxiliary switch block typical
5 000 000
● of the contactor with added auxiliary switch block typical
10 000 000
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
10/01/2009
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-25 ... +60 °C
● during storage
-55 ... +80 °C
relative humidity minimum
10 %
relative humidity at 55 °C according to IEC 60068-2-30
maximum
95 %
Environmental footprint
3RT20171BB41
Page 1/8
4/18/2024
Subject to change without notice
© Copyright Siemens
Environmental Product Declaration(EPD)
Yes
Global Warming Potential [CO2 eq] total
153 kg
Global Warming Potential [CO2 eq] during manufacturing
1.42 kg
Global Warming Potential [CO2 eq] during operation
152 kg
Global Warming Potential [CO2 eq] after end of life
-0.305 kg
Main circuit
number of poles for main current circuit
3
number of NO contacts for main contacts
3
operating voltage
● at AC-3 rated value maximum
690 V
● at AC-3e rated value maximum
690 V
operational current
● at AC-1 at 400 V at ambient temperature 40 °C rated
value
22 A
● at AC-1
— up to 690 V at ambient temperature 40 °C rated
value
22 A
— up to 690 V at ambient temperature 60 °C rated
value
20 A
● at AC-3
— at 400 V rated value
12 A
— at 500 V rated value
9.2 A
— at 690 V rated value
6.7 A
● at AC-3e
— at 400 V rated value
12 A
— at 500 V rated value
9.2 A
— at 690 V rated value
6.7 A
● at AC-4 at 400 V rated value
8.5 A
● at AC-5a up to 690 V rated value
19.4 A
● at AC-5b up to 400 V rated value
9.9 A
● at AC-6a
— up to 230 V for current peak value n=20 rated value
7.2 A
— up to 400 V for current peak value n=20 rated value
7.2 A
— up to 500 V for current peak value n=20 rated value
7.2 A
— up to 690 V for current peak value n=20 rated value
6.7 A
● at AC-6a
— up to 230 V for current peak value n=30 rated value
4.8 A
— up to 400 V for current peak value n=30 rated value
4.8 A
— up to 500 V for current peak value n=30 rated value
4.8 A
— up to 690 V for current peak value n=30 rated value
4.8 A
minimum cross-section in main circuit at maximum AC-1 rated
value
4 mm²
operational current for approx. 200000 operating cycles at
AC-4
● at 400 V rated value
4.1 A
● at 690 V rated value
3.3 A
operational current
● at 1 current path at DC-1
— at 24 V rated value
20 A
— at 60 V rated value
20 A
— at 110 V rated value
2.1 A
— at 220 V rated value
0.8 A
— at 440 V rated value
0.6 A
— at 600 V rated value
0.6 A
● with 2 current paths in series at DC-1
— at 24 V rated value
20 A
— at 60 V rated value
20 A
— at 110 V rated value
12 A
— at 220 V rated value
1.6 A
— at 440 V rated value
0.8 A
— at 600 V rated value
0.7 A
● with 3 current paths in series at DC-1
3RT20171BB41
Page 2/8
4/18/2024
Subject to change without notice
© Copyright Siemens
— at 24 V rated value
20 A
— at 60 V rated value
20 A
— at 110 V rated value
20 A
— at 220 V rated value
20 A
— at 440 V rated value
1.3 A
— at 600 V rated value
1A
● at 1 current path at DC-3 at DC-5
— at 24 V rated value
20 A
— at 60 V rated value
0.5 A
— at 110 V rated value
0.15 A
● with 2 current paths in series at DC-3 at DC-5
— at 24 V rated value
20 A
— at 60 V rated value
5A
— at 110 V rated value
0.35 A
● with 3 current paths in series at DC-3 at DC-5
— at 24 V rated value
20 A
— at 60 V rated value
20 A
— at 110 V rated value
20 A
— at 220 V rated value
1.5 A
— at 440 V rated value
0.2 A
— at 600 V rated value
0.2 A
operating power
● at AC-3
— at 230 V rated value
3 kW
— at 400 V rated value
5.5 kW
— at 500 V rated value
5.5 kW
— at 690 V rated value
5.5 kW
● at AC-3e
— at 230 V rated value
3 kW
— at 400 V rated value
5.5 kW
— at 500 V rated value
5.5 kW
— at 690 V rated value
5.5 kW
operating power for approx. 200000 operating cycles at AC4
● at 400 V rated value
2 kW
● at 690 V rated value
2.5 kW
operating apparent power at AC-6a
● up to 230 V for current peak value n=20 rated value
2.8 kVA
● up to 400 V for current peak value n=20 rated value
4.9 kVA
● up to 500 V for current peak value n=20 rated value
6.2 kVA
● up to 690 V for current peak value n=20 rated value
8 kVA
operating apparent power at AC-6a
● up to 230 V for current peak value n=30 rated value
1.9 kVA
● up to 400 V for current peak value n=30 rated value
3.3 kVA
● up to 500 V for current peak value n=30 rated value
4.1 kVA
● up to 690 V for current peak value n=30 rated value
5.7 kVA
short-time withstand current in cold operating state up to
40 °C
● limited to 1 s switching at zero current maximum
200 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 5 s switching at zero current maximum
123 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 10 s switching at zero current maximum
96 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 30 s switching at zero current maximum
74 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 60 s switching at zero current maximum
61 A; Use minimum cross-section acc. to AC-1 rated value
no-load switching frequency
● at DC
10 000 1/h
operating frequency
● at AC-1 maximum
1 000 1/h
● at AC-2 maximum
750 1/h
● at AC-3 maximum
750 1/h
● at AC-3e maximum
750 1/h
● at AC-4 maximum
250 1/h
3RT20171BB41
Page 3/8
4/18/2024
Subject to change without notice
© Copyright Siemens
Control circuit/ Control
type of voltage of the control supply voltage
DC
control supply voltage at DC rated value
●
24 V
operating range factor control supply voltage rated value of
magnet coil at DC
● initial value
0.8
● full-scale value
1.1
closing power of magnet coil at DC
4W
holding power of magnet coil at DC
4W
closing delay
● at DC
30 ... 100 ms
opening delay
● at DC
7 ... 13 ms
arcing time
10 ... 15 ms
control version of the switch operating mechanism
Standard A1 - A2
Auxiliary circuit
number of NO contacts for auxiliary contacts instantaneous
contact
1
operational current at AC-12 maximum
10 A
operational current at AC-15
● at 230 V rated value
10 A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
operational current at DC-12
● at 24 V rated value
10 A
● at 48 V rated value
6A
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 125 V rated value
2A
● at 220 V rated value
1A
● at 600 V rated value
0.15 A
operational current at DC-13
● at 24 V rated value
10 A
● at 48 V rated value
2A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 125 V rated value
0.9 A
● at 220 V rated value
0.3 A
● at 600 V rated value
0.1 A
contact reliability of auxiliary contacts
1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
11 A
● at 600 V rated value
11 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
0.5 hp
— at 230 V rated value
2 hp
● for 3-phase AC motor
— at 200/208 V rated value
3 hp
— at 220/230 V rated value
3 hp
— at 460/480 V rated value
7.5 hp
— at 575/600 V rated value
10 hp
contact rating of auxiliary contacts according to UL
A600 / Q600
Short-circuit protection
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 50A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
— with type of assignment 2 required
gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
3RT20171BB41
Page 4/8
4/18/2024
Subject to change without notice
© Copyright Siemens
● for short-circuit protection of the auxiliary switch required
gG: 10 A (500 V, 1 kA)
Installation/ mounting/ dimensions
mounting position
+/-180° rotation possible on vertical mounting surface; can be tilted forward and
backward by +/- 22.5° on vertical mounting surface
fastening method
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
height
58 mm
width
45 mm
depth
73 mm
required spacing
● with side-by-side mounting
— forwards
10 mm
— upwards
10 mm
— downwards
10 mm
— at the side
0 mm
● for grounded parts
— forwards
10 mm
— upwards
10 mm
— at the side
6 mm
— downwards
10 mm
● for live parts
— forwards
10 mm
— upwards
10 mm
— downwards
10 mm
— at the side
6 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
screw-type terminals
● at contactor for auxiliary contacts
Screw-type terminals
● of magnet coil
Screw-type terminals
type of connectable conductor cross-sections
● for main contacts
— solid
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
— solid or stranded
2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x 4 mm²
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● for AWG cables for main contacts
2x (20 ... 16), 2x (18 ... 14), 2x 12
connectable conductor cross-section for main contacts
● solid
0.5 ... 4 mm²
● stranded
0.5 ... 4 mm²
● finely stranded with core end processing
0.5 ... 2.5 mm²
connectable conductor cross-section for auxiliary contacts
● solid or stranded
0.5 ... 4 mm²
● finely stranded with core end processing
0.5 ... 2.5 mm²
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● for AWG cables for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14), 2x 12
AWG number as coded connectable conductor cross
section
● for main contacts
20 ... 12
● for auxiliary contacts
20 ... 12
Safety related data
product function
● mirror contact according to IEC 60947-4-1
suitability for use safety-related switching OFF
Yes; with 3RH29
Yes; applies only to contactor operating mechanism
proportion of dangerous failures
● with low demand rate according to SN 31920
40 %
● with high demand rate according to SN 31920
73 %
B10 value with high demand rate according to SN 31920
1 000 000
failure rate [FIT] with low demand rate according to SN
100 FIT
3RT20171BB41
Page 5/8
4/18/2024
Subject to change without notice
© Copyright Siemens
31920
IEC 61508
T1 value
● for proof test interval or service life according to IEC
61508
20 a
Electrical Safety
protection class IP on the front according to IEC 60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
Approvals Certificates
General Product Approval
Confirmation
General Product Approval
EMV
Functional Saftey
KC
Test Certificates
Type Examination Certificate
Test Certificates
Special Test Certificate
Type Test Certificates/Test Report
Marine / Shipping
Miscellaneous
Marine / Shipping
other
Miscellaneous
Confirmation
Railway
Dangerous Good
Special Test Certificate
Transport Information
Environment
Environmental Confirmations
Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT2017-1BB41
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT2017-1BB41
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RT2017-1BB41
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT2017-1BB41&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RT2017-1BB41/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RT2017-1BB41&objecttype=14&gridview=view1
3RT20171BB41
Page 6/8
4/18/2024
Subject to change without notice
© Copyright Siemens
3RT20171BB41
Page 7/8
4/18/2024
Subject to change without notice
© Copyright Siemens
5/L3
6/T3
13
3/L2
4/T2
1/L1
A1 (+)
last modified:
3RT20171BB41
Page 8/8
14
2/T1
A2
-Q
3/15/2024
4/18/2024
Subject to change without notice
© Copyright Siemens