Data sheet
3RT2025-2KB40
power contactor, AC-3 17 A, 7.5 kW / 400 V 1 NO + 1 NC, 24 V DC with
integrated varistor 3-pole, size S0, spring-type terminal suitable for PLC
outputs not expandable with auxiliary switch
product brand name
SIRIUS
product designation
Coupling contactor
product type designation
3RT2
General technical data
size of contactor
S0
product extension
● function module for communication
No
● auxiliary switch
No
power loss [W] for rated value of the current
● at AC in hot operating state
1.8 W
● at AC in hot operating state per pole
0.6 W
● without load current share typical
4.5 W
insulation voltage
● of main circuit with degree of pollution 3 rated value
690 V
● of auxiliary circuit with degree of pollution 3 rated
value
690 V
surge voltage resistance
● of main circuit rated value
6 kV
● of auxiliary circuit rated value
6 kV
maximum permissible voltage for safe isolation between
coil and main contacts according to EN 60947-1
400 V
shock resistance at rectangular impulse
● at DC
10g / 5 ms, 7,5g / 10 ms
shock resistance with sine pulse
● at DC
15g / 5 ms, 10g / 10 ms
mechanical service life (switching cycles)
● of contactor typical
10 000 000
● of the contactor with added electronically optimized
auxiliary switch block typical
5 000 000
● of the contactor with added auxiliary switch block
typical
10 000 000
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
10/01/2009
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-25 ... +60 °C
● during storage
-55 ... +80 °C
relative humidity minimum
10 %
relative humidity at 55 °C according to IEC 60068-2-30
maximum
95 %
3RT20252KB40
Page 1/8
7/8/2022
Subject to change without notice
© Copyright Siemens
Main circuit
number of poles for main current circuit
3
number of NO contacts for main contacts
3
operating voltage
● at AC-3 rated value maximum
690 V
● at AC-3e rated value maximum
690 V
operational current
● at AC-1 at 400 V at ambient temperature 40 °C
rated value
40 A
● at AC-1
— up to 690 V at ambient temperature 40 °C
rated value
40 A
— up to 690 V at ambient temperature 60 °C
rated value
35 A
● at AC-3
— at 400 V rated value
17 A
— at 500 V rated value
17 A
— at 690 V rated value
13 A
● at AC-3e
— at 400 V rated value
17 A
— at 500 V rated value
17 A
— at 690 V rated value
13 A
● at AC-4 at 400 V rated value
15.5 A
● at AC-5a up to 690 V rated value
35.2 A
● at AC-5b up to 400 V rated value
14.1 A
● at AC-6a
— up to 230 V for current peak value n=20 rated
value
11.4 A
— up to 400 V for current peak value n=20 rated
value
11.4 A
— up to 500 V for current peak value n=20 rated
value
11.4 A
— up to 690 V for current peak value n=20 rated
value
11.3 A
● at AC-6a
— up to 230 V for current peak value n=30 rated
value
7.6 A
— up to 400 V for current peak value n=30 rated
value
7.6 A
— up to 500 V for current peak value n=30 rated
value
7.6 A
— up to 690 V for current peak value n=30 rated
value
7.6 A
minimum cross-section in main circuit at maximum AC-1
rated value
10 mm²
operational current for approx. 200000 operating
cycles at AC-4
● at 400 V rated value
7.7 A
● at 690 V rated value
7.7 A
operational current
● at 1 current path at DC-1
— at 24 V rated value
35 A
— at 110 V rated value
4.5 A
— at 220 V rated value
1A
— at 440 V rated value
0.4 A
— at 600 V rated value
0.25 A
● with 2 current paths in series at DC-1
— at 24 V rated value
35 A
— at 110 V rated value
35 A
— at 220 V rated value
5A
— at 440 V rated value
1A
— at 600 V rated value
0.8 A
● with 3 current paths in series at DC-1
3RT20252KB40
Page 2/8
7/8/2022
Subject to change without notice
© Copyright Siemens
— at 24 V rated value
35 A
— at 110 V rated value
35 A
— at 220 V rated value
35 A
— at 440 V rated value
2.9 A
— at 600 V rated value
1.4 A
● at 1 current path at DC-3 at DC-5
— at 24 V rated value
20 A
— at 110 V rated value
2.5 A
— at 220 V rated value
1A
— at 440 V rated value
0.09 A
— at 600 V rated value
0.06 A
● with 2 current paths in series at DC-3 at DC-5
— at 24 V rated value
35 A
— at 110 V rated value
15 A
— at 220 V rated value
3A
— at 440 V rated value
0.27 A
— at 600 V rated value
0.16 A
● with 3 current paths in series at DC-3 at DC-5
— at 24 V rated value
35 A
— at 110 V rated value
35 A
— at 220 V rated value
10 A
— at 440 V rated value
0.6 A
— at 600 V rated value
0.6 A
operating power
● at AC-3
— at 230 V rated value
4 kW
— at 400 V rated value
7.5 kW
— at 500 V rated value
7.5 kW
— at 690 V rated value
11 kW
● at AC-3e
— at 230 V rated value
4 kW
— at 400 V rated value
4.5 kW
— at 500 V rated value
7.5 kW
— at 690 V rated value
11 kW
operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value
3.5 kW
● at 690 V rated value
6 kW
operating apparent power at AC-6a
● up to 230 V for current peak value n=20 rated value
4.5 kVA
● up to 400 V for current peak value n=20 rated value
7.8 kVA
● up to 500 V for current peak value n=20 rated value
9.9 kVA
● up to 690 V for current peak value n=20 rated value
13.6 kVA
operating apparent power at AC-6a
● up to 230 V for current peak value n=30 rated value
3 kVA
● up to 400 V for current peak value n=30 rated value
5.2 kVA
● up to 500 V for current peak value n=30 rated value
6.6 kVA
● up to 690 V for current peak value n=30 rated value
9.1 kVA
short-time withstand current in cold operating state
up to 40 °C
● limited to 1 s switching at zero current maximum
225 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 5 s switching at zero current maximum
225 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 10 s switching at zero current maximum
180 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 30 s switching at zero current maximum
115 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 60 s switching at zero current maximum
96 A; Use minimum cross-section acc. to AC-1 rated value
no-load switching frequency
● at DC
1 500 1/h
operating frequency
● at AC-1 maximum
1 000 1/h
● at AC-2 maximum
1 000 1/h
● at AC-3 maximum
1 000 1/h
3RT20252KB40
Page 3/8
7/8/2022
Subject to change without notice
© Copyright Siemens
● at AC-3e maximum
1 000 1/h
● at AC-4 maximum
300 1/h
Control circuit/ Control
type of voltage of the control supply voltage
DC
control supply voltage at DC
● rated value
24 V
operating range factor control supply voltage rated
value of magnet coil at DC
● initial value
0.7
● full-scale value
1.25
design of the surge suppressor
with varistor
closing power of magnet coil at DC
4.5 W
holding power of magnet coil at DC
4.5 W
closing delay
● at DC
52 ... 270 ms
opening delay
● at DC
19 ... 21 ms
arcing time
10 ... 10 ms
control version of the switch operating mechanism
Standard A1 - A2
Auxiliary circuit
number of NC contacts for auxiliary contacts
instantaneous contact
1
number of NO contacts for auxiliary contacts
instantaneous contact
1
operational current at AC-12 maximum
10 A
operational current at AC-15
● at 230 V rated value
10 A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
operational current at DC-12
● at 24 V rated value
10 A
● at 48 V rated value
6A
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 125 V rated value
2A
● at 220 V rated value
1A
● at 600 V rated value
0.15 A
operational current at DC-13
● at 24 V rated value
10 A
● at 48 V rated value
2A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 125 V rated value
0.9 A
● at 220 V rated value
0.3 A
● at 600 V rated value
0.1 A
contact reliability of auxiliary contacts
1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
14 A
● at 600 V rated value
17 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
1 hp
— at 230 V rated value
3 hp
● for 3-phase AC motor
— at 200/208 V rated value
3 hp
— at 220/230 V rated value
5 hp
— at 460/480 V rated value
10 hp
— at 575/600 V rated value
15 hp
3RT20252KB40
Page 4/8
7/8/2022
Subject to change without notice
© Copyright Siemens
contact rating of auxiliary contacts according to UL
A600 / P600
Short-circuit protection
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 63A (690V,100kA), aM: 32A (690V,100kA), BS88: 63A (415V,80kA)
— with type of assignment 2 required
gG: 25A (690V,100kA), aM: 20A (690V,100kA), BS88: 25A (415V,80kA)
● for short-circuit protection of the auxiliary switch
required
gG: 10 A (500 V, 1 kA)
Installation/ mounting/ dimensions
mounting position
+/-180° rotation possible on vertical mounting surface; can be tilted
forward and backward by +/- 22.5° on vertical mounting surface
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
● side-by-side mounting
Yes
height
102 mm
width
45 mm
depth
107 mm
required spacing
● with side-by-side mounting
— forwards
10 mm
— upwards
10 mm
— downwards
10 mm
— at the side
0 mm
● for grounded parts
— forwards
10 mm
— upwards
10 mm
— at the side
6 mm
— downwards
10 mm
● for live parts
— forwards
10 mm
— upwards
10 mm
— downwards
10 mm
— at the side
6 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
spring-loaded terminals
● for auxiliary and control circuit
spring-loaded terminals
● at contactor for auxiliary contacts
Spring-type terminals
● of magnet coil
Spring-type terminals
type of connectable conductor cross-sections
● for main contacts
— solid
2x (1 ... 10 mm²)
— solid or stranded
2x (1 ... 10 mm²)
— finely stranded with core end processing
2x (1 ... 6 mm²)
— finely stranded without core end processing
2x (1 ... 6 mm²)
● at AWG cables for main contacts
2x (18 ... 8)
connectable conductor cross-section for main
contacts
● solid
1 ... 10 mm²
● stranded
1 ... 10 mm²
● finely stranded with core end processing
1 ... 6 mm²
● finely stranded without core end processing
1 ... 6 mm²
connectable conductor cross-section for auxiliary
contacts
● solid or stranded
0.5 ... 2.5 mm²
● finely stranded with core end processing
0.5 ... 1.5 mm²
● finely stranded without core end processing
0.5 ... 2.5 mm²
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded
2x (0.5 ... 2.5 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²)
3RT20252KB40
Page 5/8
7/8/2022
Subject to change without notice
© Copyright Siemens
— finely stranded without core end processing
2x (0.5 ... 2.5 mm²)
● at AWG cables for auxiliary contacts
2x (20 ... 14)
AWG number as coded connectable conductor cross
section
● for main contacts
18 ... 8
● for auxiliary contacts
20 ... 14
Safety related data
product function
● mirror contact according to IEC 60947-4-1
Yes
B10 value with high demand rate according to SN 31920
450 000
proportion of dangerous failures
● with low demand rate according to SN 31920
40 %
● with high demand rate according to SN 31920
73 %
failure rate [FIT] with low demand rate according to SN
31920
100 FIT
T1 value for proof test interval or service life according to
IEC 61508
20 y
protection class IP on the front according to IEC
60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
suitability for use
● safety-related switching OFF
Yes
Certificates/ approvals
General Product Approval
Confirmation
EMC
Functional
Safety/Safety of
Machinery
Declaration of Conformity
Type Examination
Certificate
Test Certificates
KC
Test Certificates
Special Test Certificate
Type Test Certificates/Test Report
Marine / Shipping
Miscellaneous
Marine / Shipping
other
Dangerous Good
Confirmation
Transport Information
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT2025-2KB40
Cax online generator
3RT20252KB40
Page 6/8
7/8/2022
Subject to change without notice
© Copyright Siemens
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT2025-2KB40
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RT2025-2KB40
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT2025-2KB40&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RT2025-2KB40/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RT2025-2KB40&objecttype=14&gridview=view1
3RT20252KB40
Page 7/8
7/8/2022
Subject to change without notice
© Copyright Siemens
5/L3
13
6/T3
14
21
3/L2
1/L1
2/T1
4/T2
A1 (+)
A2 (-)
-Q
last modified:
3RT20252KB40
Page 8/8
22
U
6/2/2022
7/8/2022
Subject to change without notice