Data sheet
3RT2026-4XB40-0LA2
Traction contactor, AC-3 25 A, 11 kW / 400 V 1 NO + 1 NC with electronic
drive 24 V DC, 0.7-1.25* US, with integrated varistor, 3-pole, Size S0, ring
cable lug connection
product brand name
SIRIUS
product designation
Contactor
design of the product
With extended operating range
product type designation
3RT2
General technical data
size of contactor
S0
product extension
● function module for communication
No
● auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
4.8 W
● at AC in hot operating state per pole
1.6 W
● without load current share typical
0.8 W
insulation voltage
● of main circuit with degree of pollution 3 rated value
690 V
● of auxiliary circuit with degree of pollution 3 rated
value
690 V
surge voltage resistance
● of main circuit rated value
6 kV
● of auxiliary circuit rated value
6 kV
maximum permissible voltage for safe isolation between
coil and main contacts according to EN 60947-1
400 V
shock resistance at rectangular impulse
● at DC
10g / 5 ms, 7,5g / 10 ms
shock resistance with sine pulse
● at DC
15g / 5 ms, 10g / 10 ms
mechanical service life (switching cycles)
● of contactor typical
10 000 000
● of the contactor with added electronically optimized
auxiliary switch block typical
5 000 000
● of the contactor with added auxiliary switch block
typical
10 000 000
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
10/01/2009
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-40 ... +70 °C
● during storage
-55 ... +80 °C
relative humidity minimum
3RT20264XB400LA2
Page 1/6
10 %
7/4/2022
Subject to change without notice
© Copyright Siemens
relative humidity at 55 °C according to IEC 60068-2-30
maximum
95 %
Main circuit
number of poles for main current circuit
3
number of NO contacts for main contacts
3
operating voltage
● at AC-3 rated value maximum
690 V
● at AC-3e rated value maximum
690 V
operational current
● at AC-1 at 400 V at ambient temperature 40 °C
rated value
40 A
● at AC-1
— up to 690 V at ambient temperature 40 °C
rated value
40 A
— up to 690 V at ambient temperature 60 °C
rated value
35 A
● at AC-2 at 400 V rated value
25 A
● at AC-3
— at 400 V rated value
25 A
— at 500 V rated value
18 A
— at 690 V rated value
13 A
● at AC-3e
— at 400 V rated value
25 A
— at 500 V rated value
18 A
— at 690 V rated value
13 A
● at AC-4 at 400 V rated value
15.5 A
minimum cross-section in main circuit
● at maximum AC-1 rated value
10 mm²
● at maximum Ith rated value
10 mm²
operational current for approx. 200000 operating
cycles at AC-4
● at 400 V rated value
9A
● at 690 V rated value
9A
operating power
● at AC-2 at 400 V rated value
11 kW
● at AC-3
— at 230 V rated value
5.5 kW
— at 400 V rated value
11 kW
— at 500 V rated value
11 kW
— at 690 V rated value
11 kW
● at AC-3e
— at 230 V rated value
5.5 kW
— at 400 V rated value
11 kW
— at 500 V rated value
11 kW
— at 690 V rated value
11 kW
operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value
4.4 kW
● at 690 V rated value
7.7 kW
short-time withstand current in cold operating state
up to 40 °C
● limited to 1 s switching at zero current maximum
375 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 5 s switching at zero current maximum
299 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 10 s switching at zero current maximum
200 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 30 s switching at zero current maximum
128 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 60 s switching at zero current maximum
106 A; Use minimum cross-section acc. to AC-1 rated value
no-load switching frequency
● at DC
1 500 1/h
operating frequency
● at AC-1 maximum
750 1/h
● at AC-2 maximum
750 1/h
● at AC-3 maximum
750 1/h
3RT20264XB400LA2
Page 2/6
7/4/2022
Subject to change without notice
© Copyright Siemens
● at AC-3e maximum
750 1/h
● at AC-2 at AC-3e maximum
750 1/h
● at AC-4 maximum
250 1/h
Ratings for railway applications
thermal current (Ith) up to 690 V
● up to 40 °C according to IEC 60077 rated value
40 A
● up to 70 °C according to IEC 60077 rated value
30 A
Control circuit/ Control
type of voltage
DC
type of voltage of the control supply voltage
DC
control supply voltage at DC
● rated value
24 V
operating range factor control supply voltage rated
value of magnet coil at DC
● initial value
0.7
● full-scale value
1.25
design of the surge suppressor
with varistor
inrush current peak
3A
duration of inrush current peak
30 µs
locked-rotor current mean value
0.3 A
locked-rotor current peak
0.52 A
duration of locked-rotor current
180 ms
holding current mean value
45 mA
closing power of magnet coil at DC
6.7 W
holding power of magnet coil at DC
1.4 W
closing delay
● at DC
50 ... 75 ms
opening delay
● at DC
30 ... 50 ms
arcing time
10 ... 10 ms
control version of the switch operating mechanism
Standard A1 - A2
Auxiliary circuit
number of NC contacts for auxiliary contacts
● instantaneous contact
number of NO contacts for auxiliary contacts
● instantaneous contact
operational current at AC-12 maximum
1
1
1
1
10 A
operational current at AC-15
● at 230 V rated value
10 A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
operational current at DC-12
● at 24 V rated value
10 A
● at 48 V rated value
6A
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 125 V rated value
2A
● at 220 V rated value
1A
● at 600 V rated value
0.15 A
operational current at DC-13
● at 24 V rated value
10 A
● at 48 V rated value
2A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 125 V rated value
0.9 A
● at 220 V rated value
0.3 A
● at 600 V rated value
0.1 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
3RT20264XB400LA2
Page 3/6
7/4/2022
Subject to change without notice
© Copyright Siemens
● at 480 V rated value
21 A
● at 600 V rated value
22 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
2 hp
— at 230 V rated value
3 hp
● for 3-phase AC motor
— at 200/208 V rated value
5 hp
— at 220/230 V rated value
7.5 hp
— at 460/480 V rated value
15 hp
— at 575/600 V rated value
20 hp
contact rating of auxiliary contacts according to UL
A600 / Q600
Short-circuit protection
product function short circuit protection
No
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 100 A (690 V, 100 kA), aM: 50 A (690 V, 100 kA), BS88: 100 A (415
V, 80 kA)
— with type of assignment 2 required
gG: 35A (690V, 100kA), aM: 20A (690V, 100kA), BS88: 35A (415V,
80kA)
● for short-circuit protection of the auxiliary switch
required
gG: 10 A (500 V, 1 kA)
Installation/ mounting/ dimensions
mounting position
+/-180° rotation possible on vertical mounting surface; can be tilted
forward and backward by +/- 22.5° on vertical mounting surface
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
● side-by-side mounting
Yes
height
91 mm
width
45 mm
depth
107 mm
required spacing
● with side-by-side mounting
— forwards
10 mm
— upwards
10 mm
— downwards
10 mm
— at the side
0 mm
● for grounded parts
— forwards
10 mm
— upwards
10 mm
— at the side
6 mm
— downwards
10 mm
● for live parts
— forwards
10 mm
— upwards
10 mm
— downwards
10 mm
— at the side
6 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
Ring cable lug connection
● for auxiliary and control circuit
ring terminal lug connection
● at contactor for auxiliary contacts
Ring cable lug connection
● of magnet coil
Ring cable lug connection
Safety related data
product function
● mirror contact according to IEC 60947-4-1
Yes
● positively driven operation according to IEC 609475-1
No
B10 value with high demand rate according to SN 31920
450 000
proportion of dangerous failures
● with low demand rate according to SN 31920
3RT20264XB400LA2
Page 4/6
40 %
7/4/2022
Subject to change without notice
© Copyright Siemens
● with high demand rate according to SN 31920
73 %
failure rate [FIT] with low demand rate according to SN
31920
100 FIT
T1 value for proof test interval or service life according to
IEC 61508
20 y
protection class IP on the front according to IEC
60529
IP00
Communication/ Protocol
product function bus communication
No
Certificates/ approvals
General Product Approval
Confirmation
EMC
Functional
Safety/Safety of
Machinery
KC
Declaration of Conformity
Type Examination
Certificate
Test Certificates
Special Test Certificate
Type Test Certificates/Test Report
Marine / Shipping
Marine / Shipping
other
Confirmation
Railway
Vibration and Shock
Dangerous Good
Type Test Certificates/Test Report
Transport Information
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT2026-4XB40-0LA2
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT2026-4XB40-0LA2
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RT2026-4XB40-0LA2
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT2026-4XB40-0LA2&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RT2026-4XB40-0LA2/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RT2026-4XB40-0LA2&objecttype=14&gridview=view1
3RT20264XB400LA2
Page 5/6
7/4/2022
Subject to change without notice
© Copyright Siemens