Data sheet
3RT2536-1AB00
Power contactor, AC-3 50 A, 22 kW / 400 V 2 NO + 2 NC 24 V AC, 50 Hz
4-pole size S2 screw terminals 1 NO + 1 NC integrated
product brand name
SIRIUS
product designation
contactor
product type designation
3RT25
General technical data
size of contactor
S2
product extension
● function module for communication
No
● auxiliary switch
Yes
insulation voltage
● of main circuit with degree of pollution 3 rated value
690 V
● of auxiliary circuit with degree of pollution 3 rated
value
690 V
surge voltage resistance
● of main circuit rated value
6 kV
● of auxiliary circuit rated value
6 kV
maximum permissible voltage for safe isolation between
coil and main contacts acc. to EN 60947-1
400 V
shock resistance at rectangular impulse
● at AC
11.8g / 5 ms, 7.4g / 10 ms
shock resistance with sine pulse
● at AC
18.5g / 5 ms, 11.6g / 10 ms
mechanical service life (switching cycles)
● of contactor typical
10 000 000
● of the contactor with added electronically optimized
auxiliary switch block typical
5 000 000
● of the contactor with added auxiliary switch block
typical
10 000 000
reference code acc. to IEC 81346-2
Q
Substance Prohibitance (Date)
01.10.2014 00:00:00
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
● ambient temperature during operation
-40 ... +70 °C
● ambient temperature during storage
-55 ... +80 °C
Main circuit
number of poles for main current circuit
4
number of NO contacts for main contacts
2
number of NC contacts for main contacts
2
operational current
3RT25361AB00
Page 1/2
1.21.2021
Subject to change without notice
© Copyright Siemens
● at AC-1 up to 690 V
— at ambient temperature 40 °C rated value
70 A
— at ambient temperature 60 °C rated value
60 A
● at AC-2 at AC-3 at 400 V
— per NO contact rated value
41 A
— per NC contact rated value
41 A
minimum cross-section in main circuit at maximum AC-1
rated value
25 mm²
operational current
● at 1 current path at DC-1
— at 24 V rated value
60 A
— at 110 V rated value
4.5 A
— at 220 V rated value
1A
— at 440 V rated value
0.4 A
● with 2 current paths in series at DC-1
— at 24 V rated value
55 A
— at 110 V rated value
45 A
— at 220 V rated value
5A
— at 440 V rated value
1A
operational current
● at 1 current path at DC-3 at DC-5
— at 24 V per NC contact rated value
35 A
— at 24 V per NO contact rated value
35 A
— at 110 V per NC contact rated value
1.25 A
— at 110 V per NO contact rated value
2.5 A
— at 220 V per NC contact rated value
0.5 A
— at 220 V per NO contact rated value
1A
— at 440 V per NC contact rated value
0.045 A
— at 440 V per NO contact rated value
0.1 A
● with 2 current paths in series at DC-3 at DC-5
— at 24 V per NC contact rated value
55 A
— at 24 V per NO contact rated value
55 A
— at 110 V per NC contact rated value
12.5 A
— at 110 V per NO contact rated value
25 A
— at 220 V per NC contact rated value
2.5 A
— at 220 V per NO contact rated value
5A
— at 440 V per NC contact rated value
0.135 A
— at 440 V per NO contact rated value
0.27 A
operating power at AC-2 at AC-3
● at 230 V per NC contact rated value
15 kW
● at 230 V per NO contact rated value
15 kW
● at 400 V per NC contact rated value
22 kW
● at 400 V per NO contact rated value
22 kW
short-time withstand current in cold operating state
up to 40 °C
● limited to 1 s switching at zero current maximum
546 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 5 s switching at zero current maximum
443 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 10 s switching at zero current maximum
334 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 30 s switching at zero current maximum
241 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 60 s switching at zero current maximum
196 A; Use minimum cross-section acc. to AC-1 rated value
power loss [W] at AC-3 at 400 V for rated value of the
operational current per conductor
4W
no-load switching frequency
● at AC
operating frequency at AC-1 maximum
5 000 1/h
1 000 1/h
Control circuit/ Control
type of voltage of the control supply voltage
AC
control supply voltage at AC
● at 50 Hz rated value
3RT25361AB00
Page 2/3
24 V
1.21.2021
Subject to change without notice
© Copyright Siemens
operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
apparent pick-up power of magnet coil at AC
● at 50 Hz
inductive power factor with closing power of the coil
● at 50 Hz
apparent holding power of magnet coil at AC
● at 50 Hz
inductive power factor with the holding power of the
coil
● at 50 Hz
0.8 ... 1.1
190 V·A
190 V·A
0.72
0.72
16 V·A
16 V·A
0.37
0.37
closing delay
● at AC
12 ... 22 ms
opening delay
● at AC
10 ... 18 ms
arcing time
10 ... 20 ms
control version of the switch operating mechanism
AC
Auxiliary circuit
number of NC contacts for auxiliary contacts
instantaneous contact
1
number of NO contacts for auxiliary contacts
instantaneous contact
1
operational current at AC-12 maximum
10 A
operational current at AC-15
● at 230 V rated value
6A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
operational current at DC-12
● at 24 V rated value
10 A
● at 48 V rated value
6A
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 125 V rated value
2A
● at 220 V rated value
1A
● at 600 V rated value
0.15 A
operational current at DC-13
● at 24 V rated value
10 A
● at 48 V rated value
2A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 125 V rated value
0.9 A
● at 220 V rated value
0.3 A
● at 600 V rated value
0.1 A
contact reliability of auxiliary contacts
1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
contact rating of auxiliary contacts according to UL
A600 / P600
Short-circuit protection
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 160 A (690 V, 100 kA)
— with type of assignment 2 required
gG: 80 A (690 V, 100 kA)
● for short-circuit protection of the auxiliary switch
required
fuse gG: 10 A
Installation/ mounting/ dimensions
mounting position
+/-180° rotation possible on vertical mounting surface; can be tilted
forward and backward by +/- 22.5° on vertical mounting surface
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
3RT25361AB00
Page 3/4
1.21.2021
Subject to change without notice
© Copyright Siemens
according to DIN EN 50022
● side-by-side mounting
Yes
height
114 mm
width
75 mm
depth
130 mm
required spacing
● with side-by-side mounting
— forwards
0 mm
— backwards
0 mm
— upwards
0 mm
— downwards
0 mm
— at the side
0 mm
● for grounded parts
— forwards
0 mm
— backwards
0 mm
— upwards
50 mm
— at the side
10 mm
— downwards
50 mm
● for live parts
— forwards
0 mm
— backwards
0 mm
— upwards
50 mm
— downwards
50 mm
— at the side
10 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
screw-type terminals
type of connectable conductor cross-sections
● for main contacts
— solid
2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
— solid or stranded
2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
— finely stranded with core end processing
2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
● at AWG cables for main contacts
2x (18 ... 2), 1x (18 ... 1)
type of connectable conductor cross-sections
● for auxiliary contacts
— solid
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
— solid or stranded
2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14)
AWG number as coded connectable conductor cross
section for main contacts
18 ... 1
Safety related data
product function
● mirror contact acc. to IEC 60947-4-1
Yes
● positively driven operation acc. to IEC 60947-5-1
No
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe, for vertical contact from the front
Certificates/ approvals
General Product Approval
EMC
KC
Declaration of Conformity
3RT25361AB00
Page 4/5
Test Certificates
1.21.2021
Marine / Shipping
Subject to change without notice
© Copyright Siemens
Miscellaneous
Type Test
Certificates/Test
Report
Special Test
Certificate
Marine / Shipping
other
Confirmation
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT2536-1AB00
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT2536-1AB00
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RT2536-1AB00
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT2536-1AB00&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RT2536-1AB00/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RT2536-1AB00&objecttype=14&gridview=view1
3RT25361AB00
Page 5/6
1.21.2021
Subject to change without notice
© Copyright Siemens
3RT25361AB00
Page 6/7
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RT25361AB00
Page 7/7
12/15/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RT25361AB00”相匹配的价格&库存,您可以联系我们找货
免费人工找货