Data sheet
3RU2136-4QD1
Overload relay 47...57 A Thermal For motor protection Size S2, Class 10
Stand-alone installation Main circuit: Screw Auxiliary circuit: spring-type
terminal Manual-Automatic-Reset
product brand name
SIRIUS
product designation
thermal overload relay
product type designation
3RU2
General technical data
size of overload relay
S2
size of contactor can be combined company-specific
S2
power loss [W] for rated value of the current at AC in hot
operating state
15.6 W
● per pole
5.2 W
insulation voltage with degree of pollution 3 at AC rated
value
690 V
surge voltage resistance rated value
6 kV
maximum permissible voltage for safe isolation in
networks with grounded star point
● between auxiliary and auxiliary circuit
415 V
● between auxiliary and auxiliary circuit
415 V
● between main and auxiliary circuit
690 V
● between main and auxiliary circuit
690 V
shock resistance acc. to IEC 60068-2-27
8g / 11 ms
recovery time after overload trip
● with automatic reset typical
10 min
● with remote-reset
10 min
● with manual reset
10 min
type of protection according to ATEX directive
2014/34/EU
Ex II (2) GD
certificate of suitability according to ATEX directive
2014/34/EU
DMT 98 ATEX G 001
reference code acc. to IEC 81346-2
F
Substance Prohibitance (Date)
15.10.2014 00:00:00
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
● ambient temperature during operation
-40 ... +70 °C
● ambient temperature during storage
-55 ... +80 °C
● ambient temperature during transport
-55 ... +80 °C
temperature compensation
-40 ... +60 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3RU21364QD1
Page 1/2
3
1.21.2021
Subject to change without notice
© Copyright Siemens
adjustable current response value current of the
current-dependent overload release
47 ... 57 A
● operating voltage rated value
690 V
● operating voltage at AC-3 rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current rated value
57 A
Auxiliary circuit
design of the auxiliary switch
integrated
number of NC contacts for auxiliary contacts
1
● note
number of NO contacts for auxiliary contacts
● note
number of CO contacts for auxiliary contacts
for contactor disconnection
1
for message "Tripped"
0
operational current of auxiliary contacts at AC-15
● at 24 V
3A
● at 110 V
3A
● at 120 V
3A
● at 125 V
3A
● at 230 V
2A
● at 400 V
1A
operational current of auxiliary contacts at DC-13
● at 24 V
2A
● at 60 V
0.3 A
● at 110 V
0.22 A
● at 125 V
0.22 A
● at 220 V
0.11 A
design of the miniature circuit breaker for short-circuit
protection of the auxiliary switch required
6A (SCC less than equal to 0.5 kA; U less than equal to 260V)
contact rating of auxiliary contacts according to UL
B600 / R300
Protective and monitoring functions
trip class
CLASS 10
design of the overload release
thermal
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
57 A
● at 600 V rated value
57 A
Short-circuit protection
design of the fuse link
● for short-circuit protection of the auxiliary switch
required
fuse gG: 6 A, quick: 10 A
Installation/ mounting/ dimensions
mounting position
any
fastening method
stand-alone installation
height
105 mm
width
55 mm
depth
117 mm
Connections/ Terminals
product function removable terminal for auxiliary and
control circuit
No
type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
spring-loaded terminals
arrangement of electrical connectors for main current
circuit
Top and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded
2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
— finely stranded with core end processing
2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
3RU21364QD1
Page 2/3
1.21.2021
Subject to change without notice
© Copyright Siemens
● at AWG cables for main contacts
2x (18 ... 2), 1x (18 ... 1)
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded
2x (0.5 ... 2.5 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²)
— finely stranded without core end processing
2x (0.5 ... 2.5 mm²)
● at AWG cables for auxiliary contacts
2x (20 ... 14)
● tightening torque for main contacts with screw-type
terminals
3 ... 4.5 N·m
design of screwdriver shaft
Diameter 5 ... 6 mm
size of the screwdriver tip
Pozidriv PZ 2
design of the thread of the connection screw
● for main contacts
M6
Safety related data
T1 value for proof test interval or service life acc. to
IEC 61508
20 y
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe, for vertical contact from the front
Display
display version for switching status
Slide switch
Certificates/ approvals
General Product Approval
Declaration of Conformity
Miscellaneous
For use in hazardous locations
Test Certificates
Special Test
Certificate
Marine / Shipping
Type Test
Certificates/Test
Report
Marine / Shipping
other
Confirmation
Railway
Special Test
Certificate
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RU2136-4QD1
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RU2136-4QD1
3RU21364QD1
Page 3/4
1.21.2021
Subject to change without notice
© Copyright Siemens
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RU2136-4QD1
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RU2136-4QD1&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RU2136-4QD1/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RU2136-4QD1&objecttype=14&gridview=view1
3RU21364QD1
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
3RU21364QD1
Page 5/6
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RU21364QD1
Page 6/6
12/15/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RU21364QD1”相匹配的价格&库存,您可以联系我们找货