Data sheet
3RV1011-1EA15
Circuit breaker size S00 for motor protection, CLASS 10 A-release 2.8...4 A N
release 52 A Screw terminal Standard switching capacity with transverse auxiliary
switch 1 NO+1 NC
product brand name
SIRIUS
product designation
Circuit breaker
design of the product
For motor protection
product type designation
3RV1
General technical data
size of the circuit-breaker
S00
size of contactor can be combined company-specific
S00
product extension auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
7.25 W
● at AC in hot operating state per pole
2.4 W
insulation voltage with degree of pollution 3 at AC rated value
690 V
surge voltage resistance rated value
6 kV
mechanical service life (operating cycles)
● of the main contacts typical
100 000
● of auxiliary contacts typical
100 000
electrical endurance (operating cycles) typical
100 000
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
01/01/2013
SVHC substance name
Lead - 7439-92-1
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-20 ... +60 °C
● during storage
-50 ... +80 °C
● during transport
-50 ... +80 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the currentdependent overload release
2.8 ... 4 A
operating voltage
● rated value
20 ... 690 V
● at AC-3 rated value maximum
690 V
● at AC-3e rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current rated value
4A
operational current
● at AC-3 at 400 V rated value
4A
● at AC-3e at 400 V rated value
4A
3RV10111EA15
Page 1/6
4/24/2024
Subject to change without notice
© Copyright Siemens
operating power
● at AC-3
— at 230 V rated value
0.8 kW
— at 400 V rated value
1.5 kW
— at 500 V rated value
2.2 kW
— at 690 V rated value
3 kW
● at AC-3e
— at 230 V rated value
0.8 kW
— at 400 V rated value
1.5 kW
— at 500 V rated value
2.2 kW
— at 690 V rated value
3 kW
operating frequency
● at AC-3 maximum
15 1/h
● at AC-3e maximum
15 1/h
Auxiliary circuit
design of the auxiliary switch
transverse
number of NC contacts for auxiliary contacts
1
● note
number of NO contacts for auxiliary contacts
● note
number of CO contacts for auxiliary contacts
1
1
1
0
operational current of auxiliary contacts at AC-15
● at 24 V
2A
● at 110 V
2A
● at 120 V
2A
● at 125 V
2A
● at 230 V
0.5 A
operational current of auxiliary contacts at DC-13
● at 24 V
1A
● at 60 V
0.15 A
Protective and monitoring functions
product function
● ground fault detection
No
● phase failure detection
Yes
trip class
CLASS 10
design of the overload release
thermal
maximum short-circuit current breaking capacity (Icu)
● at AC at 240 V rated value
100 kA
● at AC at 400 V rated value
100 kA
● at AC at 500 V rated value
3 kA
● at AC at 690 V rated value
2 kA
operating short-circuit current breaking capacity (Ics) at AC
● at 240 V rated value
100 kA
● at 400 V rated value
100 kA
● at 500 V rated value
3 kA
● at 690 V rated value
2 kA
response value current of instantaneous short-circuit trip unit
52 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
4A
● at 600 V rated value
4A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
0.13 hp
— at 230 V rated value
0.33 hp
● for 3-phase AC motor
— at 200/208 V rated value
0.8 hp
— at 220/230 V rated value
0.75 hp
— at 460/480 V rated value
2 hp
— at 575/600 V rated value
3 hp
3RV10111EA15
Page 2/6
4/24/2024
Subject to change without notice
© Copyright Siemens
contact rating of auxiliary contacts according to UL
C300 / R300
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
design of the fuse link
● for short-circuit protection of the auxiliary switch required
fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)
design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 240 V
none required
● at 400 V
gL/gG 40 A
● at 500 V
gL/gG 35 A
● at 690 V
gL/gG 35 A
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
height
90 mm
width
45 mm
depth
75 mm
required spacing
● for grounded parts at 400 V
— downwards
20 mm
— upwards
20 mm
— at the side
9 mm
● for live parts at 400 V
— downwards
20 mm
— upwards
20 mm
— at the side
9 mm
● for grounded parts at 500 V
— downwards
20 mm
— upwards
20 mm
— at the side
9 mm
● for live parts at 500 V
— downwards
20 mm
— upwards
20 mm
— at the side
9 mm
● for grounded parts at 690 V
— downwards
20 mm
— upwards
20 mm
— backwards
0 mm
— at the side
9 mm
— forwards
0 mm
● for live parts at 690 V
— downwards
20 mm
— upwards
20 mm
— backwards
0 mm
— at the side
9 mm
— forwards
0 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
screw-type terminals
arrangement of electrical connectors for main current
circuit
Top and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded
2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x (1 ... 4 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
tightening torque
3RV10111EA15
Page 3/6
4/24/2024
Subject to change without notice
© Copyright Siemens
● for main contacts with screw-type terminals
0.8 ... 1.2 N·m
● for auxiliary contacts with screw-type terminals
0.8 ... 1.2 N·m
size of the screwdriver tip
Pozidriv size 2
design of the thread of the connection screw
● for main contacts
M3
● of the auxiliary and control contacts
M3
Safety related data
product function suitable for safety function
Yes
suitability for use
● safety-related switching on
No
● safety-related switching OFF
Yes
service life maximum
10 a
test wear-related service life necessary
Yes
proportion of dangerous failures
● with low demand rate according to SN 31920
40 %
● with high demand rate according to SN 31920
50 %
B10 value with high demand rate according to SN 31920
5 000
failure rate [FIT] with low demand rate according to SN
31920
50 FIT
ISO 13849
device type according to ISO 13849-1
3
overdimensioning according to ISO 13849-2 necessary
Yes
IEC 61508
safety device type according to IEC 61508-2
Type A
Electrical Safety
protection class IP on the front according to IEC 60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
Display
display version for switching status
Rocker switch
Approvals Certificates
General Product Approval
Confirmation
General Product Approval
For use in hazardous locations
KC
Test Certificates
Special Test Certificate
Marine / Shipping
Type Test Certificates/Test Report
Marine / Shipping
other
Confirmation
Miscellaneous
Railway
Environment
Special Test Certificate
Environmental Confirmations
Further information
3RV10111EA15
Page 4/6
4/24/2024
Subject to change without notice
© Copyright Siemens
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV1011-1EA15
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV1011-1EA15
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV1011-1EA15
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV1011-1EA15&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV1011-1EA15/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV1011-1EA15&objecttype=14&gridview=view1
3RV10111EA15
Page 5/6
4/24/2024
Subject to change without notice
© Copyright Siemens
13
21
14
22
5/L3
3/L2
1/L1
-F
last modified:
3RV10111EA15
Page 6/6
I>
6/T3
I>
4/T2
2/T1
I>
4/12/2024
4/24/2024
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RV1011-1EA15”相匹配的价格&库存,您可以联系我们找货