Data sheet
3RV1011-1GA15
Circuit breaker size S00 for motor protection, CLASS 10 A-release 4.5...6.3
A N-release 82 A Screw terminal Standard switching capacity with
transverse auxiliary switch 1 NO+1 NC
product brand name
SIRIUS
product designation
Circuit breaker
design of the product
For motor protection
product type designation
3RV1
General technical data
size of the circuit-breaker
S00
size of contactor can be combined company-specific
S00
product extension auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
7.25 W
● at AC in hot operating state per pole
2.4 W
insulation voltage with degree of pollution 3 at AC rated
value
690 V
surge voltage resistance rated value
6 kV
maximum permissible voltage for safe isolation in
networks with grounded star point
● between main and auxiliary circuit
400 V
● between main and auxiliary circuit
400 V
mechanical service life (switching cycles)
● of the main contacts typical
100 000
● of auxiliary contacts typical
100 000
electrical endurance (switching cycles) typical
100 000
reference code acc. to IEC 81346-2
Q
Substance Prohibitance (Date)
01.01.2013 00:00:00
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
● ambient temperature during operation
-20 ... +60 °C
● ambient temperature during storage
-50 ... +80 °C
● ambient temperature during transport
-50 ... +80 °C
temperature compensation
-20 ... +60 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the
current-dependent overload release
4.5 ... 6.3 A
● operating voltage rated value
690 V
● operating voltage at AC-3 rated value maximum
690 V
operating frequency rated value
3RV10111GA15
Page 1/2
50 ... 60 Hz
1.21.2021
Subject to change without notice
© Copyright Siemens
operational current rated value
6.3 A
operational current at AC-3 at 400 V rated value
6.3 A
operating power at AC-3
● at 230 V rated value
1 500 W
● at 400 V rated value
2 200 W
● at 500 V rated value
3 000 W
● at 690 V rated value
5 500 W
operating frequency at AC-3 maximum
15 1/h
Auxiliary circuit
design of the auxiliary switch
transverse
number of NC contacts for auxiliary contacts
1
● note
number of NO contacts for auxiliary contacts
● note
number of CO contacts for auxiliary contacts
1
1
1
0
operational current of auxiliary contacts at AC-15
● at 24 V
2A
● at 110 V
2A
● at 120 V
2A
● at 125 V
2A
● at 230 V
0.5 A
operational current of auxiliary contacts at DC-13
● at 24 V
1A
● at 60 V
0.15 A
Protective and monitoring functions
product function
● ground fault detection
No
● phase failure detection
Yes
trip class
CLASS 10
design of the overload release
thermal
breaking capacity operating short-circuit current (Ics)
at AC
● at 240 V rated value
100 kA
● at 400 V rated value
100 kA
● at 500 V rated value
3 kA
● at 690 V rated value
2 kA
breaking capacity maximum short-circuit current (Icu)
● at AC at 240 V rated value
100 kA
● at AC at 400 V rated value
100 kA
● at AC at 500 V rated value
3 kA
● at AC at 690 V rated value
2 kA
response value current of instantaneous short-circuit trip
unit
82 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
6.3 A
● at 600 V rated value
6.3 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
0.25 hp
— at 230 V rated value
0.5 hp
● for 3-phase AC motor
— at 200/208 V rated value
1 hp
— at 220/230 V rated value
1.5 hp
— at 460/480 V rated value
3 hp
— at 575/600 V rated value
5 hp
contact rating of auxiliary contacts according to UL
C300 / R300
Short-circuit protection
3RV10111GA15
Page 2/3
1.21.2021
Subject to change without notice
© Copyright Siemens
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
design of the fuse link
● for short-circuit protection of the auxiliary switch
required
fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik <
400 A)
design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 240 V
none required
● at 400 V
gL/gG 50 A
● at 500 V
gL/gG 40 A
● at 690 V
gL/gG 40 A
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height
90 mm
width
45 mm
depth
75 mm
required spacing
● for grounded parts at 400 V
— downwards
20 mm
— upwards
20 mm
— at the side
9 mm
● for live parts at 400 V
— downwards
20 mm
— upwards
20 mm
— at the side
9 mm
● for grounded parts at 500 V
— downwards
20 mm
— upwards
20 mm
— at the side
9 mm
● for live parts at 500 V
— downwards
20 mm
— upwards
20 mm
— at the side
9 mm
● for grounded parts at 690 V
— downwards
20 mm
— upwards
20 mm
— backwards
0 mm
— at the side
9 mm
— forwards
0 mm
● for live parts at 690 V
— downwards
20 mm
— upwards
20 mm
— backwards
0 mm
— at the side
9 mm
— forwards
0 mm
Connections/ Terminals
product function removable terminal for auxiliary and
control circuit
No
type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
screw-type terminals
arrangement of electrical connectors for main current
circuit
Top and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded
2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x (1 ... 4 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV10111GA15
Page 3/4
1.21.2021
Subject to change without notice
© Copyright Siemens
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded
2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²)
● tightening torque for main contacts with screw-type
terminals
0.8 ... 1.2 N·m
● tightening torque for auxiliary contacts with screwtype terminals
0.8 ... 1.2 N·m
size of the screwdriver tip
Pozidriv 2
design of the thread of the connection screw
● for main contacts
M3
● of the auxiliary and control contacts
M3
Safety related data
B10 value
● with high demand rate acc. to SN 31920
5 000
proportion of dangerous failures
● with low demand rate acc. to SN 31920
50 %
● with high demand rate acc. to SN 31920
50 %
failure rate [FIT]
● with low demand rate acc. to SN 31920
50 FIT
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe, for vertical contact from the front
display version for switching status
Rocker switch
Certificates/ approvals
General Product Approval
Declaration of Conformity
Miscellaneous
For use in hazardous locations
Test Certificates
Special Test
Certificate
Marine / Shipping
Type Test
Certificates/Test
Report
Marine / Shipping
other
Miscellaneous
other
Confirmation
Railway
Special Test
Certificate
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV1011-1GA15
3RV10111GA15
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV1011-1GA15
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV1011-1GA15
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV1011-1GA15&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV1011-1GA15/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV1011-1GA15&objecttype=14&gridview=view1
3RV10111GA15
Page 5/6
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RV10111GA15
Page 6/6
12/15/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RV1011-1GA15”相匹配的价格&库存,您可以联系我们找货
免费人工找货