Introduction
3RV Motor Starter Protectors
up to 100 A
General data
For motor protection
For motor protection
with overload relay function
For starter combinations
For transformer protection
For fuse monitoring
For plant protection according to
UL 489 / CSA C22.2 No.5-02
For distance protection
Accessories
Mountable accessories
Busbar accessories
Rotary operating mechanisms
Mounting accessories
Enclosures and front plates
Overload Relays
General data
3RB2 Solid-State Overload Relays
3RB20, 3RB21 for standard applications
3RB22, 3RB23 for high-feature
applications
Accessories
3RU1 Thermal Overload Relays
3RU11 for standard applications
Accessories
Siemens LV 1 · 2006
Protection Equipment
Introduction
■ Overview
3RV10
3RV11
3RV13
3RV14
3RV16
3RV16
3RV17
5
Type
1) For symmetrical loading of the three phases.
4) Only for motor starter protectors with Cage Clamp terminals.
2) With molded-plastic enclosure 500 V AC.
5) Only lateral auxiliary switches
3) For overload protection of the motors, appropriate overload relays
must be used.
5/2
Siemens LV 1 · 2006
3RV Motor Starter Protectors up to 100 A
Introduction
Type
3RU11
3RB20
3RB21
3RB22/3RB23
Plant protection
✓1)
✓1)
✓1)
✓1)
Motor protection
✓
✓
✓
✓
Alternating current, 3-phase
✓
✓
✓
✓
Alternating current, 1-phase
✓
–
–
✓
Direct current
✓
–
–
–
Size of contactor
S00, S0, S2, S3
S00 ... S12
S00 ... S12
S00 ... S12
Overload relays up to 630 A
Applications
Rated operational current Ie
A
A
up to 12
up to 25
up to 12
up to 25
up to 12
up to 25
} up to 25
Size S2
Size S3
A
A
up to 50
up to 100
up to 50
up to 100
up to 50
up to 100
} up to 100
Size S6
Size S10/S12, size 14 (3TF6)
A
A
–
–
up to 200
up to 630
up to 200
up to 630
up to 200
up to 630
Rated operational voltage Ue
V
690 / 1000 AC2)
690 / 1000 AC2)
690 / 1000 AC2)
690 / 1000 AC3)
Rated frequency
Hz
50/60
50/60
50/60
50/60
CLASS 10
CLASS 10,
CLASS 20
CLASS 5, 10, 20, 30
adjustable
CLASS 5, 10, 20, 30
adjustable
–
–
–
A
0.11 ... 0.16
up to
80 ... 100
A
–
0.1 ... 0.4
up to
160 ... 630
0.1 ... 0.4
up to
160 ... 630
0.3 ... 3
up to
63 ... 630
0.04
up to
45
0.04 ... 0.09
up to
90 ... 450
0.04 ... 0.09
up to
90 ... 450
0.09 ... 1.1
up to
37 ... 450
Trip class
Thermal
overload release
Solid-state
overload release
A
A
Rating for induction motor
at 400 V AC
kW
kW
5
Size S00
Size S0
Accessories
For sizes
S00
S0
S2
S3
S00 S0
S2
S3
S6
S10/ S00 S0
S12
Terminal brackets for stand-alone
installation
✓
✓
✓
✓
✓
4)
4)
4)
4)
✓
✓
✓
S2
S3
S6
S10/ S00 S0
S12
S2
S3
S6
S10/
S12
4)
4)
4)
4)
4)
4)
4)
4)
4)
4)
Mechanical RESET
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
–
–
–
–
–
–
Cable release for RESET
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
–
–
–
–
–
–
Electrical remote RESET
✓
✓
✓
✓
–
–
–
–
–
–
Integrated in the unit
Terminal covers
–
–
✓
✓
–
–
–
✓
✓
✓
–
–
–
✓
✓
✓
–
–
–
✓
✓
✓
Sealable covers
for setting knobs
Integrated in the unit
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
Integrated in the unit
1) The units are responsible in the main circuit for overload protection of the
assigned electrical loads (e.g. motors), feeder cable and other switching
and protection devices in the respective load feeder.
2) Size S3 and larger up to 1000 V AC.
3) Sizes S6 and S10/12 up to 1000 V AC.
4) Stand-alone installation without accessories is possible.
Siemens LV 1 · 2006
5/3
3RV Motor Starter Protectors up to 100 A
General data
■ Overview
■ Application
Operating conditions
3RV1 motor starter protectors are suitable for use in any climate.
They are intended for use in enclosed rooms in which no severe
conditions (such as dust, caustic vapors, hazardous gases)
prevail. When installed in dusty and damp areas, suitable
enclosures must be provided.
3RV motor starter protectors can optionally be fed from the top
or from below.
The permissible ambient temperatures, the maximum switching
capacities, the tripping currents and other boundary conditions
can be found in the technical specifications and tripping
characteristics.
3RV1 motor starter protectors are suitable for use in IT systems
(IT networks). In this case, the different short-circuit breaking
capacity in the IT system must be taken into account.
S0 motor starter protectors
5
3RV1 motor starter protectors are compact, current limiting
motor starter protectors which are optimized for load feeders.
The motor starter protectors are used for switching and
protecting three-phase induction motors of up to 45 kW at
400 V AC and for other loads with rated currents of up to 100 A.
Type of construction
The motor starter protectors are available in four sizes:
• Size S00 – overall width 45 mm,
max. rated current 12 A,
at 400 V AC suitable for 3-phase induction motors
up to 5.5 kW.
• Size S0 – overall width 45 mm,
max. rated current 25 A,
at 400 V AC suitable for 3-phase induction motors
up to 11 kW.
• Size S2 – overall width 55 mm,
max. rated current 50 A,
at 400 V AC suitable for 3-phase induction motors
up to 22 kW.
• Size S3 – overall width 70 mm,
max. rated current 100 A,
at 400 V AC suitable for 3-phase induction motors
up to 45 kW.
5/4
Siemens LV 1 · 2006
Since operational currents, starting currents and current peaks
are different even for motors with identical power ratings due to
the inrush current, the motor ratings in the selection tables are
only guide values. The specific rated and start-up data of the
motor to be protected is always paramount to the choice of the
most suitable motor starter protector. This also applies to motor
starter protectors for transformer protection.
Possible uses
The 3RV1 motor starter protectors can be used:
• For short-circuit protection
• For motor protection (also with overload relay function)
• For plant protection
• For short-circuit protection for starter combinations
• For transformer protection
• As main control and EMERGENCY-STOP switches
• For fuse monitoring
• For use in IT systems (IT networks)
• For switching of DC currents
• As voltage transformer circuit-breakers
More information is available under "Configuration".
3RV Motor Starter Protectors up to 100 A
For motor protection
■ Selection and ordering data
Class 10, without/with auxiliary switches
Setting range
for thermal
overload
release
In
Instantaneous
overcurrent
release
I
v
Rated Suitable
current for threephase
induction
motors1)
with P
Short-circuit DT Screw connection
breaking
capacity at
400 V AC
,cu
Order No.
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.2)
Price
per PU
A
kW
A
A
kA
0.16
0.2
0.25
0.32
0.04
0.06
0.06
0.09
0.11 ... 0.16
0.14 ... 0.2
0.18 ... 0.25
0.22 ... 0.32
2.1
2.6
3.3
4.2
100
100
100
100
3RV10 11-0AA1 @
3RV10 11-0BA1 @
3RV10 11-0CA1 @
3RV10 11-0DA1 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.245
0.246
0.246
0.247
0.4
0.5
0.63
0.8
0.09
0.12
0.18
0.18
0.28 ... 0.4
0.35 ... 0.5
0.45 ... 0.63
0.55 ... 0.8
5.2
6.5
8.2
10
100
100
100
100
3RV10 11-0EA1 @
3RV10 11-0FA1 @
3RV10 11-0GA1@
3RV10 11-0HA1 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.250
0.247
0.249
0.250
1
1.25
1.6
2
0.25
0.37
0.55
0.75
0.7 ... 1
0.9 ... 1.25
1.1 ... 1.6
1.4 ... 2
13
16
21
26
100
100
100
100
3RV10 11-0JA1 @
3RV10 11-0KA1 @
3RV10 11-1AA1 @
3RV10 11-1BA1 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.249
0.297
0.298
0.297
2.5
3.2
4
5
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
33
42
52
65
100
100
100
100
3RV10 11-1CA1 @
3RV10 11-1DA1 @
3RV10 11-1EA1 @
3RV10 11-1FA1 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.298
0.299
0.296
0.301
6.3
8
10
12
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12
82
104
130
156
100
50
50
50
3RV10 11-1GA1@
3RV10 11-1HA1 @
3RV10 11-1JA1 @
3RV10 11-1KA1 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.303
0.304
0.300
0.297
0.16
0.2
0.25
0.32
0.04
0.06
0.06
0.09
0.11 ... 0.16
0.14 ... 0.2
0.18 ... 0.25
0.22 ... 0.32
2.1
2.6
3.3
4.2
100
100
100
100
3RV10 21-0AA1 @
3RV10 21-0BA1 @
3RV10 21-0CA1 @
3RV10 21-0DA1 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.300
0.304
0.302
0.303
0.4
0.5
0.63
0.8
0.09
0.12
0.18
0.18
0.28 ... 0.4
0.35 ... 0.5
0.45 ... 0.63
0.55 ... 0.8
5.2
6.5
8.2
10
100
100
100
100
3RV10 21-0EA1 @
3RV10 21-0FA1 @
3RV10 21-0GA1@
3RV10 21-0HA1 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.303
0.304
0.305
0.370
1
1.25
1.6
2
0.25
0.37
0.55
0.75
0.7 ... 1
0.9 ... 1.25
1.1 ... 1.6
1.4 ... 2
13
16
21
26
100
100
100
100
3RV10 21-0JA1 @
3RV10 21-0KA1 @
3RV10 21-1AA1 @
3RV10 21-1BA1 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.368
0.369
0.371
0.371
2.5
3.2
4
5
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
33
42
52
65
100
100
100
100
3RV10 21-1CA1 @
3RV10 21-1DA1 @
3RV10 21-1EA1 @
3RV10 21-1FA1 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.372
0.375
0.370
0.376
6.3
8
10
12.5
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12.5
82
104
130
163
100
100
100
100
3RV10 21-1GA1@
3RV10 21-1HA1 @
3RV10 21-1JA1 @
3RV10 21-1KA1 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.374
0.374
0.375
0.374
16
20
22
25
7.5
7.5
11
11
11 ... 16
14 ... 20
17 ... 22
20 ... 25
208
260
286
325
50
50
50
50
3RV10 21-4AA1 @
3RV10 21-4BA1 @
3RV10 21-4CA1 @
3RV10 21-4DA1 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.382
0.376
0.378
0.382
kg
Size S0
Additional
price 3)
Order No. supplement for
transverse auxiliary switches
None
}
0
None
1 NO + 1 NC
}
5
X
1) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
2) Weights are specified for variants with auxiliary switch.
3) Totals are rounded up and down. This may lead to slight differences in the
overall price.
Auxiliary switches can also be ordered separately
(see "Mountable Accessories").
Multi-unit/reusable packaging, see "Appendix" -->
"Ordering Notes".
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/5
5
Size S00
3RV Motor Starter Protectors up to 100 A
For motor protection
Class 10, without/with auxiliary switches
Setting range
for thermal
overload
release
,n
Instantaneous
overcurrent
release
I
v
Rated Suitable
current for threephase
induction
motors1)
with P
Short-circuit DT Cage Clamp connection
breaking
capacity
at
400 V AC
,cu
Order No.
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.2)
Price
per PU
kg
A
kW
A
A
kA
0.16
0.2
0.25
0.32
0.04
0.06
0.06
0.09
0.11 ... 0.16
0.14 ... 0.2
0.18 ... 0.25
0.22 ... 0.32
2.1
2.6
3.3
4.2
100
100
100
100
3RV10 11-0AA2 @
3RV10 11-0BA2 @
3RV10 11-0CA2 @
3RV10 11-0DA2 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.245
0.245
0.246
0.246
0.4
0.5
0.63
0.8
0.09
0.12
0.18
0.18
0.28 ... 0.4
0.35 ... 0.5
0.45 ... 0.63
0.55 ... 0.8
5.2
6.5
8.2
10
100
100
100
100
3RV10 11-0EA2 @
3RV10 11-0FA2 @
3RV10 11-0GA2@
3RV10 11-0HA2 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.250
0.247
0.252
0.250
1
1.25
1.6
2
0.25
0.37
0.55
0.75
0.7 ... 1
0.9 ... 1.25
1.1 ... 1.6
1.4 ... 2
13
16
21
26
100
100
100
100
3RV10 11-0JA2 @
3RV10 11-0KA2 @
3RV10 11-1AA2 @
3RV10 11-1BA2 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.249
0.297
0.298
0.297
2.5
3.2
4
5
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
33
42
52
65
100
100
100
100
3RV10 11-1CA2 @
3RV10 11-1DA2 @
3RV10 11-1EA2 @
3RV10 11-1FA2 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.298
0.300
0.298
0.303
6.3
8
10
12
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12
82
104
130
156
100
50
50
50
3RV10 11-1GA2@
3RV10 11-1HA2 @
3RV10 11-1JA2 @
3RV10 11-1KA2 @
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.303
0.304
0.300
0.298
5
Size S00
Additional
price3)
Order No. supplement for
transverse auxiliary switches
None
}
0
None
1 NO + 1 NC
B
5
X
1) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
2) Weights are specified for variants with auxiliary switch.
3) Totals are rounded up and down. This may lead to slight differences in the
overall price.
Auxiliary switches can also be ordered separately
(see "Mountable Accessories").
Multi-unit/reusable packaging, see "Appendix" -->
"Ordering Notes".
* You can order this quantity or a multiple thereof.
5/6
Siemens LV 1 · 2006
3RV Motor Starter Protectors up to 100 A
For motor protection
Class 10, without auxiliary switches
Rated Suitable
current for threephase
induction
motors1)
with P
Setting range
for thermal
overload
release
Instantaneous
overcurrent
release
Short-circuit DT Screw connection
breaking
capacity
at
400 V AC
Order No.
Icu
In
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
A
kW
A
A
kA
16
20
25
32
7.5
7.5
11
15
11 ... 16
14 ... 20
18 ... 25
22 ... 32
208
260
325
416
50
50
50
50
}
}
}
}
3RV10 31-4AA10
3RV10 31-4BA10
3RV10 31-4DA10
3RV10 31-4EA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
1.046
1.043
1.031
1.028
40
45
50
18.5
22
22
28 ... 40
36 ... 45
40 ... 50
520
585
650
50
50
50
}
}
}
3RV10 31-4FA10
3RV10 31-4GA10
3RV10 31-4HA10
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.047
1.039
1.027
40
50
63
18.5
22
30
28 ... 40
36 ... 50
45 ... 63
520
650
819
50
50
50
}
}
}
3RV10 41-4FA10
3RV10 41-4HA10
3RV10 41-4JA10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.219
2.240
2.247
75
90
100
37
45
45
57 ... 75
70 ... 90
80 ... 100
975
1170
1235
50
50
50
}
}
}
3RV10 41-4KA10
3RV10 41-4LA10
3RV10 41-4MA10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.253
2.280
2.295
Size S2
5
Size S3
Size S3, with increased switching capacity
16
20
25
32
7.5
7.5
11
15
11 ... 16
14 ... 20
18 ... 25
22 ... 32
208
260
325
416
100
100
100
100
}
}
}
}
3RV10 42-4AA10
3RV10 42-4BA10
3RV10 42-4DA10
3RV10 42-4EA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
2.174
2.185
2.211
2.222
40
50
63
18.5
22
30
28 ... 40
36 ... 50
45 ... 63
520
650
819
100
100
100
}
}
}
3RV10 42-4FA10
3RV10 42-4HA10
3RV10 42-4JA10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.203
2.230
2.255
75
90
100
37
45
45
57 ... 75
70 ... 90
80 ... 100
975
1170
1235
100
100
100
}
}
}
3RV10 42-4KA10
3RV10 42-4LA10
3RV10 42-4MA10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.266
2.268
2.275
Class 20, without auxiliary switches
Size S2
16
20
25
32
7.5
7.5
11
15
11 ... 16
14 ... 20
18 ... 25
22 ... 32
208
260
325
416
50
50
50
50
A
A
A
A
3RV10 31-4AB10
3RV10 31-4BB10
3RV10 31-4DB10
3RV10 31-4EB10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
1.067
1.071
1.054
1.067
40
45
50
18.5
22
22
28 ... 40
36 ... 45
40 ... 50
520
585
650
50
50
50
A
A
A
3RV10 31-4FB10
3RV10 31-4GB10
3RV10 31-4HB10
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.076
1.073
1.071
Size S3, with increased switching capacity
40
50
63
18.5
22
30
28 ... 40
36 ... 50
45 ... 63
520
650
819
100
100
100
A
A
A
3RV10 42-4FB10
3RV10 42-4HB10
3RV10 42-4JB10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.222
2.265
2.278
75
90
100
37
45
45
57 ... 75
70 ... 90
80 ... 100
975
1.170
1.235
100
100
100
A
A
A
3RV10 42-4KB10
3RV10 42-4LB10
3RV10 42-4MB10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.268
2.313
2.322
1) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
Auxiliary switches can be ordered separately
(see "Mountable Accessories").
Multi-unit/reusable packaging, see "Appendix" -->
"Ordering Notes".
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/7
3RV Motor Starter Protectors up to 100 A
For motor protection with overload relay function
■ Selection and ordering data
CLASS 10, with overload relay functions (automatic reset),
without auxiliary switches
Setting range
for thermal
overload
release
In
Instantaneous
overcurrent
release
I
v
Rated Suitable
current for threephase
induction
motors1)
with P
Shortcircuit
breaking
capacity
at
400 V AC
DT Screw connection
Order No.
Icu
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
A
kW
A
A
kA
0.16
0.2
0.25
0.32
0.04
0.06
0.06
0.09
0.11 ... 0.16
0.14 ... 0.2
0.18 ... 0.25
0.22 ... 0.32
2.1
2.6
3.3
4.2
100
100
100
100
A
A
A
A
3RV11 21-0AA10
3RV11 21-0BA10
3RV11 21-0CA10
3RV11 21-0DA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.354
0.358
0.352
0.352
0.4
0.5
0.63
0.8
0.09
0.12
0.18
0.18
0.28 ... 0.4
0.35 ... 0.5
0.45 ... 0.63
0.55 ... 0.8
5.2
6.5
8.2
10
100
100
100
100
A
A
A
A
3RV11 21-0EA10
3RV11 21-0FA10
3RV11 21-0GA10
3RV11 21-0HA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.355
0.356
0.358
0.421
1
1.25
1.6
2
0.25
0.37
0.55
0.75
0.7 ... 1
0.9 ... 1.25
1.1 ... 1.6
1.4 ... 2
13
16
21
26
100
100
100
100
A
A
A
A
3RV11 21-0JA10
3RV11 21-0KA10
3RV11 21-1AA10
3RV11 21-1BA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.416
0.426
0.422
0.427
2.5
3.2
4
5
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
33
42
52
65
100
100
100
100
A
A
A
A
3RV11 21-1CA10
3RV11 21-1DA10
3RV11 21-1EA10
3RV11 21-1FA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.422
0.428
0.420
0.429
6.3
8
10
12.5
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12.5
82
104
130
163
100
100
100
100
A
A
A
A
3RV11 21-1GA10
3RV11 21-1HA10
3RV11 21-1JA10
3RV11 21-1KA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.426
0.425
0.428
0.426
16
20
22
25
7.5
7.5
11
11
11 ... 16
14 ... 20
17 ... 22
20 ... 25
208
260
286
325
50
50
50
50
A
A
A
A
3RV11 21-4AA10
3RV11 21-4BA10
3RV11 21-4CA10
3RV11 21-4DA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.436
0.430
0.427
0.432
16
20
25
32
7.5
7.5
11
15
11 ... 16
14 ... 20
18 ... 25
22 ... 32
208
260
325
416
50
50
50
50
A
A
A
A
3RV11 31-4AA10
3RV11 31-4BA10
3RV11 31-4DA10
3RV11 31-4EA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
1.123
1.109
1.114
1.111
40
45
50
18.5
22
22
28 ... 40
36 ... 45
40 ... 50
520
585
650
50
50
50
A
A
A
3RV11 31-4FA10
3RV11 31-4GA10
3RV11 31-4HA10
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.123
1.101
1.106
5
Size S02)
Size S22)
Size S3, with increased switching capacity2)
16
20
25
32
7.5
7.5
11
15
11 ... 16
14 ... 20
18 ... 25
22 ... 32
208
260
325
416
100
100
100
100
A
A
A
A
3RV11 42-4AA10
3RV11 42-4BA10
3RV11 42-4DA10
3RV11 42-4EA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
2.247
2.255
2.284
2.295
40
50
63
18.5
22
30
28 ... 40
36 ... 50
45 ... 63
520
650
819
100
100
100
A
A
A
3RV11 42-4FA10
3RV11 42-4HA10
3RV11 42-4JA10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.288
2.320
2.333
75
90
100
37
45
45
57 ... 75
70 ... 90
80 ... 100
975
1170
1235
100
100
100
A
A
A
3RV11 42-4KA10
3RV11 42-4LA10
3RV11 42-4MA10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.368
2.353
2.346
1) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
2) Accessories for mounting on the right (for series S0 to S3) and 3RV19 15
three-phase busbars (for size S0) cannot be used.
Auxiliary switches can be ordered separately
(see "Mountable accessories").
Multi-unit/reusable packaging, see "Appendix" -->
"Ordering Notes".
* You can order this quantity or a multiple thereof.
5/8
Siemens LV 1 · 2006
3RV Motor Starter Protectors up to 100 A
For starter combinations
■ Selection and ordering data
Without auxiliary switches
Setting range
for thermal
overload
release2)
In
Instantaneous
overcurrent
release
I
v
Rated Suitable
current for threephase
induction
motors1)
with P
Short-circuit DT Screw connection
breaking
capacity
at
400 V AC
Order No.
Icu
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
A
kW
A
A
kA
0.16
0.2
0.25
0.32
0.04
0.06
0.06
0.09
None
None
None
None
2.1
2.6
3.3
4.2
100
100
100
100
A
A
A
A
3RV13 21-0AC10
3RV13 21-0BC10
3RV13 21-0CC10
3RV13 21-0DC10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.282
0.284
0.285
0.282
0.4
0.5
0.63
0.8
0.09
0.12
0.18
0.18
None
None
None
None
5.2
6.5
8.2
10
100
100
100
100
A
A
A
A
3RV13 21-0EC10
3RV13 21-0FC10
3RV13 21-0GC10
3RV13 21-0HC10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.286
0.283
0.348
0.283
1
1.25
1.6
2
0.25
0.37
0.55
0.75
None
None
None
None
13
16
21
26
100
100
100
100
A
A
A
A
3RV13 21-0JC10
3RV13 21-0KC10
3RV13 21-1AC10
3RV13 21-1BC10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.345
0.351
0.352
0.352
2.5
3.2
4
5
0.75
1.1
1.5
1.5
None
None
None
None
33
42
52
65
100
100
100
100
A
A
A
A
3RV13 21-1CC10
3RV13 21-1DC10
3RV13 21-1EC10
3RV13 21-1FC10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.352
0.353
0.349
0.354
6.3
8
10
12.5
2.2
3
4
5.5
None
None
None
None
82
104
130
163
100
100
100
100
A
A
A
A
3RV13 21-1GC10
3RV13 21-1HC10
3RV13 21-1JC10
3RV13 21-1KC10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.355
0.354
0.357
0.354
16
20
22
25
7.5
7.5
11
11
None
None
None
None
208
260
286
325
50
50
50
50
A
A
A
A
3RV13 21-4AC10
3RV13 21-4BC10
3RV13 21-4CC10
3RV13 21-4DC10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.362
0.357
0.358
0.359
16
20
25
32
7.5
7.5
11
15
None
None
None
None
208
260
325
416
50
50
50
50
A
A
A
A
3RV13 31-4AC10
3RV13 31-4BC10
3RV13 31-4DC10
3RV13 31-4EC10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
1.038
1.037
1.014
1.018
40
45
50
18.5
22
22
None
None
None
520
585
650
50
50
50
A
A
A
3RV13 31-4FC10
3RV13 31-4GC10
3RV13 31-4HC10
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.033
1.040
1.019
40
50
63
18.5
22
30
None
None
None
520
650
819
50
50
50
A
A
A
3RV13 41-4FC10
3RV13 41-4HC10
3RV13 41-4JC10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.197
2.227
2.244
75
90
100
37
45
45
None
None
None
975
1170
1235
50
50
50
A
A
A
3RV13 41-4KC10
3RV13 41-4LC10
3RV13 41-4MC10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.247
2.269
2.292
kg
Size S2
Size S3
Size S3, with increased switching capacity
16
20
25
32
7.5
7.5
11
15
None
None
None
None
208
260
325
416
100
100
100
100
A
A
A
A
3RV13 42-4AC10
3RV13 42-4BC10
3RV13 42-4DC10
3RV13 42-4EC10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
2.175
2.188
2.219
2.208
40
50
63
18.5
22
30
None
None
None
520
650
819
100
100
100
A
A
A
3RV13 42-4FC10
3RV13 42-4HC10
3RV13 42-4JC10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.218
2.218
2.248
75
90
100
37
45
45
None
None
None
975
1170
1235
100
100
100
A
A
A
3RV13 42-4KC10
3RV13 42-4LC10
3RV13 42-4MC10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.278
2.266
2.293
1) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
Auxiliary switches can be ordered separately
(see "Mountable Accessories").
2) For overload protection of the motors, appropriate overload relays must
be used.
Multi-unit/reusable packaging, see "Appendix" -->
"Ordering Notes".
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/9
5
Size S0
3RV Motor Starter Protectors up to 100 A
For transformer protection
■ Selection and ordering data
Class 10, without auxiliary switches
Motor starter protectors for the protection of transformers
with high inrush current.
Setting range
for thermal
overload
release
In
Instantaneous
overcurrent
release
I
v
Rated
current
Short-circuit
breaking
capacity
at 400 V AC
DT Screw connection
Order No.
Icu
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
A
A
A
kA
0.16
0.2
0.25
0.32
0.11 ... 0.16
0.14 ... 0.2
0.18 ... 0.25
0.22 ... 0.32
3.3
4.2
5.2
6.5
100
100
100
100
}
}
}
}
3RV14 21-0AA10
3RV14 21-0BA10
3RV14 21-0CA10
3RV14 21-0DA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.286
0.287
0.286
0.288
0.4
0.5
0.63
0.8
0.28 ... 0.4
0.35 ... 0.5
0.45 ... 0.63
0.55 ... 0.8
8.2
10
13
16
100
100
100
100
}
}
}
}
3RV14 21-0EA10
3RV14 21-0FA10
3RV14 21-0GA10
3RV14 21-0HA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.287
0.286
0.290
0.290
1
1.25
1.6
2
0.7 ... 1
0.9 ... 1.25
1.1 ... 1.6
1.4 ... 2
21
26
33
42
100
100
100
100
}
}
}
}
3RV14 21-0JA10
3RV14 21-0KA10
3RV14 21-1AA10
3RV14 21-1BA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.353
0.354
0.353
0.358
2.5
3.2
4
5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
52
65
82
104
100
100
100
100
}
}
}
}
3RV14 21-1CA10
3RV14 21-1DA10
3RV14 21-1EA10
3RV14 21-1FA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.354
0.358
0.354
0.357
6.3
8
10
12.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12.5
130
163
208
260
100
100
100
100
}
}
}
}
3RV14 21-1GA10
3RV14 21-1HA10
3RV14 21-1JA10
3RV14 21-1KA10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.356
0.358
0.362
0.360
16
20
11 ... 16
14 ... 20
286
325
50
50
}
}
3RV14 21-4AA10
3RV14 21-4BA10
1
1
1 unit
1 unit
101
101
0.365
0.365
16
20
25
32
40
11 ... 16
14 ... 20
18 ... 25
22 ... 32
28 ... 40
325
416
520
660
836
50
50
50
50
50
}
}
}
}
}
3RV14 31-4AA10
3RV14 31-4BA10
3RV14 31-4DA10
3RV14 31-4EA10
3RV14 31-4FA10
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
1.029
1.034
1.038
1.029
1.039
kg
5
Size S0
Size S2
Auxiliary switches can be ordered separately
(see "Mountable Accessories").
Multi-unit/reusable packaging, see "Appendix" -->
"Ordering Notes".
* You can order this quantity or a multiple thereof.
5/10
Siemens LV 1 · 2006
3RV Motor Starter Protectors up to 100 A
For fuse monitoring
■ Selection and ordering data
Without auxiliary switches
In
Instantaneous Short-circuit
overcurrent
breaking
release
capacity
at 400 V AC
I
DT Screw connection
Order No.
Icu
v
Rated current Thermal
overload
release
A
A
A
kA
0.2
0.2
1.2
100
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
Size S00
}
Type
Version
1 unit
101
0.289
The auxiliary switch required for signaling can be ordered
separately.
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Mountable auxiliary switches
Transverse auxiliary switches
with screw connection
1 NO + 1 NC
}
3RV19 01-1E
1
1 unit
101
0.018
Lateral auxiliary switches
with screw connection
1 NO + 1 NC
}
3RV19 01-1A
1
1 unit
101
0.045
3RV19 01-1E
3RV19 01-1A
For further auxiliary switches, see "Mountable accessories".
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/11
5
Multi-unit/reusable packaging, see "Appendix" -->
"Ordering Notes".
1
3RV16 11-0BD10
3RV Motor Starter Protectors up to 100 A
For plant protection according to
UL 489 / CSA C22.2 No. 5-02
■ Selection and ordering data
Class 10, without auxiliary switches
Motor starter protectors for plant protection according to UL/CSA.
Setting
range for
thermal
overload
release
(nonadjustable)
In
Instantaneous
overcurrent
release
I
v
Rated
current
Short-circuit
breaking
capacity
at 400 V AC
DT
Order No.
Icu
PU
(UNIT,
SET, M)
Screw connection
PS*
PG
Weight
per PU
approx.
Price
per PU
A
A
A
kA
10
15
10
15
150
225
100
100
B
B
3RV17 42-5AD10
3RV17 42-5BD10
1
1
1 unit
1 unit
101
101
2.200
2.200
20
25
30
35
20
25
30
35
260
325
390
455
100
100
100
100
B
B
B
B
3RV17 42-5CD10
3RV17 42-5DD10
3RV17 42-5ED10
3RV17 42-5FD10
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
2.200
2.200
2.200
2.200
40
45
50
40
45
50
520
585
650
100
100
100
B
B
B
3RV17 42-5GD10
3RV17 42-5HD10
3RV17 42-5JD10
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.200
2.200
2.200
60
70
60
70
780
910
100
100
B
B
3RV17 42-5LD10
3RV17 42-5PD10
1
1
1 unit
1 unit
101
101
2.200
2.200
kg
5
Size S3
* You can order this quantity or a multiple thereof.
5/12
Siemens LV 1 · 2006
3RV Motor Starter Protectors up to 100 A
For distance protection
■ Selection and ordering data
Voltage transformer circuit-breakers with auxiliary switches
In
Instantaneous Auxiliary
overcurrent
switch
release
integrated
in the
circuitbreaker,
transverse
I
A
A
A
1.4
2.5
3
1.4
2.5
3
6
10.5
20
Short-circuit DT Screw connection
breaking
capacity
at
400 V AC
Order No.
Icu
v
Rated Thermal
current overload
release
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
kA
Size S00
50
50
50
Version
B
}
}
1
1
1
3RV16 11-1AG14
3RV16 11-1CG14
3RV16 11-1DG14
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
1 unit
1 unit
1 unit
PS*
101
101
101
PG
0.314
0.318
0.315
Weight
per PU
approx.
kg
Laterally mountable auxiliary switches
for other signaling purposes
Lateral auxiliary switches
1 NO + 1 NC
}
3RV19 01-1A
1
1 unit
101
0.045
3RV19 01-1A
For further auxiliary switches, see "Mountable Accessories".
■ More information
Conversion of voltage transformer circuit-breakers 3VU13 to 3RV1
The 3VU13 voltage transformer circuit-breakers previously
available have been discontinued. The 3RV1 voltage
transformer circuit-breakers are offered as replacement types.
Previous type
Replacement type
3VU13 11-6HR00
3RV16 11-1CG14
3VU13 21-6HR00
3RV16 11-1CG14 + 3RV19 01-1A
3VU13 11-6JR00
3RV16 11-1DG14
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/13
5
Type
1 CO
1 CO
1 CO
3RV Motor Starter Protectors up to 100 A
Accessories
Mountable accessories
■ Overview
Mounting location and function
The 3RV1 motor starter protectors have three main contact
elements. In order to achieve maximum flexibility, auxiliary
switches, alarm switches, auxiliary releases and isolator
modules can be supplied separately.
Front
Transverse auxiliary switches
Notes:
1 NO + 1 NC
These components can be fitted as required on the motor starter
protectors without using tools.
An auxiliary contact block can be inserted transversely on the front.
The overall width of the motor starter protectors remains unchanged.
• A maximum of 4 auxiliary
or
contacts with auxiliary switches 2 NO
can be attached to each motor
or 1 changeover contact
starter protector.
• Transverse auxiliary switches
must not be used for the 3RV17
motor starter protectors.
Left-hand side
Lateral auxiliary switches
(2 contacts)
1 NO + 1 NC
or
2 NO
or
2 NC
Lateral auxiliary switches
(4 contacts)
2 NO + 2 NC
One of the three auxiliary switches can be mounted laterally for each motor starter
protector. The contacts of the auxiliary switch close and open together with the main
contacts of the motor starter protector.
The overall width of the lateral auxiliary switch with 2 contacts is 9 mm.
One auxiliary switch can be mounted laterally for each motor starter protector. The
contacts of the auxiliary switch close and open together with the main contacts of the
motor starter protector.
The overall width of the lateral auxiliary switch with 4 contacts is 18 mm.
Alarm switches for sizes S0, S2, One alarm switch can be mounted at the side of each motor starter protector with a
and S3
rotary operating mechanism.
5
Notes:
• Auxiliary switches (2 contacts)
Trip 1 NO + 1 NC
and alarm switches can be
mounted separately or together. Short-circuit 1 NO + 1 NC
• A maximum of 4 auxiliary
contacts with auxiliary switches
can be attached to each motor
starter protector.
The alarm switch has two contact systems.
One contact system always signals tripping irrespective of whether this was caused by
a short-circuit, an overload or an auxiliary release. The other contact system only
switches in the event of a short-circuit. There is no signaling as a result of switching off
with the handle.
In order to be able to switch on the motor starter protector again after a short-circuit, the
alarm switch must be reset manually after the error cause has been eliminated.
The overall width of the alarm switch is 18 mm.
Right-hand side
Shunt release
For remote-controlled tripping of the motor starter protector. The release coil should
only be energized for short periods (see schematics).
or
Undervoltage release
Trips the motor starter protector when the voltage is interrupted and prevents the motor
from being restarted accidentally when the voltage is restored. Used for remotecontrolled tripping of the motor starter protector.
Particularly suitable for EMERGENCY-STOP disconnection by way of the corresponding
EMERGENCY-STOP button according to DIN VDE 0113.
or
Notes:
• One auxiliary release can be
mounted per motor starter
protector.
Undervoltage release with
leading auxiliary contacts
(2 NO)
• Accessories cannot be mounted
at the right-hand side of the
3RV11 motor starter protectors
with overload relay function.
Top
Note:
The overall width of the auxiliary release is 18 mm.
Isolator modules for
motor starter protectors
The isolator module covers the Size S0 and S2
terminal screws of the
transverse auxiliary switch. If
the isolator module is used, we
therefore recommend that
either the lateral auxiliary
switches be fitted or that the
isolator module not be mounted
until the auxiliary switch has
been wired.
5/14
Function and use as for the undervoltage release without leading auxiliary contacts, but
with the following additional function: the auxiliary contacts will open in switch position
OFF to deenergize the coil of the undervoltage release, thus interrupting power
consumption. In the "tripped" position, these auxiliary contacts are not guaranteed to
open. The leading contacts permit the motor starter protector to reclose.
Siemens LV 1 · 2006
Isolator modules can be mounted to the upper terminal end of motor starter protectors
of sizes S0 and S2.
The supply cable is connected to the motor starter protector through the isolator
module.
The plug can only be unplugged when the motor starter protector is open and isolates
all 3 poles of the motor starter protector from the network. The shock-protected isolation
point is clearly visible and secured with a padlock to prevent reinsertion of the plug.
3RV Motor Starter Protectors up to 100 A
Accessories
NSB0_01426
5
Mountable accessories
Siemens LV 1 · 2006
5/15
3RV Motor Starter Protectors up to 100 A
Accessories
Mountable accessories
■ Selection and ordering data
Type
Version
For motor
starter
protectors
Size
DT Screw connection
Order No.
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
Auxiliary switches1)
3RV19 01-1E
3RV19 01-1G
S00, S0, S2, }
S3
}
}
3RV19 01-1D
3RV19 01-1E
3RV19 01-1F
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.015
0.018
0.018
1 CO
Solid-state compatible
transverse auxiliary
switches
with screw connection
for use in dusty atmosphere
and in solid-state circuits
with low operating currents
S00, S0, S2, A
S3
3RV19 01-1G
1
1 unit
101
0.016
Covering caps for
transverse auxiliary
switches
S00, S0, S2, A
S3
3RV19 01-0H
1
10 units
101
0.006
S00, S0, S2, }
S3
}
}
A
3RV19 01-1A
3RV19 01-1B
3RV19 01-1C
3RV19 01-1J
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.045
0.045
0.045
0.083
Transverse auxiliary
switches
with screw connection
1 CO
1 NO + 1 NC
2 NO2)
3RV19 01-0H
1 NO + 1 NC
2 NO
2 NC
2 NO +2 NC
5
Lateral auxiliary switches
with screw connection
3RV19 01-1A
3RV19 01-1J
1) Each motor starter protector can be fitted with one transverse and one
lateral auxiliary switch. The lateral auxiliary switch with 2 NO + 2 NC is
used without a transverse auxiliary switch.
Type
Version
2) Compatible with the following motor starter protectors:
3RV1. 1 (size S00) as of version E01
3RV1. 2 (size S0) as of version E04
3RV1. 3 (size S2) as of version E04
3RV1. 4 (size S3) as of version E04.
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Transverse auxiliary switches with Cage Clamp connection
1 NO + 1 NC
2 NO
}
}
3RV19 01-2E
3RV19 01-2F
1
1
1 unit
1 unit
101
101
0.017
0.018
1 lateral auxiliary switch can be mounted on 1 NO + 1 NC
the left for each motor starter protector
2 NO
2 NC
}
}
}
3RV19 01-2A
3RV19 01-2B
3RV19 01-2C
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.040
0.040
0.040
1 transverse auxiliary switch can be
mounted on each motor starter protector
Laterally mountable auxiliary switches with
Cage Clamp connection
* You can order this quantity or a multiple thereof.
5/16
Siemens LV 1 · 2006
3RV Motor Starter Protectors up to 100 A
Accessories
Mountable accessories
Type
Version
For motor
starter
protectors
Size
DT Screw connection
Order No.
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
Alarm switches1)
Alarm
switches
Separate tripped and
short-circuit alarms,
each 1 NO + 1 NC.
S0, S2, S3
}
3RV19 21-1M
1
1 unit
101
0.094
}
3RV19 28-1A
1
1 unit
101
0.157
A
3RV19 38-1A
1
1 unit
101
0.324
3RV19 21-1M
Isolator modules
Isolator
modules
Visible isolating distance S0
for isolating individual
S2
motor starter protectors
from the network,
lockable in isolating
position.
5
3RV19 38-1A
with padlock
1) One alarm switch can be mounted to the left of each motor starter
protector.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/17
3RV Motor Starter Protectors up to 100 A
Accessories
Mountable accessories
Rated control supply voltage Us
AC
AC
AC
AC/DC
DC
50
Hz
60
Hz
50/60 Hz
100%
ON-time1)
50/60 Hz,
DC
5s
ON-time2)
V
V
V
For motor
starter
protectors
Size
DT Screw connection
Order No.
V
V
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
Auxiliary releases3)
Undervoltage release
24
110
-
120
208
-
-
24
-
230
400
415
500
240
440
480
575
-
-
-
S00, S0, S2, A
S3
A
A
A
3RV19 02-1AB4
3RV19 02-1AB0
3RV19 02-1AF0
3RV19 02-1AM1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.138
0.134
0.134
0.128
}
}
A
A
3RV19 02-1AP0
3RV19 02-1AV0
3RV19 02-1AV1
3RV19 02-1AS0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.131
0.127
0.129
0.127
3RV19 02-1DP0
Undervoltage release with leading
auxiliary contacts 2 NO
3RV19 12-1CP0
230
400
415
240
480
-
-
-
S00
A
A
A
3RV19 12-1CP0
3RV19 12-1CV0
3RV19 12-1CV1
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.140
0.137
0.139
230
400
415
240
480
-
-
-
S0, S2, S3
A
A
A
3RV19 22-1CP0
3RV19 22-1CV0
3RV19 22-1CV1
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.139
0.136
0.138
20 ... 70
70 ... 190
190 ... 330
330 ... 500
500
-
S00, S0, S2, }
S3
A
}
A
A
3RV19 02-1DB0
3RV19 02-1DF0
3RV19 02-1DP0
3RV19 02-1DV0
3RV19 02-1DS0
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.133
0.135
0.130
0.129
0.126
Shunt releases
5
-
-
20 ... 24
90 ... 110
210 ... 240
350 ... 415
500
1) The voltage range is valid for 100 % (infinite) ON-time. The response
voltage is at 0.9 the lower limit of the voltage range.
2) The voltage range is valid for 5 s ON-time at AC 50 Hz/60 Hz and DC.
The response voltage is at 0.85 the lower limit of the voltage range.
3) One auxiliary release can be mounted to the right of each motor starter
protector.
* You can order this quantity or a multiple thereof.
5/18
Siemens LV 1 · 2006
3RV Motor Starter Protectors up to 100 A
Accessories
Busbar accessories
■ Overview
Insulated three-phase busbar systems
Three-phase busbar systems provide an easy, time-saving and
clearly arranged means of feeding 3RV1 motor starter protectors
with screw-type terminals. Different designs are available for
sizes S00, S0 and S2 and can be used for the various different
types of motor starter protectors. The only exceptions are the
3RV19 15 three-phase busbar systems, which are not suitable
for the 3RV11 motor starter protectors with overload relay
function.
The busbars are suitable for between 2 and 5 motor starter
protectors. However, any kind of extension is possible by
clamping the tags of an additional busbar (rotated by 180°)
underneath the terminals of the respective last motor starter
protector.
Busbars with larger modular spacing can be used for motor
starter protectors with laterally mounted accessories.
The motor starter protectors are supplied by appropriate lineside terminals.
3-phase busbar system, with example for combining sizes S00 and S0
Busbar adapters
The motor starter protectors are mounted directly with the aid of
busbar adapters on busbar systems with 40 mm and 60 mm
center-line spacing in order to save space and to reduce infeed
times and costs.
The three-phase busbar systems are finger-safe. They are
designed for any short-circuit stress which can occur at the load
side of connected motor starter protectors.
Busbar adapters for busbar systems with 40 mm center-line
spacing are suitable for copper busbars with a width of 12 mm
to 15 mm, while those with 60 mm center-line spacing are
suitable for copper busbars with a width of 12 mm to 30 mm.
The busbars can be 4 to 5 mm or 10 mm thick.
The three-phase busbar systems can also be used to construct
"Type E Starters" of size S0 or S2 according to UL/CSA. Special
feeder terminals must be used for this purpose, however (see
Selection and Ordering Data).
The motor starter protectors are snapped onto the adapter and
connected on the line side. This prepared unit is then plugged
directly onto the busbar system, and is thus connected both
mechanically and electrically at the same time.
3RV19 35-5A
Further busbar adapters for snap-mounting direct-on-line
starters and reversing starters as well as additional accessories
such as line terminals and outgoing terminals, busbar copper,
etc., can be found under "Distribution/Busbar Systems and
Controlgear".
3RV19 35-1C
NSB01074a
3RV19 35-1A
3RV19 35-6A
3RV19 15-5B
NSB0_01073c
3-phase busbar system, size S2
SIRIUS motor starter protectors and load feeders with busbar adapters
snapped onto busbars
The 3RV19 infeed system can be found under "Load Feeders,
Motor Starters and Soft Starters", "3RA Fuseless Load Feeders".
3RV19 15-6AB
3-phase busbar system, size S00
Siemens LV 1 · 2006
5/19
5
Different sized motor starter protectors cannot be clamped
together due to the different dimensions. Special connectors are
available for connecting three-phase busbars for S0 motor
starter protectors to busbars for S00 motor starter protectors.
3RV Motor Starter Protectors up to 100 A
Accessories
Busbar accessories
■ Selection and ordering data
Modular Number of motor starter
spacing protectors that can be
connected
without
lateral
accessories
with
with
lateral
auxiliary
auxiliary release
switch
mm
Rated
current
In at
690 V
For
DT Order No.
motor
starter
protectors
Size
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
A
kg
3-phase busbar systems
For feeding several motor starter protectors with screwtype connection, mounted side-by-side on standard
mounting rails, insulated, with touch protection.
3RV19 15-1AB
45
2
3
4
5
-
-
63
S00,
S01)
}
}
}
}
3RV19 15-1AB
3RV19 15-1BB
3RV19 15-1CB
3RV19 15-1DB
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.044
0.071
0.099
0.124
55
-
2
3
4
5
-
63
S00,
S01)
}
}
}
}
3RV19 15-2AB
3RV19 15-2BB
3RV19 15-2CB
3RV19 15-2DB
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.048
0.079
0.111
0.140
63
-
-
2
4
63
S00,
S01)
}
}
3RV19 15-3AB
3RV19 15-3CB
1
1
1 unit
1 unit
101
101
0.052
0.120
55
2
3
4
-
-
108
S2
}
}
}
3RV19 35-1A
3RV19 35-1B
3RV19 35-1C
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.140
0.214
0.295
75
-
2
3
4
2
3
4
108
S22)
A
A
A
3RV19 35-3A
3RV19 35-3B
3RV19 35-3C
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.161
0.262
0.369
3RV19 15-1BB
3RV19 15-1CB
5
3RV19 15-1DB
2) Auxiliary releases and lateral auxiliary switches cannot be used in
combination.
1) Not suitable for 3RV11 motor starter protectors with overload relay
function. Common clamping of S00 and S0 motor starter protectors is not
possible, due to the different modular spacings and terminal heights. The
3RV19 15-DB connector is available for connecting busbars from size S0
to size S00.
Version
Modular
spacing
For motor
starter
protectors
Size
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
mm
kg
Connectors for 3-phase busbars
3RV19 15-5DB
45
For connecting threephase busbars for motor
starter protectors of size
S0 (left) to size S00 (right)
S00, S0
}
Conductor cross-section
For
motor
starter
protectors
Size
DT Order No.
Solid or
stranded
Finely
stranded
with end
sleeve
AWG
conductors,
solid or
stranded
mm²
mm²
AWG
1
3RV19 15-5DB
Price
per PU
PU
(UNIT,
SET, M)
1 unit
PS*
101
PG
0.042
Weight
per PU
approx.
kg
3-phase line-side terminals
Connection from top
2.5 ... 25
4 ... 16
S00
}
3RV19 15-5A
1
1 unit
101
0.043
S0
}
3RV19 25-5AB
1
1 unit
101
0.041
12-4
S00, S0
}
3RV19 15-5B
1
1 unit
101
0.110
14-0
S2
}
3RV19 35-5A
1
1 unit
101
0.115
C
}
3RV19 25-5EB
3RV19 35-5E
1
1
1 unit
1 unit
101
101
0.055
0.100
12-4
Connection from below1)
3RV19 25-5AB
2.5 ... 25
4 ... 16
Connection from top
2.5 ... 50
1.5 ... 35
3RV19 15-5B
3-phase line-side terminals for constructing "Type E Starters"
Connection from top
2.5 ... 25
10 ... 50
4 ... 16
-
10-4
8-0
S0
S2
1) This terminal is connected in place of a switch, please take the spacing
into account.
* You can order this quantity or a multiple thereof.
5/20
Siemens LV 1 · 2006
3RV Motor Starter Protectors up to 100 A
Accessories
Busbar accessories
Version
For motor starter DT Order No.
protectors
Size
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Covers for connection tags
Touch protection for empty
positions
3RV19 15-6AB
S00, S0
}
3RV19 15-6AB
1
10
units
101
0.003
S2
}
3RV19 35-6A
1
5 units
101
0.006
Busbar adapters
8US10 61-5DJ07
For motor starter
protectors
Size
8US12 51-5MD07
Rated
current
Connec- Adapter Adapter Rated
tion
length
width
voltage
cable
A
AWG
mm
mm
V
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Busbar adapters for 40 mm systems
S00, S0
S00, S0 + lateral
auxiliary switch
S2
S3
S3
5
For copper busbars according to DIN 46433
Width: 12 mm and 15 mm
Thickness: 5 mm and 10 mm
25
25
12
12
121
121
45
55
690
690
}
}
8US10 51-5DJ07
8US10 61-5DJ07
1
1
1 unit
1 unit
103
103
0.106
0.119
56
100
100
8
4
4
139
182
182
55
70
72
690
4001)
480 ... 6902)
}
}
}
8US10 61-5FK08
8US11 11-4SM00
8US10 11-4TM00
1
1
1
1 unit
1 unit
1 unit
103
103
103
0.231
0.541
0.478
45
55
70
72
690
690
4001)
480 ... 6902)
}
}
}
A
8US12 51-5DM07
8US12 61-5FM08
8US11 11-4SM00
8US12 11-4TM00
1
1
1
1
1 unit
6 units
1 unit
1 unit
103
103
103
103
0.183
0.263
0.541
0.498
Busbar adapters for 60 mm systems
For copper busbars according to DIN 46433
Width: 12 mm and 30 mm
Thickness: 5 mm and 10 mm
also for T and double-T special profiles
S00, S0
S2
S3
S3
25
56
100
100
12
8
4
4
182
1) Up to 460 V AC with max. short-circuit breaking capacity 25 kA.
2) Cannot be used for voltages < 480 V AC
Short-circuit breaking capacity 480 V/ 500 V/ 525 V AC:
- up to In = 25 A: max. 30 kA
- up to In = 90 A: max. 16 kA
- up to In = 100 A: max. 6 kA
Short-circuit breaking capacity 690 V AC:
- max. 12 kA.
For more busbar adapters, see "SIVACON Switchgear,
Distribution Systems and Cabinets " -->
"Components for Distribution Systems 8US, 8UC, 4NC"
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/21
3RV Motor Starter Protectors up to 100 A
Accessories
Rotary operating mechanisms
■ Overview
Door-coupling rotary operating mechanisms
Motor starter protectors with a rotary operating mechanism can
be mounted in a control cabinet and operated externally by
means of a door-coupling rotary operating mechanism. When
the cabinet door with motor starter protector is closed, the
operating mechanism is coupled. When the motor starter
protector closes, the coupling is locked which prevents the door
from being opened unintentionally. This lock can be defeated by
the maintenance personnel. In the Open position, the rotary
operating mechanism can be secured against reclosing with up
to 3 padlocks. Inadvertent opening of the door is not possible in
this case either.
Remote motorized operating mechanisms
3RV1 motor starter protectors are manually operated controls.
They automatically trip in case of an overload or short-circuit.
Intentional remote-controlled tripping is possible by means of a
shunt release or an undervoltage release. Reclosing is only
possible directly at the motor starter protector.
The remote motorized operating mechanism allows the motor
starter protectors to be opened and closed by electrical
commands. This enables a load or an installation to be isolated
from the power system or reconnected to it from an operator
panel.
NSB01078
If the motor starter protector is tripped as a result of overload or
short-circuit, it will be in tripped position. For reclosing, the
remote motorized operating mechanism must first be set
manually or electrically to the 0 position (electrically by means of
the Open command). Then it can be reclosed.
The remote motorized operating mechanism is available for
motor starter protectors of size S2 (Inmax = 50 A) and S3
(Inmax = 100 A) that are designed for control voltages of
230 V AC and 24 V DC. The motor starter protector is fitted into
the remote motorized operating mechanism as shown in the
drawing.
5
In the "MANUAL" position, the motor starter protector in the
remote motorized operating mechanism can continue to be
switched manually on site. In the "AUTOMATIC" position, the
motor starter protector is switched by means of electrical
commands. The switching command must be applied for a
minimum of 100 ms. The remote motorized operating
mechanism closes the motor starter protector after a maximum
of 1 second. On voltage failure during the switching operation it
is ensured that the motor starter protector remains in the Open
or Closed position.
3RV19 26-0K door-coupling rotary operating mechanism
Reset function
NSB01079
The RESET button on the motorized operating mechanism
serves to reset any 3RV19 21-1M alarm switch that might be
installed.
3RV19 26-2B door-coupling rotary operating mechanism for arduous
conditions
5/22
Siemens LV 1 · 2006
3RV Motor Starter Protectors up to 100 A
Accessories
Rotary operating mechanisms
■ Selection and ordering data
Type
Color of
knob
Version
For motor DT Order No.
Extension starter
shaft
protectors
Size
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
mm
kg
Door-coupling rotary operating mechanisms
The door-coupling rotary operating mechanisms consist of a knob, a coupling driver and an extension shaft of 130/330 mm in
length (5 x 5 mm). The door-coupling rotary operating mechanisms are designed to the degree of protection IP65. The door
locking device prevents accidental opening of the control cabinet door in the ON position of the motor starter protector. The OFF
position can be locked with up to 3 padlocks.
3RV19 26-0B
Door-coupling Black
rotary
operating
mechanisms
130
330
S0, S2, S3 }
}
3RV19 26-0B
3RV19 26-0K
1
1
1 unit
1 unit
101
101
0.111
0.324
EMERGENCY- Red/
Yellow
STOP doorcoupling
rotary
operating
mechanisms
130
330
S0, S2, S3 }
}
3RV19 26-0C
3RV19 26-0L
1
1
1 unit
1 unit
101
101
0.110
0.316
Door-coupling rotary operating mechanisms, for arduous
conditions
3RV19 26-2C
Door-coupling Gray
rotary
mechanisms
300
S0
S2
S3
}
}
}
3RV19 26-2B
3RV19 36-2B
3RV19 46-2B
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.180
1.570
1.722
EMERGENCY- Red/
Yellow
STOP doorcoupling
rotary
operating
mechanisms
300
S0
S2
S3
}
}
}
3RV19 26-2C
3RV19 36-2C
3RV19 46-2C
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.188
1.486
1.732
Type
Rated control
supply voltage Us
For motor DT Order No.
starter
protectors
Size
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Remote motorized operating mechanisms
Remote
motorized
operating
mechanisms
50/60 Hz, 230 V AC
24 V DC
S2
S2
B
B
3RV19 36-3AP0
3RV19 36-3AB4
1
1
1 unit
1 unit
101
101
3.520
3.420
50/60 Hz, 230 V AC
24 V DC
S3
S3
B
B
3RV19 46-3AP0
3RV19 46-3AB4
1
1
1 unit
1 unit
101
101
3.441
3.357
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/23
5
The door-coupling rotary operating mechanisms consist of a knob, a coupling driver, an extension shaft of 300 mm in length
(8 x 8 mm), a spacer and two metal brackets, into which the motor starter protector is inserted. The door-coupling rotary operating
mechanisms are designed to degree of protection IP65. The door locking device reliably prevents opening of the control cabinet
door in the ON position of the circuit-breaker. The OFF position can be locked with up to 3 padlocks. Laterally mountable auxiliary
releases and two-pole auxiliary switches can be used. The door-coupling rotary operating mechanism thus meets the
requirements for isolating functions to IEC 60947-2.
3RV Motor Starter Protectors up to 100 A
Accessories
Mounting accessories
■ Overview
The 3RV19 28-1H terminal block must be used here for size S0;
it is simply screwed onto the basic unit.
Soldering terminal
Soldering terminals are available for the main contacts and
transverse auxiliary switches of size S00 motor starter
protectors.
Basic units of size S2 are already compliant with the new
clearance and creepage distance requirements.
NSB01379a
NSB0_01077a
5
NSB01380a
The 3RT19 46-4GA07 terminal block must be used for size S3.
The standard box terminal is to be replaced by this terminal
block.
The prepared terminal parts are clamped to the upper and lower
screw terminals of the motor starter protectors which allows
them to be soldered into printed circuit boards.
3RV19 18-5A
3RV19 28-1H (left), 3RT19 46-4GA07 (right)
Terminals for "Self-Protected Combination Motor Controller
(Type E)" according to UL508
According to CSA, these modular terminals can be omitted
when the device is used as a "Self-Protected Combination Motor
Controller" (Type E).
The 3RV10 motor starter protectors are approved according to
UL508 as a "Self-Protected Combination Motor Controllers
(Type E)".
Three-phase line-side terminals are required for constructing
"Type E Starters" with an insulated busbar system (see Busbar
Accessories).
As of 16 July 2001, for this application, UL 508 demands
increased clearance and creepage distances (1 inch and
2 inches respectively) at the line side of the device.
■ Selection and ordering data
Version
For motor
starter
protectors
Size
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Covers
3RV1 (size S3) with
3RT19 46-4EA1 (left)
3RV19 08-0P (right)
Terminal covers for box terminals
Additional touch protection for fitting
to box terminals
(2 units can be mounted per
motor starter protector)
S2
S3
}
}
3RT19 36-4EA2
3RT19 46-4EA2
1
1
1 unit
1 unit
101
101
0.016
0.023
Terminal covers
For cable lug and bar connection for
maintaining the required voltage
clearance and as touch protection if
box terminal is removed (2 units can
be mounted per motor starter
protector)
S3
}
3RT19 46-4EA1
1
1 unit
101
0.037
Scale covers
Sealable,
for covering
the set current scale.
S0, S0, S2, }
S3
100
10 units
101
0.100
3RV19 08-0P
* You can order this quantity or a multiple thereof.
5/24
Siemens LV 1 · 2006
3RV Motor Starter Protectors up to 100 A
Accessories
Mounting accessories
Type
Version
For motor
starter
protectors
Size
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Fixing accessories
For screwing the motor S00, S0
starter protector onto
mounting plates.
For each motor starter
protector, 2 units are
required.
}
3RB19 00-0B
100
10 units
101
0.100
For main
contacts
For soldering the main S00
conductor crosssections of a motor
starter protector to a
printed circuit board
(1 set = 2 parts for
1 motor starter
protector)
B
3RV19 18-5A
1
4 sets
101
0.030
For main and
auxiliary
contacts
For soldering the main S00
conductor connections
and the auxiliary
conductor connections
of the transverse
auxiliary switch 1NO +
1NC of a motor starter
protector to a printed
circuit board (1 set =
3 parts for 1 motor
starter protector)
B
3RV19 18-5B
1
4 sets
101
0.044
Type
Version
DT Order No.
Push-in lugs
3RB19 00-0B
Soldering terminals
5
3RV19 18-5A with
motor starter
protector
For motor
starter
protectors
Size
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Terminals for "Self-Protected Combination Motor Controller
(Type E)" according to UL508
Note: As of 16 July 2001, UL508 demands for "Combination Motor Controller Type E" 1-inch clearance and 2-inch creepage distance at
line side. The following terminal blocks must be used in 3RV10 motor starter protectors of sizes S0 and S3. The 3RV10 motor starter
protector in size S2 conforms with the required clearance and creepage distances without a terminal block. Terminal blocks are not
required for use according to CSA. With size S0, these terminal blocks cannot be used in combination with 3RV19.5 three-phase
busbars and with size S3, they cannot be used with a transverse auxiliary switch. For construction with 3-phase busbars,
see "Busbar Accessories".
3RV19 28-1H
Terminal blocks For extended
Type E
clearance and
creepage distances
(1-inch and 2-inch
respectively)
S0
S3
}
A
Type
For motor
starter
protectors
Size
DT Order No.
1
1
3RV19 28-1H
3RT19 46-4GA07
1 unit
1 unit
101
101
0.083
0.155
PS*
PG
Weight
per PU
approx.
3RT19 46-4GA07
Price
per PU
PU
(UNIT,
SET, M)
kg
Auxiliary terminals, 3-pole
For connection of auxiliary and control
cables to the main conductor
connections (for one side)
S3
B
3RT19 46-4F
1
1 unit
101
0.033
3RT19 46-4F
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/25
3RV Motor Starter Protectors up to 100 A
Accessories
Mounting accessories
Version
Method of Size
operation Contactor Motor
starter
protector
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Link modules, single unit packaging
3RA19 11-1AA00
AC/DC
For mechanical
and electrical
connection
AC
between contactor
and motor starter
protector with
screw connection DC
S00
S00
S00
S0
}
}
3RA19 11-1AA00
3RA19 21-1DA00
1
1
1 unit
1 unit
101
101
0.027
0.028
S0
S2
S3
S0
S2
S3
}
}
}
3RA19 21-1AA00
3RA19 31-1AA00
3RA19 41-1AA00
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.037
0.042
0.090
S0
S2
S3
S0
S2
S3
}
}
}
3RA19 21-1BA00
3RA19 31-1BA00
3RA19 41-1BA00
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.039
0.043
0.089
S00
S00
S00
S0
}
}
3RA19 11-1A
3RA19 21-1D
1
1
10 units
10 units
101
101
0.019
0.021
S0
S2
S3
S0
S2
S3
}
}
}
3RA19 21-1A
3RA19 31-1A
3RA19 41-1A
1
1
1
10 units
5 units
5 units
101
101
101
0.028
0.033
0.072
S0
S2
S3
S0
S2
S3
}
}
}
3RA19 21-1B
3RA19 31-1B
3RA19 41-1B
1
1
1
10 units
5 units
5 units
101
101
101
0.030
0.034
0.073
S00
S00
S00
S0
}
}
3RA19 11-2FA00
3RA19 21-2FA00
1
1
1 unit
1 unit
101
101
0.038
0.028
S00
S00
S00
S0
}
}
3RA19 11-2F
3RA19 21-2F
1
1
10 units
10 units
101
101
0.031
0.030
Link modules, multi-unit packaging
AC/DC
For mechanical
and electrical
connection
AC
between contactor
and motor starter
protector with
screw connection DC
3RA19 31-1A
5
Hybrid link modules, single-unit packaging
3RA19 11-2FA00
AC/DC
Electrical and
mechanical connection between
motor starter
protector with
screw terminals
and contactor with
Cage Clamp
terminals
Hybrid link modules, multi-unit packaging
3RA19 11-2F
AC/DC
Electrical and
mechanical connection between
motor starter
protector with
screw terminals
and contactor with
Cage Clamp
terminals
* You can order this quantity or a multiple thereof.
5/26
Siemens LV 1 · 2006
3RV Motor Starter Protectors up to 100 A
Accessories
Mounting accessories
Type
Version
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Adapters and link modules for Cage Clamp connections
3RA19 11-2A +
8US10 51-5CM47
Link modules,
Cage Clamp
Electrical connection between
motor starter protector and
contactor (busbar adapter not
included in scope of supply)
Size S00
}
3RA19 11-2A
1
10 units
101
0.016
Link modules,
Cage Clamp with mechanical
connections
Mechanical and electrical
connection between motor starter
protector and contactor
Size S00
}
3RA19 11-2E
1
10 units
101
0.028
Adapters for rail mounting
With 2 mounting rails 45 mm wide,
one adjustable
Size S00
}
3RA19 22-1L
1
5 units
101
0.413
Busbar adapters
45 mm wide, 182 mm long, adapted
for Cage Clamp motor starter
protectors. An additional mounting
rail must be mounted for an
additional contactor.
40 mm busbar
system
60 mm busbar
system
}
8US10 51-5CM47
1
1 unit
103
0.193
}
8US12 51-5CM47
1
1 unit
103
0.190
A
8US19 98-7CA15
1
10 units
103
0.009
5
35 mm standard mounting rails
Plastic, including fixing screws
3RA19 11-2E
Type
Version
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Tools for opening Cage Clamp connections
For all SIRIUS devices with Cage
Clamp connection, up to max.
2.5 mm² conductor cross-section
Length
}
approx. 175 mm
Length; partially }
insulated
approx. 175 mm
8WA2 880
1
1 unit
041
0.012
8WA2 803
1
1 unit
041
0.024
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/27
3RV Motor Starter Protectors up to 100 A
Accessories
Enclosures and front plates
■ Overview
Enclosures
For installing motor starter protectors of sizes S00 (Inmax = 12 A),
S0 (Inmax = 25 A) and S2 (Inmax = 50 A) as a single unit, moldedplastic enclosures for surface mounting and molded-plastic
enclosures for flush mounting are available in various
dimensions.
When installed in a molded-plastic enclosure the motor starter
protectors have a rated operational voltage Ue of 500 V
The enclosures for surface mounting have the degree of
protection IP55; the enclosures for flush mounting also comply
with the degree of protection IP55 at the front (the flush-mounted
section complies with IP20).
by using a special key. The motor starter protector can
subsequently be switched on again.
The molded-plastic enclosures of S0 and S2 motor starter
protectors with rotary operating mechanism are fitted with a
rotary operating mechanism as well.
The enclosures can be supplied with a black rotary operating
mechanism or with an EMERGENCY-STOP rotary operating
mechanism with a red/yellow knob.
All rotary operating mechanisms can be locked in the Open
position with up to 3 padlocks.
Front plates
The front plates for size S00 have a retaining frame into which the
motor starter protectors can be snapped. A retaining frame for
size S0 motor starter protectors is available for front plate sizes
S0 to S3.
5
NSB01080
Motor starter protectors are frequently required to be actuated in
any enclosure. Front plates equipped with an actuating
diaphragm for size S00 motor starter protectors, or rotary
operating mechanism for S0 to S3 motor starter protectors are
available for this purpose.
NSB01081
Enclosure for surface mounting
Front plate for size S00
Accessories for enclosures and front plates
Enclosure for flush mounting
All enclosures are equipped with N and PE/ground terminals.
There are two knock-out cable entries for cable glands at the top
and two at the bottom; also on the rear corresponding cable
entries are scored. There is a knock-out on the top of the
enclosure for indicator lights that are available as accessories.
The narrow enclosure can accommodate a motor starter
protector without accessories, with transverse and lateral
auxiliary switch, whereas wide enclosures and enclosures for S2
motor starter protectors also provide space for a laterally
mounted auxiliary release. There is no provision for installing a
motor starter protector with an alarm switch.
With S00 motor starter protectors, the switch rocker is operated
by means of the actuator diaphragm of the enclosure. A locking
device, capable of holding up to three padlocks, can be fitted
onto the actuator diaphragm to prevent the motor starter
protector from closing during maintenance work, for example.
A mushroom-shaped EMERGENCY-STOP knob can be fitted in
place of the locking device. If it is actuated abruptly, the motor
starter protector opens and the mushroom-shaped knob
latches. The knob can be unlatched again either by turning it or
5/28
Siemens LV 1 · 2006
3RV Motor Starter Protectors up to 100 A
Accessories
Enclosures and front plates
■ Selection and ordering data
Type
Degree Inteof pro- grated
tection terminals
Overall width
For motor DT Order No.
starter
protectors
Size
Price
PU
per PU (UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
With
actuator
diaphragm
IP55
N and
PE/
ground
3RV19 13-1DA00
With rotary IP55
operating
mechanism,
lockable in
0 position
N and
PE/
ground
3RV19 23-1CA00
With EMER- IP55
GENCYSTOP
rotary
operating
mechanism,
lockable in
0 position
N and
PE/
ground
}
3RV19 13-1CA00
1
1 unit
101
0.296
}
3RV19 13-1DA00
1
1 unit
101
0.342
}
3RV19 23-1CA00
1
1 unit
101
0.332
}
3RV19 23-1DA00
1
1 unit
101
0.381
S2
A
3RV19 33-1DA00
1
1 unit
101
1.134
S0
}
3RV19 23-1FA00
1
1 unit
101
0.329
}
3RV19 23-1GA00
1
1 unit
101
0.372
S2
A
3RV19 33-1GA00
1
1 unit
101
1.136
54 mm
(for motor starter
protector + lateral
auxiliary switch)
72 mm
(for motor starter
protector + lateral
auxiliary switch +
auxiliary release)
S00
54 mm
(for motor starter
protector + lateral
auxiliary switch)
72 mm
(for motor starter
protector + lateral
auxiliary switch +
auxiliary release)
82 mm
(for motor starter
protector + lateral
auxiliary switch +
auxiliary release)
S0
54 mm
(for motor starter
protector + lateral
auxiliary switch)
72 mm
(for motor starter
protector + lateral
auxiliary switch +
auxiliary release)
82 mm
(for motor starter
protector + lateral
auxiliary switch +
auxiliary release)
Cast aluminum enclosures for surface mounting
With rotary IP65
operating
mechanism,
lockable in
0 position
PE1)
72 mm
(for motor starter
protector + lateral
auxiliary switch +
auxiliary release)
S0
}
3RV19 23-1DA01
1
1 unit
101
1.015
3RV19 23-1DA01 With EMER- IP65
GENCYSTOP rotary
operating
mechanism,
lockable in
0 position
PE1)
72 mm
(for motor starter
protector + lateral
auxiliary switch +
auxiliary release)
S0
A
3RV19 23-1GA01
1
1 unit
101
1.008
Molded-plastic enclosures for flush mounting
IP55
(front
side)
N and
PE/
ground
72 mm
(for motor starter
protector + lateral
auxiliary switch +
auxiliary release)
S00
A
3RV19 13-2DA00
1
1 unit
101
0.416
With rotary IP55
(front
operating
mechanism, side)
lockable in
0 position
N and
PE/
ground
72 mm
(for motor starter
protector + lateral
auxiliary switch +
auxiliary release)
S0
A
3RV19 23-2DA00
1
1 unit
101
0.426
With EMER- IP55
3RV19 23-2DA00 GENCY(front
STOP rotary side)
operating
mechanism,
lockable in
0 position
N and
PE/
ground
72 mm
(for motor starter
protector + lateral
auxiliary switch +
auxiliary release)
S0
A
3RV19 23-2GA00
1
1 unit
101
0.417
With
actuator
diaphragm
3RV19 13-2DA00
1) If required, an additional N terminal can be mounted
(e.g. 8WA10 11-1BG11).
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/29
5
Molded-plastic enclosures for surface mounting
3RV Motor Starter Protectors up to 100 A
Accessories
Enclosures and front plates
Type
Degree Version
of protection
For motor DT Order No.
starter
protectors
Size
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Front plates
Molded-plastic
front plates
with actuator
diaphragm
IP55
(front
side)
S00
For actuating
motor starter
protectors in any
enclosures,
includes holder
for motor starter
protector.
A
3RV19 13-4C
1
1 unit
101
0.216
Molded-plastic
front plates with
rotary operating
mechanism
Lockable in
0 position
IP55
(front
side)
S0, S2,
For actuating
S3
3RV1 motor
starter protectors
in any
enclosures.
}
3RV19 23-4B
1
1 unit
101
0.124
IP55
Molded-plastic
(front
front plates with
side)
EMERGENCYSTOP rotary
operating
mechanism
Red/Yellow, lockable
in 0 position
S0, S2,
EMERGENCYSTOP actuation S3
of 3RV1 motor
starter protectors
in any enclosure.
A
3RV19 23-4E
1
1 unit
101
0.124
S0
Holder is
mounted on front
plate, motor
starter protector
with and without
accessories is
snapped in.
}
3RV19 23-4G
1
1 unit
101
0.188
S00
}
3RV19 13-7D
1
1 unit
101
0.108
IP55
EMERGENCYSTOP mushroom
Molded-plastic
buttons red/yellow
enclosure for surface with safety lock
mounting with
For 3RV19 13-...
3RV19 13-7D
enclosures and front
plates,
cannot be used in
combination with
locking device
S00
Latching
mushroom
button, unlatch
with key,
Ronis safety lock,
lock number
SB 30, supplied
with 2 keys.
A
3RV19 13-7E
1
1 unit
101
0.144
IP55
Locking devices
For 3RV19 13-...
enclosures and front
plates, cannot be
used in combination
with EMERGENCYSTOP mushroom
button
For 3 padlocks
S00
with max. 8 mm
shackle diameter.
}
3RV19 13-6B
1
1 unit
101
0.074
S00
A
3RV19 13-7F
1
1 unit
101
0.023
3RV19 13-4C
3RV19 23-4B +
3RV19 23-4G
5
Holders for
front plate
For motor starter
protectors
size S0
-
Accessories for enclosures
IP55
EMERGENCYSTOP mushroom
buttons red/yellow
For 3RV19 13-...
enclosures and front
plates, cannot be
used in combination
with locking device
Spare actuator
diaphragms
Type
IP55
Version
Latching
mushroom
button, unlatch
by turning
Diaphragm,
includes holder
frame and
screws
Rated
control
supply
voltage Us
For motor DT Order No.
starter
protectors
Size
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
V
kg
Indicator Lights
Indicator
lights
For all
enclosures
and front
plates
With glow lamp
and colored
lenses red,
green, yellow,
orange and
clear
110 ... 120
220 ... 240
380 ... 415
480 ... 500
S00, S0,
S2
C
C
C
C
3RV19 03-5B
3RV19 03-5C
3RV19 03-5E
3RV19 03-5G
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.027
0.026
0.026
0.027
3RV19 03-5B
* You can order this quantity or a multiple thereof.
5/30
Siemens LV 1 · 2006
Overload Relays
General data
■ Overview
Features
Benefits
3RU11
3RB20/3RB21
3RB22/3RB23
S00 ... S12
S00 ... S12
0.1 ... 630 A
0.3 ... 630 A
( ... 820 A)1)
General data
Sizes
• Are coordinated with the dimensions, connections S00 ... S3
and technical characteristics of the other devices
in the SIRIUS modular system (contactors, soft
starters, ...)
• Permit the mounting of slim and compact load
feeders in widths of 45 mm (S00), 45 mm (S0),
55 mm (S2), 70 mm (S3), 120 mm (S6) and
145 mm (S10/S12)
• Simplify configuration
Seamless current range
• Allows easy and consistent configuration with one 0.11 ... 100 A
series of overload relays (for small to large loads)
Protective functions
• Provides optimum current-dependent protection
of loads against excessive temperature rises due
to overload
✔
✔
✔
Tripping in the event of phase
unbalance
• Provides optimum inverse-time delayed protection
of loads against excessive temperature rises due
to phase unbalance
(✔)
✔
✔
Tripping in the event of phase failure
• Minimizes heating of three-phase motors during
single-phase operation2)
✔
✔
✔
Tripping in the event of overheating
• Provides optimum temperature-dependent
protection of loads against excessive temperature
rises e.g. for stator-critical motors or in the event of
insufficient coolant flow, contamination of the
motor surface or for long starting or braking
operations
-- 3)
-- 3)
✔
--
✔
(only 3RB21)
✔
by means of
integrated thermistor motor
protection function
5
Tripping in the event of overload
• Eliminates the need for additional special
equipment
• Saves space in the controlgear cabinet
• Reduces wiring overhead and costs
Tripping in the event of a ground fault • Provides optimum protection of loads against
high-resistance short-circuits or ground faults due
to moisture, condensed water, damage to the
by means of
insulation material, etc.
internal ground fault detection
• Eliminates the need for additional special
(activatable)
equipment.
• Saves space in the controlgear cabinet
• Reduces wiring overhead and costs
Features
RESET function
• Allows manual or automatic resetting of the relay
✔
✔
✔
TEST function for auxiliary contacts
• Allows easy checking of the function and wiring
✔
✔
✔
TEST function for electronics
• Allows complete checking of the electronics
--
✔
✔
Status display
• Displays the current operating status
✔
✔
✔
Large current adjustment button
• Makes it easier to set the relay exactly to the
correct current value
✔
✔
✔
Integrated auxiliary contacts
(1 NO + 1 NC)
• Allows the load to be switched off if necessary
✔
✔
✔
(2 ×)
• Can be used to output signals
1) For motor currents up to 820 A, a current measuring module, e.g.
0.3 ... 3 A, can be used in combination with a 3UF18 series transformer.
2) Single-phase operation: Abnormal operating status of a three-phase
asynchronous motor where one phase is interrupted.
3) The SIRIUS 3RN thermistor motor protection devices can be used to
provide additional protection temperature-dependent protection.
Siemens LV 1 · 2006
5/31
Overload Relays
General data
Features
Benefits
3RU11
3RB20/3RB21
3RB22/3RB23
Design of load feeders
• Provides optimum protection of the loads and
Short-circuit strength up to 100 kA
operating personnel in the event of short-circuits
at 690 V
due to insulation faults or faulty switching
(in conjunction with the corresponding
fuses or the corresponding motor starter operations
protector)
Electrical and mechanical matching
to 3RT1 contactors
• Simplifies configuration
✔
✔
✔
✔
✔
✔1)
--
✔
(S2 ... S6)
✔
(S00 ... S6)
✔
(S00)
--
--
✔
✔
✔
✔
✔
✔
(✔)
✔
✔
--
✔
(1:4)
✔
(1:10)
• Reduces wiring overhead and costs
5
• Enables stand-alone installation as well as
space-saving direct mounting
Straight-through transformers for
main circuit2)
(in this case the cables are routed
through the push-through openings of
the overload relay and connected
directly to the box terminals of the
contactor)
• Reduces contact resistance
(only one point of contact)
Spring-loaded terminal connection
system for main circuit2)
• Enables fast connections
• Saves wiring costs (easy, no need for tools,
and fast).
• Saves material costs
• Reduces installation costs
• Permits vibration-resistant connections
• Enables maintenance-free connections
Spring-loaded terminal connection
system for auxiliary circuits2)
• Enables fast connections
• Permits vibration-resistant connections
• Enables maintenance-free connections
Other features
Temperature compensation
• Allows the use of the relays at high temperatures
without derating
• Prevents premature tripping
• Allows compact installation of the controlgear
cabinet without space between the units/load
feeders
• Simplifies configuration
• Enables space to be saved in the controlgear
cabinet
Very high long-term stability
• Provides safe protection for the loads even after
years of use in severe operating conditions
Wide setting ranges
• Reduce the number of variants
• Minimize the engineering outlay and costs
• Minimize storage overhead, storage costs,
tied-up capital
Trip class CLASS 5
• Enables solutions for very fast starting motors
requiring special protection (e.g. Ex motors)
--
✔
(only 3RB21)
✔
Trip class > CLASS 10
• Enables heavy starting solutions
--
✔
✔
Low power loss
• Reduces power consumption and energy costs
(up 98% less power is used than for thermal
overload relays).
--
✔
✔
• Minimizes temperature rises of the contactor and
controlgear cabinet – in some cases this may
eliminate the need for controlgear cabinet cooling.
• Direct mounting to contactor saves space, even
for high motor currents (i.e. no heat decoupling is
required).
1) Exception: up to size S3, only stand-alone installation is possible.
2) Alternatively available for screw connection.
5/32
Siemens LV 1 · 2006
Overload Relays
General data
Benefits
3RU11
3RB20/3RB21
3RB22/3RB23
5
Features
1) The SIRIUS 3RU11 thermal overload relays use a bimetal contactor and
therefore do not require an additional control circuit.
Siemens LV 1 · 2006
5/33
Overload Relays
General data
Overload relays Current
measurement
Type
Type
Current
range
A
Contactors (type, size, rating in kW)
3RT10 1
3RT10 2
3RT10 3
3RT10 4
3RT10 5
3RT10 6
3RT10 7
3TF68/69
S00
S0
S2
S3
S6
S10
S12
Size 14
3/4/5.5
5.5/7.5/11 15/18.5/22 30/37/45
55/75/90
110/132/160 200/250
375/450
3RU11 thermal overload relays
3RU11 1
Integrated
0.11 … 12
3RU11 2
1.8 … 25
3RU11 3
5,5 … 50
3RU11 4
18 … 100
✔
✔
✔
✔
3RB20/3RB211) solid-state overload relays
3RB2. 1
Integrated
0.1 … 12
3RB2. 2
3 … 25
3RB2. 3
6 … 50
3RB2. 4
12,5 … 100
3RB2. 5
50 ... 200
3RB2. 6
55 ... 630
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
3RB22/3RB231) solid-state overload relays
0.3 … 25
3RB29 0
10 ... 100
3RB29 5
20 … 200
3RB29 6
63 ... 630
3RB29 0 +
3UF18
630 ... 820
5
3RB22/3RB23 + 3RB29 0
✔
1) When using the overload relays with trip class CLASS 20, see Technical
Specifications, Short-Circuit Protection with Fuses for Motor Feeders,and
the configuring aid "Configuring SIRIUS Fuseless Load Feeders".
5/34
Siemens LV 1 · 2006
✔
✔
✔
✔
✔
Overload Relays
3RB2 Solid-State Overload Relays
3RB20, 3RB21 for standard applications
■ Overview
The 3RB20 and 3RB21 solid-state overload relays up to 630 A
with internal power supply have been designed for currentdependent protection of loads with normal and heavy starting
(see LV 1 T, Function) against excessive temperature rises due
to overload, phase unbalance or phase failure. An overload,
phase unbalance or phase failure result in an increase of the
motor current beyond the set motor rated current. This current
rise is detected by the current transformers integrated into the
devices and evaluated by corresponding solid-state circuits
which then output a pulse to the auxiliary contacts. The auxiliary
contacts then switch off the load by means of a contactor. The
break time depends on the ratio between the tripping current
and set current Ie and is stored in the form of a long-term stable
tripping characteristic (see LV 1 T, Characteristic Curves).
The "tripped" status is signaled by means of a switch position
indicator (see LV 1 T, Function). Resetting takes place either
manually or automatically after the recovery time has elapsed
(see LV 1 T, Function).
The devices are manufactured in accordance with
environmental guidelines and contain environmentally friendly
and reusable materials. They comply with all important
worldwide standards and approvals.
■ Benefits
The most important features and benefits of the 3RB20/3RB21
solid-state overload relays are listed in the overview table
(see Overload Relays, General Data).
Siemens LV 1 · 2006
5/35
5
(1) Connection for mounting onto contactors:
Optimally adapted in electrical, mechanical and design terms to the
contactors and soft starters, these connecting pins can be used for
direct mounting of the overload relays. Stand-alone installation is
possible as an alternative (in some cases in conjunction with a standalone installation module).
(2) Selector switch for manual/automatic RESET and RESET button:
With the slide switch you can choose between manual and automatic
RESET. A device set to manual RESET can be reset locally by pressing
the RESET button. On the 3RB21 a solid-state remote RESET is
integrated.
(3) Switch position indicator and TEST function of the wiring:
Indicates a trip and enables the wiring test.
(4) Solid-state test:
Enables a test of all important device components and functions.
(5) Motor current setting:
Setting the device to the rated motor current is easy with the large
rotary knob.
(6) Trip class setting/internal ground-fault detection (only 3RB21):
Using the rotary switch you can set the required trip class and activate
the internal ground-fault detection dependent on the starting
conditions.
(7) Connecting terminals (removable terminal block for auxiliary circuits):
The generously sized terminals permit connection of two conductors
with different cross-sections for the main and auxiliary circuits. The
auxiliary circuit can be connected with screw-type terminals and
alternatively with spring-loaded terminals.
In addition to current-dependent protection of loads against
excessive temperature rises due to overload, phase unbalance
and phase failure, the 3RB21 solid-state overload relays also
allow internal ground-fault detection (not possible in conjunction
with wye-delta assemblies). This provides protection of loads
against high-resistance short-circuits due to damage to the
insulation material, moisture, condensed water etc.
Overload Relays
3RB2 Solid-State Overload Relays
3RB20, 3RB21 for standard applications
■ Application
Industries
The 3RB20/3RB21 solid-state overload relays are suitable for
customers from all industries who want to guarantee optimum
inverse-time delayed protection of their electrical loads
(e.g. motors) under normal and heavy starting conditions
(CLASS 5 to CLASS 30), minimize project completion times,
inventories and power consumption, and optimize plant
availability and maintenance management.
Application
The 3RB20/3RB21 solid-state overload relays have been
designed for the protection of three-phase motors in sinusoidal
50/60 Hz voltage networks. The relays are not suitable for the
protection of single-phase AC or DC loads.
The 3RU11 thermal overload relay or the 3RB22/3RB23 solidstate overload relay can be used for single-phase AC loads.
For DC loads we recommend the 3RU11 thermal overload relay.
Ambient conditions
The devices are insensitive to external influences such as
shocks, corrosive environments, ageing and temperature
changes.
5
For the temperature range from –25 C to +60 °C, the
3RB20/3RB21 solid-state overload relays compensate the
temperature according to IEC 60947-4-1.
Configuration notes for use of the devices below –25 °C or above
+60 °C on request.
5/36
Siemens LV 1 · 2006
"Increased safety" type of protection EEx e according to
ATEX guideline 94/9/EC
The 3RB20/3RB21 solid-state overload relays are suitable for the
overload protection of explosion-proof motors with "increased
safety" type of protection EEx e. The relays meet the requirements of EN 60079-7 (Electrical apparatus for potentially explosive atmospheres – Increased safety "e").
The basic safety and health requirements of ATEX guideline
94/9/EG are fulfilled by compliance with
• EN 60947-1
• EN 60947-4-1
• EN 60947-5-1
• EN 60079-14
EU type test certificate for Group II, Category (2) G/D under
application. Number on request.
■ Accessories
The following accessories are available for the 3RB20/3RB21
solid-state overload relays:
• One terminal bracket each for the overload relays size S00
and S0 (sizes S2 to S12 can be installed as single units without
a terminal bracket)
• One mechanical remote RESET module for all sizes
• One cable release for resetting devices which are difficult to
access (for all sizes)
• One sealable cover for all sizes
• Box terminals for sizes S6 and S10/S12
• Terminal covers for sizes S2 to S10/S12
Overload Relays
3RB2 Solid-State Overload Relays
3RB20, 3RB21 for standard applications
■ Selection and ordering data
Conversion aid 3RB10 ––> 3RB20
Old Order No.
Setting range
A
New Order No.
Setting range
A
3RB10 16-@RB0
0.1 ... 0.4
3RB10 16-@NB0
0.4 ... 1.6
3RB20 16-@RB0
3RB20 16-@NB0
0.1 ... 0.4
0.32 ... 1.25
3RB20 16-@PB0
1 ... 4
3RB10 16-@PB0
1.5 ... 6
3RB10 16-@SB0
3RB10 26-@RB0
3
3RB20 16-@SB0
3 ... 12
S00
S0
S2
S3
S6
S10/S12
CLASS 10
CLASS 20
3RB10 26-@NB0
3RB10 26-@PB0
3RB10 26-@SB0
3RB10 26-@QB0
3RB10 36-@QB0
3RB10 36-@UB0
3RB10 46-@UB0
3RB10 46-@EB0
3RB10 56-@FW0
3RB10 56-@FG0
3RB10 66-@GG0
3RB10 66-@KG0
3RB10 66-@LG0
... 12
0.1 ... 0.4
0.4 ... 1.6
1.5 ... 6
3 ... 12
6 ... 25
6 ... 25
13 ... 50
13 ... 50
25 ... 100
50 ... 200
55 ... 250
200 ... 540
300 ... 630
Use size S00
3RB20 26-@SB0
3RB20 26-@QB0
3RB20 36-@QB0
3RB20 36-@UB0
3RB20 46-@UB0
3RB20 46-@EB0
3RB20 56-@FW2
3RB20 56-@FC2
3RB20 66-@GC2
3 ... 12
6 ... 25
6 ... 25
12.5 ... 50
12.5 ... 50
25 ... 100
3RB20 66-@MC2
160 ... 630
50 ... 200
55 ... 250
5
Size
1
2
1
2
Conversion aid 3RB10 ––> 3RB21
Size
Old Order No.
Setting range
A
New Order No.
Setting range
A
3RB10 16-@RB0
0.1 ... 0.4
3RB10 16-@NB0
0.4 ... 1.6
3RB21 13-4RB0
3RB21 13-4NB0
0.1 ... 0.4
0.32 ... 1.25
3RB21 13-4PB0
1 ... 4
3RB10 16-@PB0
1.5 ... 6
3RB10 16-@SB0
3RB10 26-@RB0
3
3RB21 13-4SB0
3 ... 12
S00
S0
S2
S3
S6
S10/S12
3RB10 26-@NB0
3RB10 26-@PB0
3RB10 26-@SB0
3RB10 26-@QB0
3RB10 36-@QB0
3RB10 36-@UB0
3RB10 46-@UB0
3RB10 46-@EB0
3RB10 56-@FW0
3RB10 56-@FG0
3RB10 66-@GG0
3RB10 66-@KG0
3RB10 66-@LG0
... 12
0.1 ... 0.4
0.4 ... 1.6
1.5 ... 6
3 ... 12
6 ... 25
6 ... 25
13 ... 50
13 ... 50
25 ... 100
50 ... 200
55 ... 250
200 ... 540
300 ... 630
Use size S00
3RB21 23-4SB0
3RB21 23-4QB0
3RB21 33-4QB0
3RB21 33-4UB0
3RB21 43-4UB0
3RB21 43-4EB0
3RB21 53-4FW2
3RB21 53-4FC2
3RB21 63-4GC2
3 ... 12
6 ... 25
6 ... 25
12.5 ... 50
12.5 ... 50
25 ... 100
3RB21 63-4MC2
160 ... 630
50 ... 200
55 ... 250
Note:
CLASS 10
CLASS 20
1
2
CLASS 5, 10, 20 and 30
can be set on the unit
Siemens LV 1 · 2006
5/37
Overload Relays
3RB2 Solid-State Overload Relays
3RB20, 3RB21 for standard applications
3RB20 solid-state overload relays with screw connection on auxiliary current side for direct mounting1)2)
and stand-alone installation2)3), CLASS 10
Features and technical specifications:
• Overload protection, phase failure protection and unbalance
protection
• Internal power supply
• Auxiliary contacts 1 NO + 1 NC
Size
Contactor4)
• Manual and automatic RESET
• Switch position indicator
• TEST function and self-monitoring
Rating
for induction
motor
Rated value5)
Set current value
of the inversetime delayed
overload trip
Short-circuit DT Order No.
protection
with fuse,
type of
coordination
2, gL/gG
operational
class6)
kW
A
A
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Size S001)
S00
0.04 … 0.09
0.1 … 0.4
2
}
3RB20 16-1RB0
1
1 unit
101
0.200
0.12 … 0.37
0.32 … 1.25
6
}
3RB20 16-1NB0
1
1 unit
101
0.200
0.55 … 1.5
1…4
20
}
3RB20 16-1PB0
1
1 unit
101
0.200
1.1 … 5.5
3 … 12
35
}
3RB20 16-1SB0
1
1 unit
101
0.200
35
3RB20 16-1RB0
Size S01)
1.1 … 5.5
3 … 12
3 … 11
6 … 25
3 … 11
6 … 25
}
3RB20 26-1SB0
1
1 unit
101
0.220
}
3RB20 26-1QB0
1
1 unit
101
0.220
5
S0
3RB20 26-1QB0
Size S2 1)3)7)
S2
7.5 … 22
12.5 … 50
35
100
}
3RB20 36-1QB0
1
1 unit
101
0.360
}
3RB20 36-1QW1
1
1 unit
101
0.230
}
3RB20 36-1UB0
1
1 unit
101
0.360
}
3RB20 36-1UW1
1
1 unit
101
0.230
3RB20 36-1UB0
Size S3 1)3)7)
S3
7.5 … 22
12.5 … 50
125
}
3RB20 46-1UB0
1
1 unit
101
0.560
11 … 45
25 … 100
200
}
3RB20 46-1EB0
1
1 unit
101
0.560
}
3RB20 46-1EW1
1
1 unit
101
0.450
3RB20 46-1EB0
Size S6 2)7)
S6
22 … 90
50 … 200
355
}
3RB20 56-1FC2
1
1 unit
101
1.030
}
3RB20 56-1FW2
1
1 unit
101
0.690
3RB20 56-1FW2
Size S10/S122)
S10/S12
and size
14
(3TF68/
3TF69)
22 … 110
55 … 250
500
}
3RB20 66-1GC2
1
1 unit
101
1.820
90 … 450
160 … 630
800
}
3RB20 66-1MC2
1
1 unit
101
1.820
3RB20 66-1MC2
1) The relays with an Order No. ending with "0" are designed for direct
mounting. With the matching terminal brackets (see Accessories) the sizes
S00 and S0 can also be installed as stand-alone units.
2) The relays with an Order No. ending with "2" are designed for direct
mounting and stand-alone installation. For 3TF68/3TF69 contactors, direct
mounting is not possible.
3) The relays with an Order No. ending with "1" are designed for stand-alone
installation.
4) Observe maximum rated operational current of the devices.
5) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
6) Maximum fuse for overload relay, type of coordination 2. For fuse values in
conjunction with contactors, see Technical Specifications, Short-Circuit
Protection with Fuses for Motor Feeders.
7) The relays with an Order No. with "W" in penultimate position are
equipped with a straight-through transformer.
* You can order this quantity or a multiple thereof.
5/38
Siemens LV 1 · 2006
Overload Relays
3RB2 Solid-State Overload Relays
3RB20, 3RB21 for standard applications
3RB20 solid-state overload relays with spring-loaded terminals on the auxiliary current side for direct mounting1)2)
and stand-alone installation2)3), CLASS 10
Features and technical specifications:
• Overload protection, phase failure protection and unbalance
protection
• Internal power supply
• Auxiliary contacts 1 NO + 1 NC
Size
Contactor4)
• Manual and automatic RESET
• Switch position indicator
• TEST function and self-monitoring
Rating
for induction
motor
Rated value5)
Set current value
of the inversetime delayed
overload trip
Short-circuit DT Order No.
protection
with fuse,
type of coordination 2,
gL/gG
operational
class6)
kW
A
A
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Size S001)
S00
0.04 … 0.09
0.1 … 0.4
2
A
3RB20 16-1RD0
1
1 unit
101
0.200
0.12 … 0.37
0.32 … 1.25
6
A
3RB20 16-1ND0
1
1 unit
101
0.200
0.55 … 1.5
1…4
20
A
3RB20 16-1PD0
1
1 unit
101
0.200
1.1 … 5.5
3 … 12
35
A
3RB20 16-1SD0
1
1 unit
101
0.200
35
3RB20 16-1RD0
Size S01)
1.1 … 5.5
3 … 12
3 … 11
6 … 25
3 … 11
6 … 25
A
3RB20 26-1SD0
1
1 unit
101
0.220
A
3RB20 26-1QD0
1
1 unit
101
0.220
5
S0
3RB20 26-1QD0
Size S2 1)3)7)
S2
7.5 … 22
12.5 … 50
35
100
A
3RB20 36-1QD0
1
1 unit
101
0.360
A
3RB20 36-1QX1
1
1 unit
101
0.230
A
3RB20 36-1UD0
1
1 unit
101
0.360
A
3RB20 36-1UX1
1
1 unit
101
0.230
3RB20 36-1UD0
Size S3 1)3)7)
S3
7.5 … 22
12.5 … 50
125
A
3RB20 46-1UD0
1
1 unit
101
0.560
11 … 45
25 … 100
200
A
3RB20 46-1ED0
1
1 unit
101
0.560
A
3RB20 46-1EX1
1
1 unit
101
0.450
3RB20 46-1ED0
Size S62)7)
S6
22 … 90
50 … 200
355
A
3RB20 56-1FF2
1
1 unit
101
1.030
A
3RB20 56-1FX2
1
1 unit
101
0.690
3RB20 56-1FX2
Size S10/S122)
S10/S12
and size
14
(3TF68/
3TF69)
22 … 110
55 … 250
500
A
3RB20 66-1GF2
1
1 unit
101
1.820
90 … 450
160 … 630
800
A
3RB20 66-1MF2
1
1 unit
101
1.820
3RB20 66-1MF2
1) The relays with an Order No. ending with "0" are designed for direct
mounting. With the matching terminal brackets (see Accessories) the sizes
S00 and S0 can also be installed as stand-alone units.
2) The relays with an Order No. ending with "2" are designed for direct
mounting and stand-alone installation. For 3TF68/3TF69 contactors, direct
mounting is not possible.
3) The relays with an Order No. ending with "1" are designed for stand-alone
installation.
4) Observe maximum rated operational current of the devices.
5) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
6) Maximum fuse for overload relay, type of coordination 2. For fuse values in
conjunction with contactors, see Technical Specifications, Short-Circuit
Protection with Fuses for Motor Feeders.
7) The relays with an Order No. with "X" in penultimate position are equipped
with a straight-through transformer.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/39
Overload Relays
3RB2 Solid-State Overload Relays
3RB20, 3RB21 for standard applications
3RB20 solid-state overload relays with screw connection on auxiliary current side for direct mounting1)2)
and stand-alone installation2)3), CLASS 20
Features and technical specifications:
• Overload protection, phase failure protection and unbalance
protection
• Internal power supply
• Auxiliary contacts 1 NO + 1 NC
Size
Contactor4)
• Manual and automatic RESET
• Switch position indicator
• TEST function and self-monitoring
Rating
for induction
motor
Rated value5)
Set current value
of the inversetime delayed
overload trip
Short-circuit DT With screw connection on
protection
auxiliary current side
with fuse,
type of coorOrder No.
Price
dination 2,
per PU
gL/gG
operational
class6)
kW
A
A
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Size S001)
S00
0.04 … 0.09
0.1 … 0.4
2
}
3RB20 16-2RB0
1
1 unit
101
0.200
0.12 … 0.37
0.32 … 1.25
6
}
3RB20 16-2NB0
1
1 unit
101
0.200
0.55 … 1.5
1…4
20
}
3RB20 16-2PB0
1
1 unit
101
0.200
1.1 … 5.5
3 … 12
35
}
3RB20 16-2SB0
1
1 unit
101
0.200
35
3RB20 16-2RB0
Size S01)
1.1 … 5.5
3 … 12
3 … 11
6 … 25
3 … 11
6 … 25
}
3RB20 26-2SB0
1
1 unit
101
0.220
}
3RB20 26-2QB0
1
1 unit
101
0.220
5
S0
3RB20 26-2QB0
Size S21)3)7)
S2
7.5 … 22
12.5 … 50
35
100
}
3RB20 36-2QB0
1
1 unit
101
0.360
}
3RB20 36-2QW1
1
1 unit
101
0.230
}
3RB20 36-2UB0
1
1 unit
101
0.360
}
3RB20 36-2UW1
1
1 unit
101
0.230
3RB20 36-2UB0
Size S31)3)7)
S3
7.5 … 22
12.5 … 50
125
}
3RB20 46-2UB0
1
1 unit
101
0.560
11 … 45
25 … 100
200
}
3RB20 46-2EB0
1
1 unit
101
0.560
}
3RB20 46-2EW1
1
1 unit
101
0.450
}
3RB20 56-2FC2
1
1 unit
101
1.030
}
3RB20 56-2FW2
1
1 unit
101
0.690
3RB20 46-2EB0
Size S62)7)
S6
22 … 90
50 … 200
355
3RB20 56-2FW2
Size S10/S122)
S10/S12
and
size 14
(3TF68/
3TF69)
22 … 110
55 … 250
500
}
3RB20 66-2MC2
1) The relays with an Order No. ending with "0" are designed for direct
mounting. With the matching terminal brackets (see Accessories) the sizes
S00 and S0 can also be installed as stand-alone units.
2) The relays with an Order No. ending with "2" are designed for direct
mounting and stand-alone installation. For 3TF68/3TF69 contactors, direct
mounting is not possible.
3) The relays with an Order No. ending with "1" are designed for stand-alone
installation.
4) Observe maximum rated operational current of the devices.
5/40
Siemens LV 1 · 2006
5) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
6) Maximum fuse for overload relay, type of coordination 2. For fuse values in
conjunction with contactors, see Technical Specifications, Short-Circuit
Protection with Fuses for Motor Feeders.
7) The relays with an Order No. with "W" in penultimate position are
equipped with a straight-through transformer.
Overload Relays
3RB2 Solid-State Overload Relays
3RB20, 3RB21 for standard applications
3RB20 solid-state overload relays with spring-loaded terminals on the auxiliary current side for direct mounting1)2)
and stand-alone installation2)3), CLASS 20
Features and technical specifications:
• Overload protection, phase failure protection and unbalance
protection
• Internal power supply
• Auxiliary contacts 1 NO + 1 NC
Size
Contactor4)
• Manual and automatic RESET
• Switch position indicator
• TEST function and self-monitoring
Rating
for induction
motor
Rated value5)
Set current value
of the inversetime delayed
overload trip
Short-circuit DT With spring-loaded
protection
terminals on auxiliary
with fuse,
current side
type of coorOrder No.
Price
dination 2,
per PU
gL/gG
operational
class6)
kW
A
A
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Size S001)
S00
0.04 … 0.09
0.1 … 0.4
2
A
3RB20 16-2RD0
1
1 unit
101
0.200
0.12 … 0.37
0.32 … 1.25
6
A
3RB20 16-2ND0
1
1 unit
101
0.200
0.55 … 1.5
1…4
20
A
3RB20 16-2PD0
1
1 unit
101
0.200
1.1 … 5.5
3 … 12
35
A
3RB20 16-2SD0
1
1 unit
101
0.200
35
3RB20 16-2RD0
Size S01)
1.1 … 5.5
3 … 12
3 … 11
6 … 25
3 … 11
6 … 25
A
3RB20 26-2SD0
1
1 unit
101
0.220
A
3RB20 26-2QD0
1
1 unit
101
0.220
5
S0
3RB20 26-2QD0
Size S21)3)7)
S2
7.5 … 22
12.5 … 50
35
100
A
3RB20 36-2QX1
1
1 unit
101
0.230
A
3RB20 36-2QD0
1
1 unit
101
0.360
A
3RB20 36-2UD0
1
1 unit
101
0.360
A
3RB20 36-2UX1
1
1 unit
101
0.230
3RB20 36-2UD0
Size S31)3)7)
S3
7.5 … 22
12.5 … 50
125
A
3RB20 46-2UD0
1
1 unit
101
0.560
11 … 45
25 … 100
200
A
3RB20 46-2ED0
1
1 unit
101
0.560
A
3RB20 46-2EX1
1
1 unit
101
0.450
A
3RB20 56-2FF2
1
1 unit
101
1.030
A
3RB20 56-2FX2
1
1 unit
101
0.690
3RB20 46-2ED0
Size S62)7)
S6
22 … 90
50 … 200
355
3RB20 56-2FX2
Size S10/S122)
1) The relays with an Order No. ending with "0" are designed for direct
mounting. With the matching terminal brackets (see Accessories) the sizes
S00 and S0 can also be installed as stand-alone units.
2) The relays with an Order No. ending with "2" are designed for direct
mounting and stand-alone installation. For 3TF68/3TF69 contactors, direct
mounting is not possible.
3) The relays with an Order No. ending with "1" are designed for stand-alone
installation.
4) Observe maximum rated operational current of the devices.
5) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
6) Maximum fuse for overload relay, type of coordination 2. For fuse values in
conjunction with contactors, see Technical Specifications, Short-Circuit
Protection with Fuses for Motor Feeders.
7) The relays with an Order No. with "X" in penultimate position are equipped
with a straight-through transformer.
Siemens LV 1 · 2006
5/41
Overload Relays
3RB2 Solid-State Overload Relays
3RB20, 3RB21 for standard applications
3RB21 solid-state overload relays with screw connection on auxiliary current side for direct mounting1)2)
and stand-alone installation2)3), CLASS 5, 10, 20 and 30 adjustable
Features and technical specifications:
• Overload protection, phase failure protection and unbalance
protection
• Internal ground fault detection (activatable)
• Internal power supply
• Auxiliary contacts 1 NO + 1 NC
Size
Contactor4)
•
•
•
•
Manual and automatic RESET
Electrical remote RESET integrated
Switch position indicator
TEST function and self-monitoring
Rating
for induction
motor
Rated value5)
Set current value
of the inversetime delayed
overload trip
Short-circuit DT With screw connection on
protection
auxiliary current side
with fuse,
type of
Order No.
Price
coordination
per PU
2, gL/gG
operational
class6)
kW
A
A
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Size S001)
S00
0.04 … 0.09
0.1 … 0.4
2
}
3RB21 13-4RB0
1
1 unit
101
0.200
0.12 … 0.37
0.32 … 1.25
6
}
3RB21 13-4NB0
1
1 unit
101
0.200
0.55 … 1.5
1…4
20
}
3RB21 13-4PB0
1
1 unit
101
0.200
1.1 … 5.5
3 … 12
35
}
3RB21 13-4SB0
1
1 unit
101
0.200
35
3RB21 13-4RB0
Size S01)
1.1 … 5.5
3 … 12
3 … 11
6 … 25
3 … 11
6 … 25
}
3RB21 23-4SB0
1
1 unit
101
0.220
}
3RB21 23-4QB0
1
1 unit
101
0.220
5
S0
3RB21 23-4QB0
Size S21)3)7)
S2
7.5 … 22
12.5 … 50
35
100
}
3RB21 33-4QB0
1
1 unit
101
0.360
}
3RB21 33-4QW1
1
1 unit
101
0.230
}
3RB21 33-4UB0
1
1 unit
101
0.360
}
3RB21 33-4UW1
1
1 unit
101
0.230
3RB21 33-4UB0
Size S31)3)7)
S3
7.5 … 22
12.5 … 50
125
}
3RB21 43-4UB0
1
1 unit
101
0.560
11 … 45
25 … 100
200
}
3RB21 43-4EB0
1
1 unit
101
0.560
}
3RB21 43-4EW1
1
1 unit
101
0.450
3RB21 43-4EB0
Size S62)7)
S6
22 … 90
50 … 200
355
}
3RB21 53-4FC2
1
1 unit
101
1.030
}
3RB21 53-4FW2
1
1 unit
101
0.690
}
3RB21 63-4GC2
1
1 unit
101
1.820
3RB21 53-4FC2
Size S10/S122)
S10/S12
and size
14
(3TF68/
3TF69)
22 … 110
55 … 250
90 … 450
160 … 630
500
500 800
3RB21 63-4MC2
1) The relays with an Order No. ending with "0" are designed for direct
mounting. With the matching terminal brackets (see Accessories) the sizes
S00 and S0 can also be installed as stand-alone units.
2) The relays with an Order No. ending with "2" are designed for direct
mounting and stand-alone installation. For 3TF68/3TF69 contactors, direct
mounting is not possible.
3) The relays with an Order No. ending with "1" are designed for stand-alone
installation.
4) Observe maximum rated operational current of the devices.
5/42
Siemens LV 1 · 2006
5) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
6) Maximum fuse for overload relay, type of coordination 2. For fuse values in
conjunction with contactors, see Technical Specifications, Short-Circuit
Protection with Fuses for Motor Feeders.
7) The relays with an Order No. with "W" in penultimate position are
equipped with a straight-through transformer.
Overload Relays
3RB2 Solid-State Overload Relays
3RB20, 3RB21 for standard applications
3RB21 solid-state overload relays with spring-loaded terminals on the auxiliary current side for direct mounting1)2) and
stand-alone installation1)3), CLASS 5, 10, 20 and 30 adjustable
Features and technical specifications:
• Overload protection, phase failure protection and unbalance
protection
• Internal ground fault detection (activatable)
• Internal power supply
• Auxiliary contacts 1 NO + 1 NC
Size
Contactor4)
•
•
•
•
Manual and automatic RESET
Electrical remote RESET integrated
Switch position indicator
TEST function and self-monitoring
Rating
for induction
motor
Rated value5)
Set current value
of the inversetime delayed
overload trip
Short-circuit DT With spring-loaded
protection
terminals on auxiliary
with fuse,
current side
type of coorOrder No.
Price
dination 2,
per PU
gL/gG
operational
class6)
kW
A
A
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Size S001)
S00
0.04 … 0.09
0.1 … 0.4
2
A
3RB21 13-4RD0
1
1 unit
101
0.200
0.12 … 0.37
0.32 … 1.25
6
A
3RB21 13-4ND0
1
1 unit
101
0.200
0.55 … 1.5
1…4
20
A
3RB21 13-4PD0
1
1 unit
101
0.200
1.1 … 5.5
3 … 12
35
A
3RB21 13-4SD0
1
1 unit
101
0.200
35
3RB21 13-4RD0
Size S01)
1.1 … 5.5
3 … 12
3 … 11
6 … 25
3 … 11
6 … 25
A
3RB21 23-4SD0
1
1 unit
101
0.220
A
3RB21 23-4QD0
1
1 unit
101
0.220
5
S0
3RB21 23-4QD0
Size S21)3)7)
S2
7.5 … 22
12.5 … 50
35
100
A
3RB21 33-4QD0
1
1 unit
101
0.360
A
3RB21 33-4QX1
1
1 unit
101
0.230
A
3RB21 33-4UD0
1
1 unit
101
0.360
A
3RB21 33-4UX1
1
1 unit
101
0.230
3RB21 33-4UD0
Size S31)3)7)
S3
7.5 … 22
12.5 … 50
125
A
3RB21 43-4UD0
1
1 unit
101
0.560
11 … 45
25 … 100
200
A
3RB21 43-4ED0
1
1 unit
101
0.560
A
3RB21 43-4EX1
1
1 unit
101
0.450
3RB21 43-4ED0
Size S62)7)
S6
22 … 90
50 … 200
355
A
3RB21 53-4FF2
1
1 unit
101
1.030
A
3RB21 53-4FX2
1
1 unit
101
0.690
3RB21 53-4FX2
Size S10/S122)
S10/S12
and size
14
(3TF68/
3TF69)
22 … 110
55 … 250
500
A
3RB21 63-4GF2
1
1 unit
101
1.820
90 … 450
160 … 630
800
A
3RB21 63-4MF2
1
1 unit
101
1.820
3RB21 63-4MF2
1) The relays with an Order No. ending with "0" are designed for direct
mounting. With the matching terminal brackets (see Accessories) the sizes
S00 and S0 can also be installed as stand-alone units.
2) The relays with an Order No. ending with "2" are designed for direct
mounting and stand-alone installation. For 3TF68/3TF69 contactors, direct
mounting is not possible.
3) The relays with an Order No. ending with "1" are designed for stand-alone
installation.
4) Observe maximum rated operational current of the devices.
5) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
6) Maximum fuse for overload relay, type of coordination 2. For fuse values in
conjunction with contactors, see Technical Specifications, Short-Circuit
Protection with Fuses for Motor Feeders.
7) The relays with an Order No. with "X" in penultimate position are equipped
with a straight-through transformer.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/43
Overload Relays
3RB2 Solid-State Overload Relays
3RB22, 3RB23 for high-feature applications
■ Overview
5
The modular, solid-state overload relays with external power
supply type 3RB22 (with monostable auxiliary contacts) and
type 3RB23 (with bistable auxiliary contacts) up to 630 A (up to
820 A possible with a series transformer) have been designed
for inverse-time delayed protection of loads with normal and
heavy starting (see LV 1 T, Function) against excessive
temperature rises due to overload, phase unbalance or phase
failure. An overload, phase unbalance or phase failure result in
an increase of the motor current beyond the set motor rated
current. This current rise is detected by means of a current
measuring module and electronically evaluated by a special
evaluation module which is connected to it. The evaluation
electronics sends a signal to the auxiliary contacts. The auxiliary
contacts then switch off the load by means of a contactor. The
break time depends on the ratio between the tripping current
and set current Ie and is stored in the form of a long-term stable
tripping characteristic (see LV 1 T, Characteristic Curves). The
"tripped" status is signaled by means of a continuous red
"Overload" LED.
3RB22/3RB23 evaluation module
(1) Green "Ready" LED
A continuous green light signals that the device is working correctly.
(2) Red "Ground fault" LED:
A continuous red light signals a ground fault.
(3) Red "Thermistor" LED:
A continuous red light signals an active thermistor trip.
(4) Red "Overload" LED:
A continuous red light signals an active overload trip; a flickering red
light signals an imminent trip (overload warning).
(5) Motor current and trip class adjustment:
Setting the device to the motor current and to the required trip class
dependent on the starting conditions is easy with the two rotary knobs.
(6) Selector switch for manual/automatic RESET:
With this switch you can choose between manual and automatic
RESET.
(7) Test/RESET button:
Enables testing of all important device components and functions,
plus resetting of the device after a trip when manual RESET is
selected.
(8) Connecting terminals (removable terminal block):
The generously sized terminals permit connection of two conductors
with different cross-sections for the auxiliary, control and sensor
circuits. Connection is possible with screw-type terminals and
alternatively with spring-loaded terminals.
(9) 3RB29 85 function expansion module:
Enables more functions to be added, e.g. internal ground fault
detection and/or an analog output with corresponding signals.
The LED indicates imminent tripping of the relay due to overload,
phase unbalance or phase failure by flickering when the limit
current has been violated. This warning can also issued as a
signal through auxiliary contacts.
In addition to the described inverse-time delayed protection of
loads against excessive temperature rises, the 3RB22/3RB23
solid-state overload relays also allow direct temperature monitoring of the motor windings (full motor protection) by failsafe
connection of a PTC sensor circuit. With this temperature-dependent protection, the loads can be protected against overheating
caused indirectly by reduced coolant flow, for example, which
cannot be detected by means of the current alone. In the event
of overheating, the devices switch off the contactor, and thus the
load, by means of the auxiliary contacts. The "tripped" status is
signaled by means of a continuously illuminated "Overload" LED.
To also protect the loads against high-resistance short-circuits
due to damage to the insulation, humidity, condensed water,
etc., the 3RB22/3RB23 solid-state overload relays offer the
possibility of internal ground fault monitoring in conjunction with
a function expansion module (for details see Selection and
Ordering Data; not possible in conjunction with contactor
assembly for Wye-Delta starting). In the event of a ground fault
the 3RB22/3RB23 relays trip instantaneously. The "tripped"
status is signaled by means of a red "Ground Fault" LED.
Signaling through auxiliary contacts is also possible.
After tripping due to overload, phase unbalance, phase failure,
thermistor tripping or ground fault, the relay is reset manually or
automatically after the recovery time has elapsed (see LV 1 T,
Function).
In conjunction with a function expansion module the motor
current measured by the microprocessor can be output in the
form of an analog signal 4 ... 20 mA DC for operating rotary coil
instruments or for feeding into analog inputs of programmable
logic controllers. With an additional AS-Interface analog module
the current values can also be transferred over the
AS-i bus system.
The devices are manufactured in accordance with environmental guidelines and contain environmentally friendly and reusable
materials.
They comply with all important worldwide standards and
approvals.
3RB29 06 current measuring module
5/44
Siemens LV 1 · 2006
Overload Relays
3RB2 Solid-State Overload Relays
3RB22, 3RB23 for high-feature applications
■ Benefits
The most important features and benefits of the 3RB22/3RB23
solid-state overload relays are listed in the overview table
(see Overload Relays, General Data).
■ Application
Industries
The 3RB22/3RB23 solid-state overload relays are suitable for
customers from all industries who want to guarantee optimum
inverse-time delayed and temperature-dependent protection of
their electrical loads (e.g. motors) under normal and heavy
starting conditions (CLASS 5 to CLASS 30), minimize project
completion times, inventories and power consumption, and
optimize plant availability and maintenance management.
Application
The 3RB22/3RB23 solid-state overload relays have been
designed for the protection of three-phase asynchronous and
single-phase AC motors.
5
If single-phase AC motors are to be protected by the
3RB22/3RB23 solid-state overload relays, the main circuits of
the currets ofnuu buriescnieectee
(sheRF1 1,(/)-1. Sc(T)6.8(m4(at)5.oli)6.c(e)-0.s1())]TJ0 g -120019 0 TD0 Tc0 Tw(.)TJ/F6 1 Tf/Cs6 cs 0 0.553 1 sc-g -120010 -1.7165 TD-0.0142 T
Siemens LV 1 · 2006
5/45
Overload Relays
3RB2 Solid-State Overload Relays
3RB22, 3RB23 for high-feature applications
■ Selection and ordering data
Conversion aid 3RB12 ––> 3RB22/3RB23
Size
Old Order No.
Complete unit
Setting range
A
3RB12 46-1P @@@ 1.25 ... 6.3
S00/S0
5
3RB12 46-1Q @@@ 6.3 ... 25
S2/S3
3RB12 46-1E @@@ 25 ... 100
S6
3RB12 53-1F @@@ 50 ... 205
S10/S12
3RB12 57-0K @@@ 125 ... 500
3RB12 62-0L @@@ 200 ... 820
110 ... 120 V AC
220 ... 240 V AC
24 V DC
Standard design
with ground fault signal
Standard design
with overload warning
Version with internal
ground fault detection
and ground fault signal
Version with internal
ground fault detection
and overload warning
Version
with analog output
Bistable version
with ground fault signal
Bistable version
with overload warning
5/46
Siemens LV 1 · 2006
New Order No.
Setting range
Current measuring A
module
3RB29 06-2BG1
0.3 ... 3
3RB29 06-2DG1
2.4 ... 25
3RB29 06-2JG1
3RB29 56-2TG2
3RB29 56-2TH2
10 ... 100
3RB29 66-2WH2
63 ... 630 (820)
New Order No.
New Order No.
Evaluation module Function expansion
module
3RB2@ 83-4AA1
3RB29 85-2@@@
20 ... 200
00
Integrated
Integrated
Integrated
Not available
10
2
20
2
CB1
30
2
CA1
40
2
AA0
01
Not available
--
11
3
G
M
B
Integrated
Integrated
Integrated
-Not required
Not required
Overload Relays
3RB2 Solid-State Overload Relays
3RB22, 3RB23 for high-feature applications
3RB22/3RB23 solid-state overload relays for full motor protection with screw connection or spring-loaded terminals
for stand-alone installation, CLASS 5, 10, 20 and 30 adjustable
Features and technical specifications:
• Overload protection, phase failure protection and unbalance
protection
• External power supply 24 ... 240 V AC/DC
• Auxiliary contacts 2 NO +2 NC
• Manual and automatic RESET
• Electrical remote RESET integrated
• 4 LEDs for operating and status displays
Size
Version
Contactor
• TEST function and self-monitoring
• Internal ground fault detection with function expansion
module
• Screw connection or spring-loaded terminals for auxiliary,
control and sensor circuits
• Input for PTC sensor circuit
• Analog output with function expansion module
Connection DT Order No.
type
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Evaluation modules
Screw
connection
}
3RB22 83-4AA1
1
1 unit
101
0.300
Springloaded
terminals
A
3RB22 83-4AC1
1
1 unit
101
0.300
Screw
connection
}
3RB23 83-4AA1
1
1 unit
101
0.300
Springloaded
terminals
A
3RB23 83-4AC1
1
1 unit
101
0.300
Analog Basic 1 module1)
Analog output DC 4 ... 20 mA,
with overload warning
}
3RB29 85-2AA0
1
1 unit
101
0.030
Analog Basic 1 GF module1)2)
Analog output DC 4 ... 20 mA,
with internal ground fault
detection and overload warning
}
3RB29 85-2AA1
1
1 unit
101
0.030
Analog Basic 2 GF module1)2)
Analog output DC 4 ... 20 mA,
with internal ground fault
detection and ground fault
signaling
}
3RB29 85-2AB1
1
1 unit
101
0.030
Basic 1 GF module2)
with internal ground fault
detection and overload warning
}
3RB29 85-2CA1
1
1 unit
101
0.030
Basic 2 GF module2)
with internal ground fault
detection and ground fault
signaling
}
3RB29 85-2CB1
1
1 unit
101
0.030
S00 ... S12 Monostable
Bistable
5
3RB2. 83-4AA1
3RB2. 83-4AC1
Function expansion modules
–
1) The analog signal 4 ... 20 mA DC can be used for operating rotary coil
instruments or for feeding into analog inputs of programmable logic
controllers.
2) The following information on ground fault protection refers to sinusoidal
residual currents at 50/60 Hz:
- With a motor current of between 0.3 and 2 times the set current Ie the unit
will trip at a ground fault current equal to 30% of the set current.
- With a motor current of between 2 and 8 times the set current Ie the unit
will trip at a ground fault current equal to 15% of the set current.
- The trip delay amounts to between 0.5 and 1 second.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/47
Overload Relays
3RB2 Solid-State Overload Relays
3RB22, 3RB23 for high-feature applications
Current measuring modules for direct mounting1) and stand-alone installation1)2)
Size
Contactor3)
Rating
for induction
motor,
Rated value4)
Set current value
of the inversetime delayed
overload trip
Short-circuit DT Order No.
protection
with fuse,
type of coordination 2,
gL/gG
operational
class5)
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kW
A
A
0.09 … 1.1
0.3 … 3
16
}
3RB29 06-2BG1
1
1 unit
101
0.100
1.1 … 11
2.4 … 25
63
}
3RB29 06-2DG1
1
1 unit
101
0.150
S2/S3
5.5 … 45
10 … 100
250
}
3RB29 06-2JG1
1
1 unit
101
0.350
S6
11 … 90
20 … 200
355
kg
Size S00/S02)6)
S00/S0
3RB29 06-2.G1
Size S2/S32)6)
3RB29 06-2JG1
5
Size S61)6)
}
3RB29 56-2TG2
1
1 unit
101
0.600
}
3RB29 56-2TH2
1
1 unit
101
1.000
}
3RB29 66-2WH2
1
1 unit
101
1.750
3RB29 56-2TG2
Size S10/S121)
S10/S12
and
size 14
(3TF68/
3TF69)
37 … 450
63 … 630
630
3RB29 66-2WH2
1) The current measuring modules with an Order No. ending with "2" are
designed for direct mounting and stand-alone installation. For
3TF68/3TF69 contactors, direct mounting is not possible.
2) The current measuring modules with an Order No. ending with "1" are
designed for stand-alone installation.
3) Observe maximum rated operational current of the devices.
Size
Version
Contactor
4) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
5) Maximum fuse for overload relay, type of coordination 2. For fuse values in
conjunction with contactors, see Technical Specifications, Short-Circuit
Protection with Fuses for Motor Feeders.
6) The modules with an Order No. with "G" in penultimate position are
equipped with a straight-through transformer.
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Connecting leads
S00 ... S12 For connection between evaluation module and
current measuring module
• Length 0.1 m
}
3RB29 87-2B
1
1 unit
101
0.010
• Length 0.5 m
}
3RB29 87-2D
1
1 unit
101
0.020
3RB29 87-2.
* You can order this quantity or a multiple thereof.
5/48
Siemens LV 1 · 2006
Overload Relays
3RB2 Solid-State Overload Relays
Accessories
■ Overview
Overload relays for standard applications
Overload relays for high-feature applications
The following accessories are available for the 3RB20/3RB21
solid-state overload relays:
• One terminal bracket each for the overload relays size S00
and S0 (sizes S2 to S12 can be installed as single units without
a terminal bracket)
• One mechanical RESET module for all sizes
• One cable release for resetting devices which are difficult to
access (for all sizes)
• One sealable cover for all sizes
• Box terminal blocks for sizes S6 and S10/S12
• Terminal covers for sizes S2 to S10/S12
The following accessories are available for the 3RB22/3RB23
solid-state overload relays:
• A sealable cover for the evaluation module
• Box terminal blocks for the current measuring modules size S6
and S10/S12
• Terminal covers for the current measuring modules size S6
and S10/S12
• Push-in lugs for screw mounting the size S00 to S3 current
measuring modules
■ Selection and ordering data
Version
Size
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Terminal brackets for stand-alone installation1)
S00
A
3RB29 13-0AA1
1
1 unit
101
0.060
S0
A
3RB29 23-0AA1
1
1 unit
101
0.080
Resetting plungers, holders and formers S00 ...
S10/S12
}
3RU19 00-1A
1
1 set
101
0.038
Pushbuttons with extended stroke
(12 mm), IP65, Ø 22 mm
B
3SB30 00-0EA11
1
1 unit
102
0.021
Extension plungers
For compensation of the distance between
a pushbutton and the unlatching button of
the relay
A
3SX1 335
1
1 unit
102
0.004
• Length 400 mm
}
3RU19 00-1B
1
1 unit
101
0.063
• Length 600 mm
}
3RU19 00-1C
1
1 unit
101
0.073
5
For separate mounting of the overload
relays; screw and snap-on mounting onto
TH35 standard mounting rail
3RB29 .3-0AA1
Mechanical RESET2)
3RU19 00-1A
with pushbutton and
extension plunger
Cable releases with holder for RESET2)
For holes with Ø 6.5 mm
in the mounting plate;
max. control panel thickness 8 mm
S00 ...
S10/S12
3RU19 00-1.
1) Only for 3RB20/3RB21.
2) Only for 3RB20/3RB21. The accessories are identical to those of the
3RU11 thermal overload relays.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/49
Overload Relays
3RB2 Solid-State Overload Relays
Accessories
Version
Size
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Sealable covers
For covering the setting knobs
• For 3RB20/3RB21
S00 ...
S10/S12
}
3RB29 84-0
1 10 units
101
0.020
• For 3RB22/3RB23
–
}
3RB29 84-2
1 10 units
101
0.050
Terminal covers
Covers for cable lugs and rail connection
3RT19 46-4EA1
• Length 55 mm1)
S3
}
3RT19 46-4EA1
1
1 unit
101
0.037
• Length 100 mm
S6
}
3RT19 56-4EA1
1
1 unit
101
0.067
• Length 120 mm
S10/S12
}
3RT19 66-4EA1
1
1 unit
101
0.124
• Length 20.6 mm1)
S2
}
3RT19 36-4EA2
1
1 unit
101
0.016
• Length 20.8 mm1)
S3
}
3RT19 46-4EA2
1
1 unit
101
0.023
• Length 25 mm
S6
}
3RT19 56-4EA2
1
1 unit
101
0.028
• Length 30 mm
S10/S12
}
3RT19 66-4EA2
1
1 unit
101
0.038
S6
}
3RT19 56-4EA3
1
1 unit
101
0.021
S10/S12
}
3RT19 66-4EA3
1
1 unit
101
0.062
S62)
}
3RT19 55-4G
1
1 unit
101
0.237
S6
}
3RT19 56-4G
1
1 unit
101
0.270
S10/S12
}
3RT19 66-4G
1
1 unit
101
0.676
S00 ... S3 }
3RT19 00-0B
100 10 units
101
0.100
Covers for box terminals
Covers for screw connections
between contactor and overload relay,
3RT19 36-4EA2
without box terminals
The figures show
mounting on the contactor (1 unit required per combination)
Box terminal blocks
For round and ribbon cables
5
up to 70 mm2
up to
120mm2
up to 240mm2
For conductor cross-sections,
see LV 1 T "Technical Specifications"
3RT19 5.-4G
Push-in lugs
For screw mounting of 3RB29 06 current
measuring modules
(2 units are required per module)
3RB19 00-0B
For more accessories (tools for spring-loaded terminals and
labeling plates), see page 5/56.
1) Only for 3RB20/3RB21. The accessories are identical to those of the
3RU11 thermal overload relays.
2) In the scope of supply for 3RT10 54-1 contactors (55 kW).
* You can order this quantity or a multiple thereof.
5/50
Siemens LV 1 · 2006
Overload Relays
3RU1 Thermal Overload Relays
3RU11 for standard applications
■ Overview
■ Benefits
The most important features and benefits of the 3RU11 thermal
overload relays are listed in the overview table (see Overload
Relays, General Data).
■ Application
Industries
The 3RU11 thermal overload relays are suitable for customers
from all industries who want to guarantee optimum inverse-time
delayed protection of their electrical loads (e.g. motors) under
normal starting conditions (CLASS 10).
Application
The 3RU11 thermal overload relays have been designed for the
protection of three-phase and single-phase AC and DC motors.
The 3RU11 thermal overload relays up to 100 A have been
designed for current-dependent protection of loads with normal
starting (see LV 1 T, Function) against excessive temperature
rises due to overload or phase failure. An overload or phase
failure results in an increase of the motor current beyond the set
motor rated current. Via heating elements, this current rise heats
up the bimetal strips inside the device, which then bend and as
a result trigger the auxiliary contacts by means of a tripping
mechanism. The auxiliary contacts then switch off the load by
means of a contactor. The break time depends on the ratio
between the tripping current and set current Ie and is stored in
the form of a long-term stable tripping characteristic (see LV 1 T,
Characteristic Curves).
Ambient conditions
The 3RU11 thermal overload relays have temperature
compensation in accordance with IEC 60947-4-1 for the
temperature range of –20 to +60 °C. For temperatures from
+60 to +80 °C the upper setpoint value of the setting range must
be reduced by the factor listed in the table below.
Ambient temperature in °C
Derating factor for
the upper setpoint value
+60
1.0
+65
0.94
+70
0.87
+75
0.81
+80
0.73
"Increased safety" type of protection EEx e according to
ATEX guideline 94/9/EC
The 3RU11 thermal overload relays are suitable for the overload
protection of explosion-proof motors with "increased safety" type
of protection EEx e. The relays meet the requirements of
EN 60079-7 (Electrical apparatus for potentially explosive
atmospheres – Increased safety "e").
The basic safety and health requirements of ATEX guideline
94/9/EG are fulfilled by compliance with
• EN 60947-4-1
• EN 60947-5-1
• EN 60079-14: 1997-02
• EN 60079-17: 1996-12
EU type test certificate for Category (2) G/D exists. It has the
number DMT 98 ATEX 6001.
The "tripped" status is signaled by means of a switch position
indicator (see LV 1 T, Function). Resetting takes place either
manually or automatically after the recovery time has elapsed
(see LV 1 T, Function).
The devices are manufactured in accordance with
environmental guidelines and contain environmentally friendly
and reusable materials.
They comply with all important worldwide standards and
approvals.
Siemens LV 1 · 2006
5/51
5
(1) Connection for mounting onto contactors:
Optimally adapted in electrical, mechanical and design terms to the
contactors, these connecting pins can be used for direct mounting of
the overload relays. Stand-alone installation is possible as an
alternative (in some cases in conjunction with a stand-alone
installation module).
(2) Selector switch for manual/automatic RESET and RESET button:
With this switch you can choose between manual and automatic
RESET. A device set to manual RESET can be reset locally by pressing
the RESET button. A remote RESET is possible using the RESET
modules (accessories), which are independent of size.
(3) Switch position indicator and TEST function of the wiring:
Indicates a trip and enables the wiring test.
(4) Motor current setting:
Setting the device to the rated motor current is easy with the large
rotary knob.
(5) STOP button:
If the STOP button is pressed, the NC contact is opened. This switches
off the contactor downstream. The contactor is switched on again
when the STOP button is released.
(6) Transparent, sealable cover:
Secures the motor current setting, TEST function and the selector
switch for manual/automatic RESET against adjustment.
(7) Supply terminals:
The generously sized terminals permit connection of two conductors
with different cross-sections for the main and auxiliary circuits. The
auxiliary circuit can be connected with screw-type terminals and
alternatively with spring-loaded terminals.
If single-phase AC or DC loads are to be protected by the 3RU11
thermal overload relays, all three bimetal strips must be heated.
For this purpose, all main circuits of the relay must be connected
in series.
Overload Relays
3RU1 Thermal Overload Relays
3RU11 for standard applications
■ Selection and ordering data
3RU11 thermal overload relays with screw connection on the auxiliary current side for direct mounting1), CLASS 10
•
•
•
•
Features and technical specifications:
• Overload and phase failure protection
• Auxiliary contacts 1 NO + 1 NC
• Manual and automatic RESET
Size
Contactor2)
Switch position indicator
TEST function
STOP button
Integrated, sealable cover
Rating
for induction
motor,
Rated value3)
Set current value
of the inversetime delayed
overload trip
Short-circuit DT Order No.
protection
with fuse,
type of coordination 2,
gL/gG
operational
class4)
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kW
A
A
0.04
0.06
0.06
0.09
0.11 ... 0.16
0.14 ... 0.2
0.18 ... 0.25
0.22 ... 0.32
0.5
1
1
1.6
A
A
}
}
3RU11 16-0AB0
3RU11 16-0BB0
3RU11 16-0CB0
3RU11 16-0DB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.150
0.150
0.150
0.150
0.09
0.12
0.18
0.18
0.28 ... 0.4
0.35 ... 0.5
0.45 ... 0.63
0.55 ... 0.8
2
2
2
4
}
}
}
}
3RU11 16-0EB0
3RU11 16-0FB0
3RU11 16-0GB0
3RU11 16-0HB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.150
0.150
0.150
0.150
0.25
0.37
0.55
0.75
0.7 ... 1
0.9 ... 1.25
1.1 ... 1.6
1.4 ... 2
4
4
6
6
}
}
}
}
3RU11 16-0JB0
3RU11 16-0KB0
3RU11 16-1AB0
3RU11 16-1BB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.150
0.150
0.150
0.150
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
10
10
16
20
}
}
}
}
3RU11 16-1CB0
3RU11 16-1DB0
3RU11 16-1EB0
3RU11 16-1FB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.150
0.150
0.150
0.150
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12
20
25
35
35
}
}
}
}
3RU11 16-1GB0
3RU11 16-1HB0
3RU11 16-1JB0
3RU11 16-1KB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.150
0.150
0.150
0.150
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
10
10
16
20
}
}
}
}
3RU11 26-1CB0
3RU11 26-1DB0
3RU11 26-1EB0
3RU11 26-1FB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12.5
20
25
35
35
}
}
}
}
3RU11 26-1GB0
3RU11 26-1HB0
3RU11 26-1JB0
3RU11 26-1KB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
7.5
7.5
11
11
11 ... 16
14 ... 20
17 ... 22
20 ... 25
40
50
63
63
}
}
}
}
3RU11 26-4AB0
3RU11 26-4BB0
3RU11 26-4CB0
3RU11 26-4DB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
3
4
5.5
5.5 ... 8
7 ... 10
9 ... 12.5
25
35
35
A
A
A
3RU11 36-1HB0
3RU11 36-1JB0
3RU11 36-1KB0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.320
0.320
0.320
7.5
7.5
11
15
11 ... 16
14 ... 20
18 ... 25
22 ... 32
40
50
63
80
}
}
}
}
3RU11 36-4AB0
3RU11 36-4BB0
3RU11 36-4DB0
3RU11 36-4EB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.320
0.320
0.320
0.320
18.5
22
22
28 ... 40
36 ... 45
40 ... 50
80
100
100
}
}
}
3RU11 36-4FB0
3RU11 36-4GB0
3RU11 36-4HB0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.320
0.320
0.320
11
15
18 ... 25
22 ... 32
63
80
A
A
3RU11 46-4DB0
3RU11 46-4EB0
1
1
1 unit
1 unit
101
101
0.550
0.550
18.5
22
30
37
28 ... 40
36 ... 50
45 ... 63
57 ... 75
80
125
125
160
}
}
}
}
3RU11 46-4FB0
3RU11 46-4HB0
3RU11 46-4JB0
3RU11 46-4KB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.550
0.550
0.550
0.550
45
45
70 ... 90
80 ... 1005)
160
200
}
}
3RU11 46-4LB0
3RU11 46-4MB0
1
1
1 unit
1 unit
101
101
0.550
0.550
kg
Size S00
S00
5
3RU11 16 -..B0
Size S0
S0
3RU11 26 -..B0
Size S2
S2
3RU11 36 -..B0
Size S3
S3
3RU11 46 -..B0
1) With the suitable terminal brackets (see Accessories) the 3RU11 overload
relays for direct mounting can also be installed as stand-alone units.
2) Observe maximum rated operational current of the devices.
3) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
4) Maximum fuse for overload relay, type of coordination 2. For fuse values in
conjunction with contactors, see Technical Specifications, Short-Circuit
Protection with Fuses/Motor Starter Protectors for Motor Feeders.
5) For overload relays > 100 A, see 3RB2.
* You can order this quantity or a multiple thereof.
5/52
Siemens LV 1 · 2006
Overload Relays
3RU1 Thermal Overload Relays
3RU11 for standard applications
3RU11 thermal overload relays with screw connection on the auxiliary current side for stand alone installation1), CLASS 10
•
•
•
•
Features and technical specifications:
• Overload and phase failure protection
• Auxiliary contacts 1 NO + 1 NC
• Manual and automatic RESET
Size
Contactor2)
Switch position indicator
TEST function
STOP button
Integrated, sealable cover
Rating
for induction
motor,
Rated value3)
Set current value
of the inversetime delayed
overload trip
Short-circuit DT Order No.
protection
with fuse,
type of coordination 2,
gL/gG
operational
class4)
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kW
A
A
0.04
0.06
0.06
0.09
0.11 ... 0.16
0.14 ... 0.2
0.18 ... 0.25
0.22 ... 0.32
0.5
1
1
1.6
B
B
B
B
3RU11 16-0AB1
3RU11 16-0BB1
3RU11 16-0CB1
3RU11 16-0DB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.180
0.180
0.180
0.180
0.09
0.12
0.18
0.18
0.28 ... 0.4
0.35 ... 0.5
0.45 ... 0.63
0.55 ... 0.8
2
2
2
4
A
A
A
A
3RU11 16-0EB1
3RU11 16-0FB1
3RU11 16-0GB1
3RU11 16-0HB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.180
0.180
0.180
0.180
0.25
0.37
0.55
0.75
0.7 ... 1
0.9 ... 1.25
1.1 ... 1.6
1.4 ... 2
4
4
6
6
}
A
}
}
3RU11 16-0JB1
3RU11 16-0KB1
3RU11 16-1AB1
3RU11 16-1BB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.180
0.180
0.180
0.180
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
10
10
16
20
}
}
}
}
3RU11 16-1CB1
3RU11 16-1DB1
3RU11 16-1EB1
3RU11 16-1FB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.180
0.180
0.180
0.180
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12
20
25
35
35
}
}
}
A
3RU11 16-1GB1
3RU11 16-1HB1
3RU11 16-1JB1
3RU11 16-1KB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.180
0.180
0.180
0.180
S0
7.5
7.5
11
11
11 ... 16
14 ... 20
17 ... 22
20 ... 25
40
50
63
63
}
}
A
}
3RU11 26-4AB1
3RU11 26-4BB1
3RU11 26-4CB1
3RU11 26-4DB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.240
0.240
0.240
0.240
S2
15
18.5
22
22
22 ... 32
28 ... 40
36 ... 45
40 ... 50
80
80
100
100
}
}
A
A
3RU11 36-4EB1
3RU11 36-4FB1
3RU11 36-4GB1
3RU11 36-4HB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.480
0.480
0.480
0.480
S3
30
37
45
45
45 ... 63
57 ... 75
70 ... 90
80 ... 1005)
125
160
160
200
}
A
A
A
3RU11 46-4JB1
3RU11 46-4KB1
3RU11 46-4LB1
3RU11 46-4MB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.810
0.810
0.810
0.810
kg
S00
Size S0
Size S2
Size S3
1) Size S00 to S3 for screw and snap-on mounting onto TH 35 standard
mounting rails, size S3 also for TH 75 standard mounting rails.
2) Observe maximum rated operational current of the devices.
3) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
4) Maximum fuse for overload relay, type of coordination 2. For fuse values in
conjunction with contactors, see Technical Specifications, Short-Circuit
Protection with Fuses/Motor Starter Protectors for Motor Feeders.
5) For overload relays > 100 A, see 3RB2.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/53
5
Size S00
Overload Relays
3RU1 Thermal Overload Relays
3RU11 for standard applications
3RU11 thermal overload relays with Cage Clamp connection for direct mounting1) and stand-alone installation2), CLASS 10
•
•
•
•
Features and technical specifications:
• Overload and phase failure protection
• Auxiliary contacts 1 NO + 1 NC
• Manual and automatic RESET
Size
Contactor3)
Switch position indicator
TEST function
STOP button
Integrated, sealable cover
Rating
for induction
motor
Rated value4)
Set current value
of the inversetime delayed
overload trip
Short-circuit DT Order No.
protection
with fuse,
type of coordination 2,
gL/gG
operational
class5)
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kW
A
A
0.04
0.06
0.06
0.09
0.11 ... 0.16
0.14 ... 0.2
0.18 ... 0.25
0.22 ... 0.32
0.5
1
1
1.6
B
B
B
B
3RU11 16-0AC1
3RU11 16-0BC1
3RU11 16-0CC1
3RU11 16-0DC1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
0.09
0.12
0.18
0.18
0.28 ... 0.4
0.35 ... 0.5
0.45 ... 0.63
0.55 ... 0.8
2
2
2
4
B
B
A
A
3RU11 16-0EC1
3RU11 16-0FC1
3RU11 16-0GC1
3RU11 16-0HC1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
0.25
0.37
0.55
0.75
0.7 ... 1
0.9 ... 1.25
1.1 ... 1.6
1.4 ... 2
4
4
6
6
A
A
A
A
3RU11 16-0JC1
3RU11 16-0KC1
3RU11 16-1AC1
3RU11 16-1BC1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
10
10
16
20
A
A
A
A
3RU11 16-1CC1
3RU11 16-1DC1
3RU11 16-1EC1
3RU11 16-1FC1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12
20
25
35
35
A
A
A
A
3RU11 16-1GC1
3RU11 16-1HC1
3RU11 16-1JC1
3RU11 16-1KC1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
10
10
16
20
B
B
B
B
3RU11 26-1CD0
3RU11 26-1DD0
3RU11 26-1ED0
3RU11 26-1FD0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12.5
20
25
35
35
B
B
B
B
3RU11 26-1GD0
3RU11 26-1HD0
3RU11 26-1JD0
3RU11 26-1KD0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
7.5
7.5
11
11
11 ... 16
14 ... 20
17 ... 22
20 ... 25
40
50
63
63
A
A
A
A
3RU11 26-4AD0
3RU11 26-4BD0
3RU11 26-4CD0
3RU11 26-4DD0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
3
4
5.5
7.5
5.5 ... 8
7 ... 10
9 ... 12.5
11 ... 16
25
35
35
40
B
B
B
B
3RU11 36-1HD0
3RU11 36-1JD0
3RU11 36-1KD0
3RU11 36-4AD0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.320
0.320
0.320
0.320
7.5
11
15
14 ... 20
18 ... 25
22 ... 32
50
63
80
B
B
A
3RU11 36-4BD0
3RU11 36-4DD0
3RU11 36-4ED0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.320
0.320
0.320
18.5
22
22
28 ... 40
36 ... 45
40 ... 50
80
100
100
A
A
A
3RU11 36-4FD0
3RU11 36-4GD0
3RU11 36-4HD0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.320
0.320
0.320
11
15
18.5
22
18 ... 25
22 ... 32
28 ... 40
36 ... 50
63
80
80
125
B
B
B
B
3RU11 46-4DD0
3RU11 46-4ED0
3RU11 46-4FD0
3RU11 46-4HD0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.550
0.550
0.550
0.550
30
37
45
45
45 ... 63
57 ... 75
70 ... 90
80 ... 100
125
160
160
200
A
A
A
A
3RU11 46-4JD0
3RU11 46-4KD0
3RU11 46-4LD0
3RU11 46-4MD0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.550
0.550
0.550
0.550
kg
Size S00 for stand-alone installation6)
S00
5
3RU11 16 -..C1
Size S0 for direct mounting1)7)
S0
3RU11 16-..D0
Size S2 for direct mounting1)7)
S2
3RU11 36-..D0
Size S3 for direct mounting1)7)
S3
3RU11 46-..D0
1) With the suitable terminal brackets (see Accessories) the 3RU11 overload
relays for direct mounting can also be installed as stand-alone units.
2) Size S00 for screw and snap-on mounting onto TR35 standard mounting
rail.
3) Observe maximum rated operational current of the devices.
4) Standard value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
5) Maximum fuse for overload relay, type of coordination 2. For fuse values in
conjunction with contactors, see Technical Specifications, Short-Circuit
Protection with Fuses/Motor Starter Protectors for Motor Feeders.
6) Auxiliary and main conductor terminals with Cage Clamp connection.
7) Auxiliary conductor terminals with Cage Clamp connection and main
conductor terminals with screw connection.
* You can order this quantity or a multiple thereof.
5/54
Siemens LV 1 · 2006
Overload Relays
3RU1 Thermal Overload Relays
Accessories
■ Overview
The following accessories are available for the 3RU11 thermal
overload relays:
• For the four overload relay sizes S00 to S3 one terminal
bracket each for stand-alone installation
• One electrical remote RESET module in three voltage variants
for all sizes
• One mechanical RESET module for all sizes
• One cable release for resetting devices which are difficult to
access (for all sizes)
• Terminal covers
■ Selection and ordering data
Version
Size
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Terminal brackets for stand-alone installation
For separate mounting of overload relays;
screw and snap-on mounting onto TH35
standard mounting rail; size S3 also for
TH75 standard mounting rail
S00
}
3RU19 16-3AA01
1
1 unit
101
0.060
S0
}
3RU19 26-3AA01
1
1 unit
101
0.080
S2
}
3RU19 36-3AA01
1
1 unit
101
0.180
S3
}
3RU19 46-3AA01
1
1 unit
101
0.280
3RU19 0.6-3AA01
Resetting plungers, holders and formers S00 ...S3
}
3RU19 00-1A
1
1 set
101
0.038
Pushbuttons with extended stroke
(12 mm), IP65, Ø 22 mm
B
3SB30 00-0EA11
1
1 unit
102
0.021
Extension plungers
For compensation of the distance between
a pushbutton and the unlatching button of
the relay
A
3SX1 335
1
1 unit
102
0.004
• Length 400 mm
}
3RU19 00-1B
1
1 unit
101
0.063
• Length 600 mm
}
3RU19 00-1C
1
1 unit
101
0.073
3RU19 00-1A
with pushbutton and
extension plunger
Cable releases with holder for RESET1)
For 6.5 mm Ø hole
in the mounting plate;
max. 8 mm control panel thickness
S00 ...S3
3RU19 00-1.
Modules for remote RESET, electrical
Operating range
0.85 ... 1.1 x Us,
power consumption
80 VA AC, 70 W DC,
ON period
0.2 ... 4 s,
operating frequency
60/h
}
3RU19 00-2AB71
1
1 unit
101
0.066
110 ... 127 V AC/DC
}
3RU19 00-2AF71
1
1 unit
101
0.067
220 ... 250 V AC/DC
}
3RU19 00-2AM71
1
1 unit
101
0.066
}
3RT19 46-4EA1
1
1 unit
101
0.037
24 ... 30 V AC/DC
S00 ...S3
3RU19 00-2A.71
Terminal covers1)
Covers for cable lug and rail connections
• Length 55 mm
S3
Covers for box terminals
• Length 20.6 mm
S2
}
3RT19 36-4EA2
1
1 unit
101
0.016
• Length 20.8 mm
S3
}
3RT19 46-4EA2
1
1 unit
101
0.023
1) The accessories are identical to those of the 3RB2 solid-state overload
relays.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
5/55
5
Mechanical RESET1)
Overload Relays
3RU1 Thermal Overload Relays
Accessories
Version
Size/
Color
Use
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Tools for opening Cage Clamp terminals
3.5 x 0.5 mm,
suitable for a max.
conductor crosssection of 2.5 mm2
Length approx.
175 mm;
green; partially
insulated
SIRIUS units A
with springloaded/
Cage Clamp
connections
8WA2 880
1
1 unit
041
0.012
Length approx.
175 mm;
green
A
8WA2 803
1
1 unit
041
0.024
Length approx.
160 mm;
green
A
8WA2 807
1
1 unit
041
0.023
D
3RT19 00-1SB10
100
816 units
101
0.240
20 mm x 7 mm
pastel turquoise
C
3RT19 00-1SB20
100
340 units
101
0.220
19 mm x 6 mm 3RU11,
pastel turquoise 3RB2
D
3RT19 00-1SB60
100
3060 units
101
0.155
19 mm x 6 mm
zinc yellow
C
3RT19 00-1SD60
100
3060 units
101
0.120
8WA2 880
8WA2 803
2.5 x 0.4 mm,
suitable for a max.
conductor crosssection of 1.5 mm2
8WA2 807
Blank labeling plates
Labeling plates for
sticking (labels)
For SIRIUS devices
NSK-7237
5
Device labeling plates 10 mm x 7 mm 3RU11,
For SIRIUS devices
pastel turquoise 3RB2
3RT19 00-1SB10
PC labeling system
For individual inscription
of device labeling plates
Obtainable from:
murrplastik Systemtechnik GmbH
(http://www.murrplastik.com)
* You can order this quantity or a multiple thereof.
5/56