Data sheet
3RV2011-1BA15
Circuit breaker size S00 for motor protection, CLASS 10 A-release 1.4...2 A
N-release 26 A screw terminal Standard switching capacity with transverse
auxiliary switches 1 NO+1 NC
product brand name
SIRIUS
product designation
Circuit breaker
design of the product
For motor protection
product type designation
3RV2
General technical data
size of the circuit-breaker
S00
size of contactor can be combined company-specific
S00, S0
product extension auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
7.25 W
● at AC in hot operating state per pole
2.4 W
insulation voltage with degree of pollution 3 at AC rated
value
690 V
surge voltage resistance rated value
6 kV
shock resistance according to IEC 60068-2-27
25g / 11 ms
mechanical service life (switching cycles)
● of the main contacts typical
100 000
● of auxiliary contacts typical
100 000
electrical endurance (switching cycles) typical
100 000
type of protection according to ATEX directive
2014/34/EU
Ex II (2) GD
certificate of suitability according to ATEX directive
2014/34/EU
DMT 02 ATEX F 001
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
10/01/2009
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-20 ... +60 °C
● during storage
-50 ... +80 °C
● during transport
-50 ... +80 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the
current-dependent overload release
1.4 ... 2 A
operating voltage
● rated value
20 ... 690 V
● at AC-3 rated value maximum
690 V
● at AC-3e rated value maximum
690 V
3RV20111BA15
Page 1/5
7/4/2022
Subject to change without notice
© Copyright Siemens
operating frequency rated value
50 ... 60 Hz
operational current rated value
2A
operational current
● at AC-3 at 400 V rated value
2A
● at AC-3e at 400 V rated value
2A
operating power
● at AC-3
— at 230 V rated value
0.4 kW
— at 400 V rated value
0.75 kW
— at 500 V rated value
0.8 kW
— at 690 V rated value
1.1 kW
● at AC-3e
— at 230 V rated value
0.4 kW
— at 400 V rated value
0.75 kW
— at 500 V rated value
0.8 kW
— at 690 V rated value
1.1 kW
operating frequency
● at AC-3 maximum
15 1/h
● at AC-3e maximum
15 1/h
Auxiliary circuit
design of the auxiliary switch
transverse
number of NC contacts for auxiliary contacts
1
number of NO contacts for auxiliary contacts
1
number of CO contacts for auxiliary contacts
0
operational current of auxiliary contacts at AC-15
● at 24 V
2A
● at 120 V
0.5 A
● at 125 V
0.5 A
● at 230 V
0.5 A
operational current of auxiliary contacts at DC-13
● at 24 V
1A
● at 60 V
0.15 A
Protective and monitoring functions
product function
● ground fault detection
No
● phase failure detection
Yes
trip class
CLASS 10
design of the overload release
thermal
breaking capacity maximum short-circuit current (Icu)
● at AC at 240 V rated value
100 kA
● at AC at 400 V rated value
100 kA
● at AC at 500 V rated value
100 kA
● at AC at 690 V rated value
10 kA
breaking capacity operating short-circuit current (Ics)
at AC
● at 240 V rated value
100 kA
● at 400 V rated value
100 kA
● at 500 V rated value
100 kA
● at 690 V rated value
10 kA
response value current of instantaneous short-circuit trip
unit
26 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
2A
● at 600 V rated value
2A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 230 V rated value
0.13 hp
● for 3-phase AC motor
— at 460/480 V rated value
3RV20111BA15
Page 2/5
1 hp
7/4/2022
Subject to change without notice
© Copyright Siemens
— at 575/600 V rated value
contact rating of auxiliary contacts according to UL
1 hp
C300 / R300
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
design of the fuse link
● for short-circuit protection of the auxiliary switch
required
Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current
Ik < 400 A)
design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 400 V
gL/gG 25 A
● at 500 V
gL/gG 25 A
● at 690 V
gL/gG 20 A
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height
97 mm
width
45 mm
depth
97 mm
required spacing
● for grounded parts at 400 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for live parts at 400 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for grounded parts at 500 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for live parts at 500 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for grounded parts at 690 V
— downwards
50 mm
— upwards
50 mm
— backwards
0 mm
— at the side
30 mm
— forwards
0 mm
● for live parts at 690 V
— downwards
50 mm
— upwards
50 mm
— backwards
0 mm
— at the side
30 mm
— forwards
0 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
screw-type terminals
arrangement of electrical connectors for main current
circuit
Top and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded
2x (0,75 ... 2,5 mm²), 2x 4 mm²
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for main contacts
2x (18 ... 14), 2x 12
type of connectable conductor cross-sections
3RV20111BA15
Page 3/5
7/4/2022
Subject to change without notice
© Copyright Siemens
● for auxiliary contacts
— solid or stranded
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14)
tightening torque
● for main contacts with screw-type terminals
0.8 ... 1.2 N·m
● for auxiliary contacts with screw-type terminals
0.8 ... 1.2 N·m
design of screwdriver shaft
Diameter 5 to 6 mm
size of the screwdriver tip
Pozidriv size 2
design of the thread of the connection screw
● for main contacts
M3
● of the auxiliary and control contacts
M3
Safety related data
B10 value
● with high demand rate according to SN 31920
5 000
proportion of dangerous failures
● with low demand rate according to SN 31920
50 %
● with high demand rate according to SN 31920
50 %
failure rate [FIT]
● with low demand rate according to SN 31920
50 FIT
T1 value for proof test interval or service life according to
IEC 61508
10 y
protection class IP on the front according to IEC
60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
display version for switching status
Handle
Certificates/ approvals
General Product Approval
Confirmation
For use in hazardous locations
KC
Declaration of Conformity
Test Certificates
Type Test Certificates/Test Report
Special Test Certificate
Marine / Shipping
Marine / Shipping
other
Railway
Confirmation
Confirmation
Vibration and Shock
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
3RV20111BA15
Page 4/5
7/4/2022
Subject to change without notice
© Copyright Siemens
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2011-1BA15
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2011-1BA15
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2011-1BA15
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2011-1BA15&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2011-1BA15/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2011-1BA15&objecttype=14&gridview=view1
last modified:
3RV20111BA15
Page 5/5
6/25/2022
7/4/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RV20111BA15”相匹配的价格&库存,您可以联系我们找货
免费人工找货