Data sheet
3RV2011-1FA10-0BA0
Special type Circuit breaker size S00 for motor protection, CLASS 10 Arelease 3.5...5 A N release 65 A screw terminal Standard switching
capacity Ambient temperature -50 °C 500 switching cycles
product brand name
SIRIUS
product designation
Circuit breaker
design of the product
For motor protection
product type designation
3RV2
General technical data
size of the circuit-breaker
S00
size of contactor can be combined company-specific
S00, S0
product extension auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
7.25 W
● at AC in hot operating state per pole
2.4 W
insulation voltage with degree of pollution 3 at AC rated
value
690 V
surge voltage resistance rated value
6 kV
maximum permissible voltage for safe isolation in
networks with grounded star point
● between main and auxiliary circuit
400 V
● between main and auxiliary circuit
400 V
shock resistance acc. to IEC 60068-2-27
25g / 11 ms
mechanical service life (switching cycles)
● of the main contacts typical
500
● of auxiliary contacts typical
500
electrical endurance (switching cycles) typical
500
reference code acc. to IEC 81346-2
Q
Substance Prohibitance (Date)
01.10.2009 00:00:00
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
● ambient temperature during operation
-50 ... +60 °C
● ambient temperature during storage
-50 ... +80 °C
● ambient temperature during transport
-50 ... +80 °C
temperature compensation
-20 ... +60 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the
current-dependent overload release
3.5 ... 5 A
● operating voltage rated value
690 V
● operating voltage at AC-3 rated value maximum
690 V
3RV20111FA100BA0
Page 1/2
1.21.2021
Subject to change without notice
© Copyright Siemens
operating frequency rated value
50 ... 60 Hz
operational current rated value
5A
operational current at AC-3 at 400 V rated value
5A
operating power at AC-3
● at 230 V rated value
1 100 W
● at 400 V rated value
1 500 W
● at 500 V rated value
2 200 W
● at 690 V rated value
4 000 W
operating frequency at AC-3 maximum
15 1/h
Auxiliary circuit
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
0
number of CO contacts for auxiliary contacts
0
Protective and monitoring functions
product function
● ground fault detection
No
● phase failure detection
Yes
trip class
CLASS 10
design of the overload release
thermal
breaking capacity operating short-circuit current (Ics)
at AC
● at 240 V rated value
100 kA
● at 400 V rated value
100 kA
● at 500 V rated value
100 kA
● at 690 V rated value
4 kA
breaking capacity maximum short-circuit current (Icu)
● at AC at 240 V rated value
100 kA
● at AC at 400 V rated value
100 kA
● at AC at 500 V rated value
100 kA
● at AC at 690 V rated value
6 kA
response value current of instantaneous short-circuit trip
unit
65 A
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 400 V
gG 32 A
● at 500 V
gG 32 A
● at 690 V
gG 25 A
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height
97 mm
width
45 mm
depth
97 mm
required spacing
● for grounded parts at 400 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for live parts at 400 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for grounded parts at 500 V
— downwards
30 mm
— upwards
30 mm
3RV20111FA100BA0
Page 2/3
1.21.2021
Subject to change without notice
© Copyright Siemens
— at the side
9 mm
● for live parts at 500 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for grounded parts at 690 V
— downwards
50 mm
— upwards
50 mm
— backwards
0 mm
— at the side
30 mm
— forwards
0 mm
● for live parts at 690 V
— downwards
50 mm
— upwards
50 mm
— backwards
0 mm
— at the side
30 mm
— forwards
0 mm
Connections/ Terminals
product function removable terminal for auxiliary and
control circuit
No
type of electrical connection
● for main current circuit
screw-type terminals
arrangement of electrical connectors for main current
circuit
Top and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded
2x (0,75 ... 2,5 mm²), 2x 4 mm²
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● tightening torque for main contacts with screw-type
terminals
0.8 ... 1.2 N·m
design of screwdriver shaft
Diameter 5 to 6 mm
size of the screwdriver tip
Pozidriv 2
design of the thread of the connection screw
● for main contacts
M3
Safety related data
T1 value for proof test interval or service life acc. to
IEC 61508
10 y
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe, for vertical contact from the front
display version for switching status
Handle
Certificates/ approvals
General Product
Approval
Declaration of Conformity
Miscellaneous
Test Certificates
Type Test
Certificates/Test
Report
Marine / Shipping
Special Test
Certificate
Marine / Shipping
other
3RV20111FA100BA0
Page 3/4
Railway
1.21.2021
Subject to change without notice
© Copyright Siemens
Confirmation
Vibration and Shock
Confirmation
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2011-1FA10-0BA0
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2011-1FA10-0BA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2011-1FA10-0BA0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2011-1FA10-0BA0&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2011-1FA10-0BA0/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2011-1FA10-0BA0&objecttype=14&gridview=view1
3RV20111FA100BA0
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
3RV20111FA100BA0
Page 5/6
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RV20111FA100BA0
Page 6/6
12/15/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RV20111FA100BA0”相匹配的价格&库存,您可以联系我们找货
免费人工找货