Data sheet
3RV2011-1JA20
Circuit breaker size S00 for motor protection, CLASS 10 A-release 7...10 A
N release 130 A Spring-type terminal Standard switching capacity
product brand name
SIRIUS
product designation
Circuit breaker
design of the product
For motor protection
product type designation
3RV2
General technical data
size of the circuit-breaker
S00
size of contactor can be combined company-specific
S00, S0
product extension auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
9.25 W
● at AC in hot operating state per pole
3.1 W
insulation voltage with degree of pollution 3 at AC rated
value
690 V
surge voltage resistance rated value
6 kV
shock resistance according to IEC 60068-2-27
25g / 11 ms
mechanical service life (switching cycles)
● of the main contacts typical
100 000
● of auxiliary contacts typical
100 000
electrical endurance (switching cycles) typical
100 000
type of protection according to ATEX directive
2014/34/EU
Ex II (2) GD
certificate of suitability according to ATEX directive
2014/34/EU
DMT 02 ATEX F 001
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
10/01/2009
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-20 ... +60 °C
● during storage
-50 ... +80 °C
● during transport
-50 ... +80 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the
current-dependent overload release
7 ... 10 A
operating voltage
● rated value
20 ... 690 V
● at AC-3 rated value maximum
690 V
● at AC-3e rated value maximum
690 V
3RV20111JA20
Page 1/5
7/4/2022
Subject to change without notice
© Copyright Siemens
operating frequency rated value
50 ... 60 Hz
operational current rated value
10 A
operational current
● at AC-3 at 400 V rated value
10 A
● at AC-3e at 400 V rated value
10 A
operating power
● at AC-3
— at 230 V rated value
2.2 kW
— at 400 V rated value
4 kW
— at 500 V rated value
5.5 kW
— at 690 V rated value
7.5 kW
● at AC-3e
— at 230 V rated value
2.2 kW
— at 400 V rated value
4 kW
— at 500 V rated value
5.5 kW
— at 690 V rated value
7.5 kW
operating frequency
● at AC-3 maximum
15 1/h
● at AC-3e maximum
15 1/h
Auxiliary circuit
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
0
number of CO contacts for auxiliary contacts
0
Protective and monitoring functions
product function
● ground fault detection
No
● phase failure detection
Yes
trip class
CLASS 10
design of the overload release
thermal
breaking capacity maximum short-circuit current (Icu)
● at AC at 240 V rated value
100 kA
● at AC at 400 V rated value
100 kA
● at AC at 500 V rated value
42 kA
● at AC at 690 V rated value
6 kA
breaking capacity operating short-circuit current (Ics)
at AC
● at 240 V rated value
100 kA
● at 400 V rated value
100 kA
● at 500 V rated value
42 kA
● at 690 V rated value
4 kA
response value current of instantaneous short-circuit trip
unit
130 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
10 A
● at 600 V rated value
10 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
0.5 hp
— at 230 V rated value
1.5 hp
● for 3-phase AC motor
— at 200/208 V rated value
2 hp
— at 220/230 V rated value
3 hp
— at 460/480 V rated value
5 hp
— at 575/600 V rated value
10 hp
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
design of the fuse link for IT network for short-circuit
protection of the main circuit
3RV20111JA20
Page 2/5
7/4/2022
Subject to change without notice
© Copyright Siemens
● at 400 V
gL/gG 50 A
● at 500 V
gL/gG 40 A
● at 690 V
gL/gG 40 A
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height
106 mm
width
45 mm
depth
97 mm
required spacing
● for grounded parts at 400 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for live parts at 400 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for grounded parts at 500 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for live parts at 500 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for grounded parts at 690 V
— downwards
50 mm
— upwards
50 mm
— backwards
0 mm
— at the side
30 mm
— forwards
0 mm
● for live parts at 690 V
— downwards
50 mm
— upwards
50 mm
— backwards
0 mm
— at the side
30 mm
— forwards
0 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
arrangement of electrical connectors for main current
circuit
spring-loaded terminals
Top and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded
2x (0,5 ... 4 mm²)
— finely stranded with core end processing
2x (0.5 ... 2.5 mm²)
— finely stranded without core end processing
2x (0.5 ... 2.5 mm²)
● at AWG cables for main contacts
2x (20 ... 12)
design of screwdriver shaft
Diameter 3 mm
size of the screwdriver tip
3,0 x 0,5 mm
Safety related data
B10 value
● with high demand rate according to SN 31920
5 000
proportion of dangerous failures
● with low demand rate according to SN 31920
50 %
● with high demand rate according to SN 31920
50 %
failure rate [FIT]
● with low demand rate according to SN 31920
3RV20111JA20
Page 3/5
50 FIT
7/4/2022
Subject to change without notice
© Copyright Siemens
T1 value for proof test interval or service life according to
IEC 61508
10 y
protection class IP on the front according to IEC
60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
display version for switching status
Handle
Certificates/ approvals
General Product Approval
Confirmation
For use in hazardous locations
KC
Declaration of Conformity
Test Certificates
Type Test Certificates/Test Report
Special Test Certificate
Marine / Shipping
Marine / Shipping
other
Confirmation
Railway
Vibration and Shock
Confirmation
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2011-1JA20
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2011-1JA20
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2011-1JA20
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2011-1JA20&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2011-1JA20/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2011-1JA20&objecttype=14&gridview=view1
3RV20111JA20
Page 4/5
7/4/2022
Subject to change without notice
© Copyright Siemens
last modified:
3RV20111JA20
Page 5/5
6/25/2022
7/4/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RV20111JA20”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+1849.521761+229.43232
- 5+1746.748775+216.68338
- 10+1541.2556910+191.19206
- 50+1337.8936650+165.96509