Data sheet
3RV2031-4BA10
Circuit breaker size S2 for motor protection, CLASS 10 A-release 14...20 A
N-release 260 A screw terminal Standard switching capacity
product brand name
SIRIUS
product designation
Circuit breaker
design of the product
For motor protection
product type designation
3RV2
General technical data
size of the circuit-breaker
S2
size of contactor can be combined company-specific
S2
product extension auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
14.5 W
● at AC in hot operating state per pole
4.8 W
insulation voltage with degree of pollution 3 at AC rated
value
690 V
surge voltage resistance rated value
6 kV
shock resistance according to IEC 60068-2-27
25g / 11 ms Sinus
mechanical service life (switching cycles)
● of the main contacts typical
50 000
● of auxiliary contacts typical
50 000
electrical endurance (switching cycles) typical
50 000
type of protection according to ATEX directive
2014/34/EU
Ex II (2) GD
certificate of suitability according to ATEX directive
2014/34/EU
DMT 02 ATEX F 001
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
10/15/2014
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-20 ... +60 °C
● during storage
-50 ... +80 °C
● during transport
-50 ... +80 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the
current-dependent overload release
14 ... 20 A
operating voltage
● rated value
20 ... 690 V
● at AC-3 rated value maximum
690 V
● at AC-3e rated value maximum
690 V
3RV20314BA10
Page 1/4
7/5/2022
Subject to change without notice
© Copyright Siemens
operating frequency rated value
50 ... 60 Hz
operational current rated value
20 A
operational current
● at AC-3 at 400 V rated value
20 A
● at AC-3e at 400 V rated value
20 A
operating power
● at AC-3
— at 230 V rated value
5.5 kW
— at 400 V rated value
7.5 kW
— at 500 V rated value
11 kW
— at 690 V rated value
15 kW
● at AC-3e
— at 230 V rated value
5.5 kW
— at 400 V rated value
7.5 kW
— at 500 V rated value
11 kW
— at 690 V rated value
15 kW
operating frequency
● at AC-3 maximum
15 1/h
● at AC-3e maximum
15 1/h
Protective and monitoring functions
product function
● ground fault detection
No
● phase failure detection
Yes
trip class
CLASS 10
design of the overload release
thermal
breaking capacity maximum short-circuit current (Icu)
● at AC at 240 V rated value
100 kA
● at AC at 400 V rated value
65 kA
● at AC at 500 V rated value
12 kA
● at AC at 690 V rated value
5 kA
breaking capacity operating short-circuit current (Ics)
at AC
● at 240 V rated value
100 kA
● at 400 V rated value
30 kA
● at 500 V rated value
6 kA
● at 690 V rated value
3 kA
response value current of instantaneous short-circuit trip
unit
260 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
20 A
● at 600 V rated value
20 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
1.5 hp
— at 230 V rated value
3 hp
● for 3-phase AC motor
— at 200/208 V rated value
7.5 hp
— at 220/230 V rated value
7.5 hp
— at 460/480 V rated value
15 hp
— at 575/600 V rated value
20 hp
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 240 V
none required
● at 400 V
100
● at 500 V
80
● at 690 V
63
3RV20314BA10
Page 2/4
7/5/2022
Subject to change without notice
© Copyright Siemens
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height
140 mm
width
55 mm
depth
149 mm
required spacing
● for grounded parts at 400 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for live parts at 400 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for grounded parts at 500 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for live parts at 500 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for grounded parts at 690 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for live parts at 690 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
arrangement of electrical connectors for main current
circuit
screw-type terminals
Top and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded
2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
— finely stranded with core end processing
2x (1 ... 16 mm²), 1x (1 ... 25 mm²)
● at AWG cables for main contacts
2x (18 ... 3), 1x (18 ... 2)
tightening torque
● for main contacts with screw-type terminals
3 ... 4.5 N·m
design of screwdriver shaft
Diameter 5 to 6 mm
size of the screwdriver tip
Pozidriv size 2
design of the thread of the connection screw
● for main contacts
M6
Safety related data
B10 value
● with high demand rate according to SN 31920
5 000
proportion of dangerous failures
● with low demand rate according to SN 31920
50 %
● with high demand rate according to SN 31920
50 %
failure rate [FIT]
● with low demand rate according to SN 31920
50 FIT
T1 value for proof test interval or service life according to
IEC 61508
10 y
protection class IP on the front according to IEC
60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
3RV20314BA10
Page 3/4
7/5/2022
Subject to change without notice
© Copyright Siemens
display version for switching status
Handle
Certificates/ approvals
General Product Approval
Confirmation
For use in hazardous locations
KC
Declaration of Conformity
Test Certificates
Type Test Certificates/Test Report
Special Test Certificate
Marine / Shipping
Marine / Shipping
other
Railway
Confirmation
Confirmation
Vibration and Shock
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2031-4BA10
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2031-4BA10
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2031-4BA10
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2031-4BA10&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2031-4BA10/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2031-4BA10&objecttype=14&gridview=view1
last modified:
3RV20314BA10
Page 4/4
6/25/2022
7/5/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RV20314BA10”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+2645.020341+328.11355
- 5+2199.634075+272.86359
- 10+2030.4122210+251.87170