Data sheet
3RV2032-4RA15
Circuit breaker size S2 for motor protection, CLASS 10 A-release 70...80 A Nrelease 1040 A screw terminal increased switching capacity with transverse
auxiliary switches 1 NO+1 NC
product brand name
SIRIUS
product designation
Circuit breaker
design of the product
For motor protection
product type designation
3RV2
General technical data
size of the circuit-breaker
S2
size of contactor can be combined company-specific
S2
product extension auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
29.5 W
● at AC in hot operating state per pole
9.8 W
insulation voltage with degree of pollution 3 at AC rated value
690 V
surge voltage resistance rated value
6 kV
shock resistance according to IEC 60068-2-27
25g / 11 ms Sinus
mechanical service life (operating cycles)
● of the main contacts typical
20 000
● of auxiliary contacts typical
20 000
electrical endurance (operating cycles) typical
20 000
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
03/01/2017
SVHC substance name
Lead - 7439-92-1
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-20 ... +60 °C
● during storage
-50 ... +80 °C
● during transport
-50 ... +80 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the currentdependent overload release
70 ... 80 A
operating voltage
● rated value
20 ... 690 V
● at AC-3 rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current rated value
80 A
3RV20324RA15
Page 1/6
4/19/2024
Subject to change without notice
© Copyright Siemens
operational current
● at AC-3 at 400 V rated value
80 A
operating power
● at AC-3
— at 230 V rated value
22 kW
— at 400 V rated value
37 kW
— at 500 V rated value
55 kW
— at 690 V rated value
75 kW
operating frequency
● at AC-3 maximum
15 1/h
Auxiliary circuit
design of the auxiliary switch
transverse
number of NC contacts for auxiliary contacts
1
number of NO contacts for auxiliary contacts
1
operational current of auxiliary contacts at AC-15
● at 24 V
2A
● at 230 V
0.5 A
operational current of auxiliary contacts at DC-13
● at 24 V
1A
● at 60 V
0.15 A
● at 110 V
0A
● at 125 V
0A
● at 220 V
0A
Protective and monitoring functions
product function
● ground fault detection
No
● phase failure detection
Yes
trip class
CLASS 10
design of the overload release
thermal
maximum short-circuit current breaking capacity (Icu)
● at AC at 240 V rated value
100 kA
● at AC at 400 V rated value
100 kA
● at AC at 500 V rated value
10 kA
● at AC at 690 V rated value
6 kA
operating short-circuit current breaking capacity (Ics) at AC
● at 240 V rated value
100 kA
● at 400 V rated value
50 kA
● at 500 V rated value
8 kA
● at 690 V rated value
4 kA
response value current of instantaneous short-circuit trip unit
1 040 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
77 A
● at 600 V rated value
77 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
7.5 hp
— at 230 V rated value
15 hp
● for 3-phase AC motor
— at 200/208 V rated value
25 hp
— at 220/230 V rated value
30 hp
— at 460/480 V rated value
60 hp
— at 575/600 V rated value
75 hp
contact rating of auxiliary contacts according to UL
C300 / R300
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
design of the fuse link
● for short-circuit protection of the auxiliary switch required
fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)
design of the fuse link for IT network for short-circuit
protection of the main circuit
3RV20324RA15
Page 2/6
4/19/2024
Subject to change without notice
© Copyright Siemens
● at 240 V
none required
● at 400 V
160
● at 500 V
125
● at 690 V
100
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
height
140 mm
width
55 mm
depth
149 mm
required spacing
● with side-by-side mounting at the side
0 mm
● for grounded parts at 400 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for live parts at 400 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for grounded parts at 500 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for live parts at 500 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for grounded parts at 690 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for live parts at 690 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
screw-type terminals
arrangement of electrical connectors for main current
circuit
Top and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded
2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
— finely stranded with core end processing
2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
● for AWG cables for main contacts
2x (18 ... 2), 1x (18 ... 1)
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● for AWG cables for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14)
tightening torque
● for main contacts with screw-type terminals
3 ... 4.5 N·m
● for auxiliary contacts with screw-type terminals
0.8 ... 1.2 N·m
design of screwdriver shaft
Diameter 5 to 6 mm
size of the screwdriver tip
Pozidriv size 2
design of the thread of the connection screw
● for main contacts
M6
● of the auxiliary and control contacts
M3
Safety related data
3RV20324RA15
Page 3/6
4/19/2024
Subject to change without notice
© Copyright Siemens
product function suitable for safety function
Yes
suitability for use
● safety-related switching on
No
● safety-related switching OFF
Yes
service life maximum
10 a
test wear-related service life necessary
Yes
proportion of dangerous failures
● with low demand rate according to SN 31920
40 %
● with high demand rate according to SN 31920
50 %
B10 value with high demand rate according to SN 31920
5 000
failure rate [FIT] with low demand rate according to SN
31920
50 FIT
ISO 13849
device type according to ISO 13849-1
3
overdimensioning according to ISO 13849-2 necessary
Yes
IEC 61508
safety device type according to IEC 61508-2
Type A
T1 value
● for proof test interval or service life according to IEC
61508
10 a
Electrical Safety
protection class IP on the front according to IEC 60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
Display
display version for switching status
Handle
Approvals Certificates
General Product Approval
Confirmation
General Product Approval
For use in hazardous locations
KC
Test Certificates
Special Test Certificate
Marine / Shipping
Type Test Certificates/Test Report
Marine / Shipping
other
Miscellaneous
other
Confirmation
Railway
Environment
Special Test Certificate
Confirmation
Environment
Environmental Confirmations
3RV20324RA15
Page 4/6
4/19/2024
Subject to change without notice
© Copyright Siemens
Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2032-4RA15
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2032-4RA15
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2032-4RA15
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2032-4RA15&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2032-4RA15/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2032-4RA15&objecttype=14&gridview=view1
3RV20324RA15
Page 5/6
4/19/2024
Subject to change without notice
© Copyright Siemens
13
21
14
22
5/L3
3/L2
1/L1
-F
last modified:
3RV20324RA15
Page 6/6
I>
6/T3
I>
4/T2
2/T1
I>
4/12/2024
4/19/2024
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RV2032-4RA15”相匹配的价格&库存,您可以联系我们找货
免费人工找货