Data sheet
3RV2331-4KC10
Circuit breaker size S2 for starter combination Rated current 73 A Nrelease 949 A screw terminal Standard switching capacity
product brand name
SIRIUS
product designation
Circuit breaker
design of the product
For starter combinations
product type designation
3RV2
General technical data
size of the circuit-breaker
S2
size of contactor can be combined company-specific
S2
product extension auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
29.5 W
● at AC in hot operating state per pole
9.8 W
insulation voltage with degree of pollution 3 at AC rated
value
690 V
surge voltage resistance rated value
6 kV
maximum permissible voltage for safe isolation in
networks with grounded star point
● between main and auxiliary circuit
400 V
● between main and auxiliary circuit
400 V
shock resistance acc. to IEC 60068-2-27
25g / 11 ms Sinus
mechanical service life (switching cycles)
● of the main contacts typical
20 000
● of auxiliary contacts typical
20 000
electrical endurance (switching cycles) typical
20 000
reference code acc. to IEC 81346-2
Q
Substance Prohibitance (Date)
01.03.2017 00:00:00
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
● ambient temperature during operation
-20 ... +60 °C
● ambient temperature during storage
-50 ... +80 °C
● ambient temperature during transport
-50 ... +80 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
● operating voltage rated value
690 V
● operating voltage at AC-3 rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current rated value
73 A
3RV23314KC10
Page 1/2
1.21.2021
Subject to change without notice
© Copyright Siemens
operational current at AC-3 at 400 V rated value
73 A
operating power at AC-3
● at 230 V rated value
22 000 W
● at 400 V rated value
37 000 W
● at 500 V rated value
45 000 W
● at 690 V rated value
55 000 W
operating frequency at AC-3 maximum
15 1/h
Auxiliary circuit
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
0
Protective and monitoring functions
product function
● ground fault detection
No
● phase failure detection
No
breaking capacity operating short-circuit current (Ics)
at AC
● at 240 V rated value
100 kA
● at 400 V rated value
30 kA
● at 500 V rated value
5 kA
● at 690 V rated value
2 kA
breaking capacity maximum short-circuit current (Icu)
● at AC at 240 V rated value
100 kA
● at AC at 400 V rated value
65 kA
● at AC at 500 V rated value
8 kA
● at AC at 690 V rated value
4 kA
response value current of instantaneous short-circuit trip
unit
949 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
65 A
● at 600 V rated value
62 A
yielded mechanical performance [hp]
● for 3-phase AC motor
— at 200/208 V rated value
20 hp
— at 220/230 V rated value
25 hp
— at 460/480 V rated value
50 hp
— at 575/600 V rated value
60 hp
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 240 V
none required
● at 400 V
160
● at 500 V
125
● at 690 V
100
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height
140 mm
width
55 mm
depth
149 mm
required spacing
● for grounded parts at 400 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for live parts at 400 V
3RV23314KC10
Page 2/3
1.21.2021
Subject to change without notice
© Copyright Siemens
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for grounded parts at 500 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for live parts at 500 V
— downwards
50 mm
— upwards
50 mm
— at the side
10 mm
● for grounded parts at 690 V
— downwards
50 mm
— upwards
50 mm
— backwards
0 mm
— at the side
10 mm
— forwards
0 mm
● for live parts at 690 V
— downwards
50 mm
— upwards
50 mm
— backwards
0 mm
— at the side
10 mm
— forwards
0 mm
Connections/ Terminals
product function removable terminal for auxiliary and
control circuit
No
type of electrical connection
● for main current circuit
arrangement of electrical connectors for main current
circuit
screw-type terminals
Top and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded
2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
— finely stranded with core end processing
2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
● at AWG cables for main contacts
2x (18 ... 2), 1x (18 ... 1)
● tightening torque for main contacts with screw-type
terminals
3 ... 4.5 N·m
design of screwdriver shaft
Diameter 5 to 6 mm
size of the screwdriver tip
Pozidriv 2
design of the thread of the connection screw
● for main contacts
M6
Safety related data
B10 value
● with high demand rate acc. to SN 31920
5 000
proportion of dangerous failures
● with low demand rate acc. to SN 31920
50 %
● with high demand rate acc. to SN 31920
50 %
failure rate [FIT]
● with low demand rate acc. to SN 31920
50 FIT
T1 value for proof test interval or service life acc. to
IEC 61508
10 y
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe, for vertical contact from the front
display version for switching status
Handle
Certificates/ approvals
Declaration of
Conformity
General Product Approval
3RV23314KC10
Page 3/4
1.21.2021
Subject to change without notice
© Copyright Siemens
KC
Declaration of
Conformity
Test Certificates
Type Test
Certificates/Test
Report
Miscellaneous
Marine / Shipping
Special Test
Certificate
Marine / Shipping
other
Confirmation
Railway
Vibration and Shock
Confirmation
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2331-4KC10
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2331-4KC10
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2331-4KC10
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2331-4KC10&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2331-4KC10/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2331-4KC10&objecttype=14&gridview=view1
3RV23314KC10
Page 4/5
1.21.2021
Subject to change without notice
© Copyright Siemens
3RV23314KC10
Page 5/6
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RV23314KC10
Page 6/6
12/15/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RV23314KC10”相匹配的价格&库存,您可以联系我们找货