Data sheet
3RV2421-4DA10
Circuit breaker size S0 for transformer protection A-release 18...25 A Nrelease 400 A screw terminal Standard switching capacity
product brand name
SIRIUS
product designation
Circuit breaker
design of the product
For transformer protection
product type designation
3RV2
General technical data
size of the circuit-breaker
S0
size of contactor can be combined company-specific
S00, S0
product extension auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
10.5 W
● at AC in hot operating state per pole
3.5 W
insulation voltage with degree of pollution 3 at AC rated
value
690 V
surge voltage resistance rated value
6 kV
maximum permissible voltage for safe isolation in
networks with grounded star point
● between main and auxiliary circuit
400 V
● between main and auxiliary circuit
400 V
shock resistance acc. to IEC 60068-2-27
25g / 11 ms
mechanical service life (switching cycles)
● of the main contacts typical
100 000
● of auxiliary contacts typical
100 000
electrical endurance (switching cycles) typical
100 000
reference code acc. to IEC 81346-2
Q
Substance Prohibitance (Date)
01.10.2009 00:00:00
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
● ambient temperature during operation
-20 ... +60 °C
● ambient temperature during storage
-50 ... +80 °C
● ambient temperature during transport
-50 ... +80 °C
temperature compensation
-20 ... +60 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the
current-dependent overload release
18 ... 25 A
● operating voltage rated value
690 V
● operating voltage at AC-3 rated value maximum
690 V
3RV24214DA10
Page 1/2
1.20.2021
Subject to change without notice
© Copyright Siemens
operating frequency rated value
50 ... 60 Hz
operational current rated value
25 A
operational current at AC-3 at 400 V rated value
25 A
operating power at AC-3
● at 230 V rated value
5 500 W
● at 400 V rated value
11 000 W
● at 500 V rated value
15 000 W
● at 690 V rated value
22 000 W
operating frequency at AC-3 maximum
15 1/h
Auxiliary circuit
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
0
number of CO contacts for auxiliary contacts
0
Protective and monitoring functions
product function
● ground fault detection
No
● phase failure detection
Yes
trip class
CLASS 10
design of the overload release
thermal
breaking capacity operating short-circuit current (Ics)
at AC
● at 240 V rated value
100 kA
● at 400 V rated value
25 kA
● at 500 V rated value
5 kA
● at 690 V rated value
2 kA
breaking capacity maximum short-circuit current (Icu)
● at AC at 240 V rated value
100 kA
● at AC at 400 V rated value
55 kA
● at AC at 500 V rated value
10 kA
● at AC at 690 V rated value
4 kA
response value current of instantaneous short-circuit trip
unit
400 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
25 A
● at 600 V rated value
25 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
2 hp
— at 230 V rated value
3 hp
● for 3-phase AC motor
— at 200/208 V rated value
5 hp
— at 220/230 V rated value
7.5 hp
— at 460/480 V rated value
15 hp
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 400 V
gL/gG 63 A
● at 500 V
gL/gG 50 A
● at 690 V
gL/gG 50 A
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height
97 mm
width
45 mm
depth
97 mm
3RV24214DA10
Page 2/3
1.20.2021
Subject to change without notice
© Copyright Siemens
required spacing
● for grounded parts at 400 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for live parts at 400 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for grounded parts at 500 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for live parts at 500 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for grounded parts at 690 V
— downwards
50 mm
— upwards
50 mm
— backwards
0 mm
— at the side
30 mm
— forwards
0 mm
● for live parts at 690 V
— downwards
50 mm
— upwards
50 mm
— backwards
0 mm
— at the side
30 mm
— forwards
0 mm
Connections/ Terminals
product function removable terminal for auxiliary and
control circuit
No
type of electrical connection
● for main current circuit
arrangement of electrical connectors for main current
circuit
screw-type terminals
Top and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded
2x (1 ... 2,5 mm²), 2x (2,5 ... 10 mm²)
— finely stranded with core end processing
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
● at AWG cables for main contacts
2x (16 ... 12), 2x (14 ... 8)
● tightening torque for main contacts with screw-type
terminals
2 ... 2.5 N·m
design of screwdriver shaft
Diameter 5 to 6 mm
size of the screwdriver tip
Pozidriv 2
design of the thread of the connection screw
● for main contacts
M4
Safety related data
B10 value
● with high demand rate acc. to SN 31920
5 000
proportion of dangerous failures
● with low demand rate acc. to SN 31920
50 %
● with high demand rate acc. to SN 31920
50 %
failure rate [FIT]
● with low demand rate acc. to SN 31920
50 FIT
T1 value for proof test interval or service life acc. to
IEC 61508
10 y
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe, for vertical contact from the front
3RV24214DA10
Page 3/4
1.20.2021
Subject to change without notice
© Copyright Siemens
display version for switching status
Handle
Certificates/ approvals
Declaration of
Conformity
General Product Approval
KC
Declaration of
Conformity
Test Certificates
Special Test
Certificate
Miscellaneous
Marine / Shipping
Type Test
Certificates/Test
Report
Marine / Shipping
other
Confirmation
Railway
Confirmation
Vibration and Shock
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2421-4DA10
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2421-4DA10
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2421-4DA10
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2421-4DA10&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2421-4DA10/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2421-4DA10&objecttype=14&gridview=view1
3RV24214DA10
Page 4/5
1.20.2021
Subject to change without notice
© Copyright Siemens
3RV24214DA10
Page 5/6
1.20.2021
Subject to change without notice
© Copyright Siemens
3RV24214DA10
Page 6/7
1.20.2021
Subject to change without notice
© Copyright Siemens
last modified:
3RV24214DA10
Page 7/7
12/15/2020